RNPCP - CHAPTER 06 WATER SUPPLY AND DISTRIBUTION

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/33

encourage image

There's no tags or description

Looks like no tags are added yet.

34 Terms

1
New cards

2 x diameter

Minimum air gap for fixtures not affected by side walls in reference to effective opening. (minus 1 for 13mm less, plus I for 25mm less)

2
New cards

3 x diameter

Minimum air gap for fixtures affected by side walls in reference to effective opening. (minus 1 for 13mm less, plus I for 25mm less)

3
New cards

0 to 63.5 cm

Airgap less than 25mm shall only be approved if tested with vacuums of mercury from _____.

4
New cards

150 mm

Minimum distance of Atmospheric Vacuum Breaker (AVB) above all downstream piping and floor level rim of receptor.

5
New cards

30.5 cm

Minimum space clearance between the lowest portion of the assembly and the grade, floor or platform for access and clearance.

6
New cards

30.5 cm

Minimum distance of Double Check Valve assembly above all downstream piping and floor level rim of receptor.

7
New cards

152 mm

Minimum distance of Spill

8
New cards

1.52m

Elevation of installations above the floor or grade to bc provided with a permanent platform.

9
New cards

25 mm

Minimum air gap for water distribution, or a minimum of 2 pipe diameters.

10
New cards

152 mm

Installation of atmospheric vacuum breaker above the flood level rim.

11
New cards

43.3 oC

Minimum temperature for backflow prevention device to operate without rendering any portion inoperative.

12
New cards

152 mm

Minimum height of the AVB critical level above the overflow rim of a water closet bowl or the highest part of a urinal.

13
New cards

25 mm

Minimum height of ballcock 's critical level above the full opening of the overflow pipe.

14
New cards

152 mm

Minimum installation height of listed non

15
New cards

51 mm or smaller

Size of cast iron fittings to be galvanized when used in water piping.

16
New cards

8%

Maximum lead content for water pipes and fittings.

17
New cards

14 to 18

Number of mesh per 25 mm for gravity tanks vent screen.

18
New cards

less than 103 kPa

Inadequate water pressure

19
New cards

more than 551 kPa

Excessive water pressure

20
New cards

80%

Percentage of the reduced pressure used for all pipe size determination.

21
New cards

1033 kPa

Maximum pressure setting of pressure relief valve.

22
New cards

152 mm to 600 mm

Height of the drain pipe of pressure relief valve above the ground and pointing downward.

23
New cards

0.30m

Distance between bottom of water pipe and top of the sewer or drain line.

24
New cards

0.30m

Horizontal distance between the water line and the sewer or drain line.

25
New cards

0.30m

Distance between sewer or drainage piping and water pipes crossing above such drainage pipes.

26
New cards

0.30m

Maximum distance of unions away from regulating equipment, water heater, conditioning tank or similar.

27
New cards

4 feet (1219 mm)

Maximum intervals of piping supports

28
New cards

3 feet (914 mm)

Support trap arms more than ____ length shall be as close as possible.

29
New cards

¼ inch

Closet rings shall be tightly fastened up to the floor with top surface ______ above finish floor.

30
New cards

19 mm diameter

Minimum size of water service Pipe.

31
New cards

13 mm diameter

Minimum size of building supply and branches

32
New cards

at least 0.3m below

All water service yard piping shall be ________ the finish ground level.

33
New cards

Unions

shall be installed in the water supply piping within 0.3m away from regulating equipment, water heater, conditioning tanks & similar equipment which require removal for servicing or replacement.

34
New cards