RNPCP - CHAPTER 11 STORM DRAINAGE SYSTEM

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/21

encourage image

There's no tags or description

Looks like no tags are added yet.

22 Terms

1
New cards

GA 26

Minimum thickness of galvanized sheet metal for rainwater downspout or conductor.

2
New cards

0.6 meter

Rainwater piping commencing ______ from the exterior of a building may be suitable approved materials.

3
New cards

102 mm

Extension of roof drain strainers above the surface of the roof.

4
New cards

1.5x the area of outlet

Minimum total net inlet area of roof drain with dome

5
New cards

2x the area of outlet

Minimum total net inlet area of drain with roof deck strainers.

6
New cards

102 mm/hour

Rainfall intensity normally used around Manila area.

7
New cards

50%

Additional for area of 1 wall

8
New cards

35%

Additional for area of 2 adjacent walls

9
New cards

0%

Additional for area of 2 opposite walls

10
New cards

50%

Additional for side of tall building exposed to rain

11
New cards

0.392x diameter

When gutter has semi

12
New cards

0.8862x diameter

When gutter has semi

13
New cards

7/24 full

Basis of Table 11

14
New cards

3:1

Ratio of the side dimension of a rectangular vertical piping.

15
New cards

Rainwater Downspout or Conductor Pipings

placed within the interior side of the building inside a vertical pipe chase or run within a vent shaft shall be of Cast Iron, Ductile Iron, Galvanized Steel, Iron, Lead, Copper, Brass, Schedule 40, ABS, Series 1000 PVC DWV, or other approved materials.

16
New cards

Rainwater Downspout or Conductor

located on the exterior side of a low height building shall be not less than Ga. 26 galvanized sheet metal.

17
New cards

102mm

Strainers should not exceed _____ above the surface of the roof immediately adjacent to the drain

18
New cards

1 1/2 times

Dome

19
New cards

2 times

Roof Deck strainers shall have at least ______ the area of the outlet pipe to which it is connected.

20
New cards

50% of area

For 1 wall – add _____ of the wall to the roof area

21
New cards

35% of the total wall areas

For 2 adjacent walls – add ______ to the roof area.

22