What is the effect of an oversized heating and cooling system?

Moisture damage to a furnace heat exchanger and inadequate humidity removal during cooling cycles

2
New cards

When the inside and outside temperature of a structure are equal, there is;

No heat transfer

3
New cards

Heat moves at a rate relative to;

the temperature difference between hot to cold

4
New cards

Radiant heat travels from a source;

by electromagnetic waves from the source

5
New cards

Doubling the thickness of an insulating material while maintaining temperature difference, the rate of heat transfer will be;

One half

6
New cards

Thermal conductivity is defined as;

Heat transfer through a specific mass of material over a given time

7
New cards

When performing a load calculation, which building walls are most affected by solar gain in the northern hemisphere?

South, East and West

8
New cards

Convection heat transfer occurs when;

Fluids at different temperatures flow within a given space

9
New cards

Forced convection occurs when;

A ceiling fan pushes warmer air down to the living area

10
New cards

Radiant heat;

Travels outward from its source in straight lines at the speed of light (186,000 mi/s)

11
New cards

What are heat transmission losses?

Heat transferred through walls, glass, ceiling, floor or other surfaces

12
New cards

Approximately how much sensible heat and latent does the human body produce when resting?

300-500 BTU

13
New cards

An area of an external wall which allows light to pass through is referred to as;

fenestration

14
New cards

As a building’s sensible cooling loads go down, the run time of the air conditioner becomes shorter. A short-cycling air conditioner runs only long enough to satisfy the thermostat and may not adequately address;

Humidity control

15
New cards

The normal sequence to calculate the cumulative conductivity for a cross section of building materials;

Look up the R-value for each material in the building cross-section, add these values, and then take the reciprocal of that answer to get the U-factor

16
New cards

What are heat infiltration losses?

Uncontrolled outdoor air leaking into the occupied space from cracks and crevices through the building envelope during the cooling operation

17
New cards

To calculate the rate of heat loss, what three factors must be known?

The total area of exposed surface of the plane, the U-value for the construction plane, and the temperature difference from one side to other side of the construction plane

18
New cards

The inverse of “U” value is;

R value

19
New cards

The term Building Envelope is;

Any part of the building enclosure that has thermal boundary conditions between the interior and exterior of the building

20
New cards

Which of the following best describes R-value?

The rating of thermal resistance for a material. The higher the rating number the slower heat passes through it when the temperature difference is maintained across it

21
New cards

Which of the following has the lowest R value?

Drywall (U = 20)

22
New cards

The R-value for building materials used in residential construction increases directly proportionate to the;

Thickness of the material

23
New cards

Three basic types of insulation are;

Fiber, reflective and foam

24
New cards

Reflective foil insulation will conduct to the next solid layer and have an equivalent R-value of zero unless there is;

an air gap between the foil layers

25
New cards

Moisture control within the wall cavity is very important because damp insulation has;

Reduced insulating value

26
New cards

Temperature difference between the inside and outside of a structure and “R” value are;

factors effecting heat loss and gain calculations

27
New cards

When sizing an air conditioner, what critical information must be known?

Calculated sensible and latent loads

28
New cards

Outer elements of a building, such as walls, windows, doors, roofs, and floors, including those having contact with earth is the ASHRAE definition of;

Building envelope

29
New cards

Hot and cold spots are caused by;

Inconsistencies in construction, materials, thermal bridges (highly conductive material ex: metal frame), breaks (missed insulation), settling of materials, and quality of workmanship

30
New cards

What document gives the designer an opportunity to see if any of the calculated values are out of line?

The heat gain/loss summary

31
New cards

During the process of calculating the heating loads of a building, you must first;

Identify the heating zones within the building

32
New cards

Transmission Heat Loss is;

Heat transferred through confining walls, glass, ceiling, floor, or other surfaces

33
New cards

A basement interior is considered conditioned space if;

A minimum of 50 degrees F is maintained over heating season

34
New cards

Spray foam insulation can be effectively used for sealing;

Open cavities around ducts, pipes, and electrical wiring that pass through the building envelope

35
New cards

What are 3 types of batt insulation?

Fiberglass, cotton, and rock wool

36
New cards

The effectiveness of an envelope’s ability to perform as expected depends on the;

Quality of workmanship and materials used

37
New cards

For heating, heat gain from the sun and internal sources within the building are;

Neglected when doing heating load calculations because they are not dependable heat sources

38
New cards

Which of the following is considered an Infiltration load?

Outdoor air leaking in (requires extra energy to condition)

39
New cards

Which of the following is an example of a thermal break?

A non-conducting frame around a door or window acting to retard heat flow

40
New cards

What will non-uniform distribution from settling insulation in an attic cause?

reduction in insulating value and effectiveness

41
New cards

One nondestructive way to check a wall for insulation is to;

Look around the sides and/or behind an electrical outlet on an exterior wall

42
New cards

The National Fenestration Rating Council (NFRC) energy performance label can help you determine how well a product will;

Reduce the building heat gain in the summer, reduce the building heat loss in the winter, keep out wind, and resist condensation

43
New cards

Low Emittance (E) Glass is;

Glass which has low emissivity (ability to radiate thermal energy) due to a film or metallic coating on the glass

44
New cards

The construction features needed to calculate basement heat loss are;

Above-grade wall, below-grade wall, and basement floor

45
New cards

The terms awning, bay, and bow casement refer to;

types of windows

46
New cards

When the outside temperature or wind speed changes;

The rate of heat loss or gain changes

47
New cards

Local geography and microclimatic conditions often result in significant differences between;

Any given site and the nearest reported weather station

48
New cards

Elevation changes greater than a few hundred feet can;

Significantly change the design conditions

49
New cards

When calculating thermal loss or gain;

Fractional measurements are usually rounded to the next or nearest whole number

50
New cards

The outside surface of a building has a strong effect on how much solar energy gets absorbed or reflected. Which of the following has the greatest effect?

direction and material

51
New cards

When calculating the heating load for a zone, which of the following should be used?

identify the exposed surfaces by directions, type, and net area of each surface

52
New cards

Glass with a textured surface which provides low visibility and allows in natural light is called;

obscure glass

53
New cards

The ability of a window to absorb certain types of energy and radiate that energy through itself and out of a room is called;

emissivity

54
New cards

Using a blueprint with a scale of ¼ inch = 1 foot and you measure 8 ¾ for an exterior wall with a ruler. What is the actual length of the wall?

35 feet

55
New cards

Windows featuring a hinged sash that uses a crank to swing out left or right are called;

casement

56
New cards

A window designed for sloped or horizontal installation in the roof of a residential building to provide day-lighting and/or ventilation and may be fixed or operable are called;

skylight window

57
New cards

The blueprint scale is 3/16 inch = 1 foot, and the measurement is 1 3/8 inch, what is the actual length?

7 feet 4 inches

58
New cards

When selecting equipment cooling capacity for a load performed with a 80 degree outdoor design temperature, what must be done to the equipment rating?

The equipment rating would need to be increased

59
New cards

The blueprint scale is 1/8 inch = 1 foot and the measurement in ½ inch, what is the actual length?

4 feet

60
New cards

A resident with a heat loss of 60,000 BTU at a 30 degree outdoor design condition would have a _____ BTU heat loss at 20 degrees

80,000 BTU

61
New cards

What is the shorthand term for the difference between two temperatures?

Delta T

62
New cards

When installing zones for heating and cooling;

Each zone should have its own thermostat or sensor

63
New cards

The Set Point (inside temperature) = 70F and the outside temperature = 60F. If the outside temperature changes to 50F, what happens to the rate of heat transfer?

The temperature difference doubles so the rate of heat transfer doubles

64
New cards

The design cooling load is an estimate of the rate at which a building gains heat;

based on the design outdoor temperature

65
New cards

Typical values of air change rates range from;

0.5 for new construction to 1.0 air changes per hour for leaky, older buildings

66
New cards

Estimating the rate of infiltration air is difficult, because it depends on the;

quality of construction, age of the structure, direction and strength of wind

67
New cards

Ventilation is important to the home owner becuase;

Too little ventilation may result in improper equipment size and poor indoor air quality

68
New cards

Ventilation air should be;

Provided to conditioned rooms through mechanical and/or natural air distribution

69
New cards

A satisfactory ventilation system will provide supply air with these characteristics;

Minimal impurities or pollutants, comfortable temperatures, low flow rate and reduced noise

70
New cards

To control comfort level and efficiency, it is necessary to control the rate of ventilation air;

Based on the number of occupants, size of the building and infiltration rate

71
New cards

What is blower door test equipment used for?

A testing apparatus used for measuring building envelope air tightness

72
New cards

Negative pressures in the lower levels of a structure and positive pressure in the upper levels are caused by;

Stack effect from building height

73
New cards

What are some wind pathways for air penetration during heating season?

Through connections at a foundation/wall, floor/wall, wall/window, wall/roof, and through materials such as concrete blocks and mortar joints.

74
New cards

The purpose of a home air conditioner is to move heat from inside the home to the outside by;

Absorbing the heat from the inside air into the evaporator

75
New cards

A simple thermostat controlling the air conditioner’s function senses;

sensible heat

76
New cards

The total CFM required for an air conditioning system is determined by the;

sensible heat load

77
New cards

An oversized air conditioner runs only long enough to satisfy the temperature and may not adequately address;

humidity issues

78
New cards

The amount of building air leakage at specific pressures, or an equivalent leakage area can be found with which of the following?

blower-door tester

79
New cards

Supply ducts can only be sized by knowing;

system static pressure, velocity, and CFM for individual rooms

80
New cards

One ton of cooling is equal to how many BTU/h?

12,000 BTU/h

81
New cards

Find the heat gain for the exposed wall and knee-wall. The building is 20 ft wide with an exterior wall height of 8 ft. The roof has a 6 on 12 pitch, Insulation R-11, Outdoor Summer design 95F, Indoor design 70F, Attic Temerature 145F.


705 BTU/h

82
New cards

What is the perimeter in feet of exposed wall for the entire house provided?

172 ft

83
New cards

What is the total area of gross exposed walls of the provided house drawing if the ceiling height is 9 ft.?

1548 sq ft

84
New cards

What is the total area of windows located on the south side of the house in the drawing?

60 sq ft

85
New cards

What is the total square feet of gross windows used for calculating heat loss of the provided house drawing?

159 sq ft

86
New cards

Find the total glass area of the North side of the provided house drawing

36 sq ft

87
New cards

Find the total glass area on the East & West side of the provided house drawing

63 sq ft

88
New cards

Calculate the total BTU heat loss of all windows for the provided drawing. Windows are wood frame double pane, clear glass, with no external shading, winter design temperature outdoor 18F, winter design temperature indoor 68F, U-Value 0.99

7871 Total BTU

89
New cards

What is the total area of exterior doors, used for calculating heat gain and/or loss for the provided drawing?

38 sq ft

90
New cards

Calculate the total BTU loss for all hardwood floors from the provided drawing with the following specifications: Total R value = 30 over open crawl space. Outdoor winter design temperature 18F. Indoor winter design temperature 68F.

3010 BTU

91
New cards

Gross area of the floor for the provided drawing;

Is usually the same as the ceiling

92
New cards

If the floor plan indicated two bedrooms, how many people would be used in the calculation of heat gain?

3

93
New cards

Calculate BTU loss for windows on the south side based on solar and transmission with a HTM (heat transfer multiplier) of 52

3120 BTU

94
New cards

Calculate the total BTU loss for all exterior walls constructed using the following specifications and the dimensions from the provided drawing. Walls (Insulation R-11, ½ poly board R-2.5, 2×4 wood frame, brick exterior finish). Total R value equals 15.5. Winter design temperature outdoor = 18F. Winter design temperature indoor = 68F

5198 BTU

95
New cards

Calculate the BTU loss for the ceilings in the diagram provided;

4834 BTU

96
New cards

What is the total net area for the ceiling based on the provided diagram?

1824 sq ft

97
New cards

Calculate the total heat gain for the walls in the diagram provided;

2041 BTU/h

98
New cards

Calculate the total BTU gain for the Room 4 ceiling in the diagram provided;

915 BTU/h

99
New cards

Calculate the BTU heat gain for room 1 based on the diagram provided;

5803 BTU/h

100
New cards

Calculate sensible heat gain for the entire house based on the diagram provided;

15,943 BTU/h