1/156
Looks like no tags are added yet.
What does ASHRAE Standard 34 classify?
Refrigerants according to toxicity and flammability.
What is ASHRAE Class A?
Lower toxicity.
What is ASHRAE Class B?
Higher toxicity.
What does Flammability Class 1 indicate?
No flame propagation.
What does Flammability Class 2L indicate?
Lower flammability with slow burning velocity.
What does Flammability Class 2 indicate?
Flammable.
What does Flammability Class 3 indicate?
Higher flammability.
What are examples of A1 refrigerants?
R-22, R-134a, and R-410A.
What are examples of A2L refrigerants?
R-32, R-454B, and R-1234yf.
What is an example of an A2 refrigerant?
R-152a.
What are examples of A3 refrigerants?
R-290 and R-600a.
What is an example of a B1 refrigerant?
R-123.
What is an example of a B2L refrigerant?
R-717 ammonia.
What is R-290?
Propane.
What is R-600a?
Isobutane.
What is R-717?
Ammonia.
What is R-744?
Carbon dioxide.
What is the maximum burning velocity for A2L refrigerants?
10 cm/s.
What is the heat of combustion criterion for A2L refrigerants?
Below 8,169 BTU/lb.
What does GWP stand for?
Global warming potential.
What does ODP stand for?
Ozone depletion potential.
What is the reference GWP of carbon dioxide?
1.
What is the GWP of R-410A?
2088.
What is the GWP of R-404A?
3920.
What is the GWP of R-32?
675.
What is the GWP of R-290?
3.
What is the GWP of R-600a?
3.
What is the GWP of R-1234yf?
Less than 1.
Which refrigerant families contain chlorine?
CFCs and HCFCs.
What does HFC stand for?
Hydrofluorocarbon.
What does HFO stand for?
Hydrofluoroolefin.
What do hydrocarbon refrigerants contain?
Hydrogen and carbon.
Does low GWP mean low flammability?
No.
What is the function of a compressor?
Compresses low-pressure vapor into high-pressure, high-temperature vapor.
What is the function of a condenser?
Rejects heat and condenses refrigerant vapor into liquid.
What does a metering device do?
Reduces refrigerant pressure and regulates flow into the evaporator.
What is the function of an evaporator?
Absorbs heat and boils liquid refrigerant into vapor.
What does a filter drier do?
Removes moisture and particulate contamination.
What is the function of a receiver?
Stores liquid refrigerant as operating load changes.
What does an accumulator do?
Prevents liquid refrigerant from entering the compressor.
Where is the accumulator located?
Suction line before the compressor.
What are examples of fixed metering devices?
Pistons and capillary tubes.
What are examples of adjustable metering devices?
TXVs, EEVs, and AEVs.
What is sensible heat?
Heat that changes temperature without changing state.
What is latent heat?
Heat associated with a change of state.
What is saturation?
Condition in which liquid and vapor coexist.
What does a pressure-temperature chart do?
Converts refrigerant pressure to its corresponding saturation temperature.
What is the superheat formula?
Actual vapor-line temperature minus low-side saturation temperature.
What is the subcooling formula?
High-side saturation temperature minus actual liquid-line temperature.
What is the superheat example for a 58°F line and 51°F saturation?
7°F.
What is the subcooling example for a 114°F saturation and 100°F line?
14°F.
What is an azeotropic blend?
A blend that behaves like a single-compound refrigerant.
What series is the azeotropic refrigerant?
500 series.
What is a zeotropic blend?
A refrigerant blend that can fractionate and exhibits temperature glide.
What series is the zeotropic refrigerant?
400 series.
What is a near-azeotropic blend?
A zeotropic blend with very little temperature glide.
What is fractionation?
Separation of blend components at different rates, changing refrigerant composition.
What is temperature glide?
Difference between bubble-point and dew-point temperatures at the same pressure.
What is the bubble point?
Saturated-liquid temperature.
What is the dew point?
Saturated-vapor temperature.
Which point is used for superheat?
Dew point.
Which point is used for subcooling?
Bubble point.
How are zeotropic blends withdrawn from a cylinder?
As liquid to prevent fractionation.
How may azeotropic blends be charged?
As liquid or vapor.
What is the temperature glide of R-410A?
Approximately 0.3°F.
What is a binary blend?
Contains two refrigerant components.
What is a ternary blend?
Contains three refrigerant components.
What is the evaporator midpoint formula?
(Bubble temperature × 0.40) + (Dew temperature × 0.60).
What is the condenser midpoint formula?
(Dew temperature + Bubble temperature) ÷ 2.
What is the standard comfort-cooling airflow?
400 CFM per ton.
What is the high-humidity airflow?
325-350 CFM per ton.
What is the high sensible-load airflow?
425-450 CFM per ton.
What is the typical supply-to-return temperature split?
16-22°F.
What is the typical evaporator coil temperature?
40-45°F.
What is the effect of a dirty condenser?
Restricts airflow and reduces heat rejection.
What is mitigation in refrigerant management?
Measures that reduce the likelihood of refrigerant accumulation or ignition.
What does an active refrigerant sensor do?
Detects refrigerant leaks and may initiate mitigation controls.
Why may a blower operate during an A2L leak?
To dilute the refrigerant concentration.
What is miscibility?
Ability of refrigerant and oil to mix.
What does hygroscopic mean?
Ability to absorb moisture from air.
What is hydrolysis?
Reaction involving water that can degrade POE oil and produce acids and sludge.
What is mineral oil (MO)?
Petroleum-derived oil containing wax, used mainly with CFCs and some HCFCs.
What is alkylbenzene oil (AB)?
Synthetic wax-free oil used in certain R-22 and retrofit applications.
What is polyol ester oil (POE)?
Very hygroscopic synthetic oil commonly used with HFCs and HFOs.
What is polyvinyl ether oil (PVE)?
Synthetic oil used in some HFC systems that does not undergo POE-type hydrolysis.
What is polyalkylene glycol oil (PAG)?
Extremely hygroscopic oil primarily used in automotive air conditioning.
What is polyalkylene glycol oil (PAG) primarily used for?
Automotive air conditioning.
What is the recommended oil exposure time?
Approximately 15 minutes.
Can evacuation remove all moisture from heavily contaminated oil?
Not necessarily; contaminated oil may require replacement.
What gas is used for pressure testing?
Dry nitrogen.
Why is dry nitrogen used for pressure testing?
It is an inert gas.
How is leak-test pressure determined?
Use the lowest applicable component test-pressure limit and manufacturer instructions.
What can a pressure drop during leak testing indicate?
A leak, after accounting for temperature changes.
What is the right gauge on the nitrogen regulator?
Tank pressure.
What is the left gauge on the nitrogen regulator?
Outlet pressure.
What are the four leak detection methods?
Ultrasonic detector, bubble solution, trace gas, and electronic leak detector.
What is the flammable refrigerant trace-gas limit?
25% of the lower flammability limit.
What is the response to a flammable refrigerant leak?
Vacate, safely ventilate, and verify the area is safe before service.
What is recovery in refrigerant handling?
Removing refrigerant from a system and storing it in an approved cylinder.
What is recycling in refrigerant handling?
Cleaning recovered refrigerant for permitted reuse.