Looks like no tags are added yet.
2 x diameter
Minimum air gap for fixtures not affected by side walls in reference to effective opening. (minus 1 for 13mm less, plus I for 25mm less)
3 x diameter
Minimum air gap for fixtures affected by side walls in reference to effective opening. (minus 1 for 13mm less, plus I for 25mm less)
0 to 63.5 cm
Airgap less than 25mm shall only be approved if tested with vacuums of mercury from _____.
150 mm
Minimum distance of Atmospheric Vacuum Breaker (AVB) above all downstream piping and floor level rim of receptor.
30.5 cm
Minimum space clearance between the lowest portion of the assembly and the grade, floor or platform for access and clearance.
30.5 cm
Minimum distance of Double Check Valve assembly above all downstream piping and floor level rim of receptor.
152 mm
Minimum distance of Spill
1.52m
Elevation of installations above the floor or grade to bc provided with a permanent platform.
25 mm
Minimum air gap for water distribution, or a minimum of 2 pipe diameters.
152 mm
Installation of atmospheric vacuum breaker above the flood level rim.
43.3 oC
Minimum temperature for backflow prevention device to operate without rendering any portion inoperative.
152 mm
Minimum height of the AVB critical level above the overflow rim of a water closet bowl or the highest part of a urinal.
25 mm
Minimum height of ballcock 's critical level above the full opening of the overflow pipe.
152 mm
Minimum installation height of listed non
51 mm or smaller
Size of cast iron fittings to be galvanized when used in water piping.
8%
Maximum lead content for water pipes and fittings.
14 to 18
Number of mesh per 25 mm for gravity tanks vent screen.
less than 103 kPa
Inadequate water pressure
more than 551 kPa
Excessive water pressure
80%
Percentage of the reduced pressure used for all pipe size determination.
1033 kPa
Maximum pressure setting of pressure relief valve.
152 mm to 600 mm
Height of the drain pipe of pressure relief valve above the ground and pointing downward.
0.30m
Distance between bottom of water pipe and top of the sewer or drain line.
0.30m
Horizontal distance between the water line and the sewer or drain line.
0.30m
Distance between sewer or drainage piping and water pipes crossing above such drainage pipes.
0.30m
Maximum distance of unions away from regulating equipment, water heater, conditioning tank or similar.
4 feet (1219 mm)
Maximum intervals of piping supports
3 feet (914 mm)
Support trap arms more than ____ length shall be as close as possible.
¼ inch
Closet rings shall be tightly fastened up to the floor with top surface ______ above finish floor.
19 mm diameter
Minimum size of water service Pipe.
13 mm diameter
Minimum size of building supply and branches
at least 0.3m below
All water service yard piping shall be ________ the finish ground level.
Unions
shall be installed in the water supply piping within 0.3m away from regulating equipment, water heater, conditioning tanks & similar equipment which require removal for servicing or replacement.