1/25
Vocabulary practice flashcards covering technical protective measures against direct and indirect electrical contact, physiological effects of electric currents, and earthing distribution systems (TN, TT, and IT).
Electric Shock (Strujni udar)
The instant of contact with an energized conductor and the initial physiological impact of electric current experienced by a human being.

Direct Contact (Direktni dodir)
Accidental human contact with conductive parts of an installation or electrical load that are energized under normal operating conditions, such as bare conductors, fuse terminals, switches, and lamp sockets.
Indirect Contact (Indirektni dodir)
Human contact with exposed conductive parts of electrical equipment (such as metallic enclosures of motors, cookers, or boilers) that are not energized during normal operation, but become live due to an insulation breakdown.
Human Body Resistance Components
The total impedance opposing current flow through a human body, consisting of three elements: input contact resistance, internal body resistance, and output contact resistance.
Thermal Effect of Electric Current
The conversion of electrical energy into thermal energy within tissue resistance, elevating body temperature, destroying tissue, causing severe internal burns, fluid loss, and potentially charring.
Mechanical Effect of Electric Current
The physiological consequence of current passage producing violent involuntary muscle spasms and uncontrolled reflex movements, creating severe risks of falls and physical injury when working at heights.
Chemical Effect of Electric Current
The action occurring during the flow of direct current (DC) where the body fluids act as an electrolyte, causing permanent tissue damage through electrolytic decomposition.
Perception Threshold (1mA at 50Hz)
The lowest alternating current intensity detectable by the human body, producing the initial sensation of current flow and a slight muscle twitch.
Let-Go Threshold Current (Struja otpuštanja)
The maximum current limit at which an individual holding an energized conductor can still release their grip; defined as 10mA for women and 15mA for men at 50Hz.
Ventricular Fibrillation Threshold (100mA at 50Hz)
A lethal alternating current magnitude that triggers uncoordinated cardiac flutter (fibrillation) and heart failure when sustained through the body for longer than 1–2s (or 3s).
Protection by Insulation of Live Parts
A direct contact protection measure consisting of a durable insulating coating applied to energized conductors that cannot be removed without complete destruction; paints, clear varnishes, and enamels are not recognized as acceptable protective insulation.
Protection by Barriers or Enclosures
A direct contact prevention method enclosing energized parts in sturdy housings or partitions that can only be unlocked or dismantled using a dedicated key or tool following power disconnection.
Protection by Obstacles (Zapreke)
A safety provision designed to prevent unintentional physical approach or accidental touch of energized equipment during normal operation and maintenance, removable without tools but secured against accidental displacement.

Protection by Placing Out of Reach (Zaštita stavljanjem van dohvata ruke)
A measure ensuring that simultaneously accessible conductive parts at differing electrical potentials are separated beyond arm's reach, requiring a minimum vertical clearance of 2.5m and a horizontal clearance of 1.25m.
Residual Current Device (Zaštitna strujna sklopka - RCD / FI)
A protection device operating on the vector sum of currents in multi-phase systems; automatically disconnects supply in under 0.1s when differential fault current exceeds its rating (typically ≤30mA).

Class II Equipment (Oprema klase II)
Electrical devices that utilize double insulation (basic plus supplementary) or reinforced insulation to protect against indirect contact without connecting metallic enclosures to a protective earth (PE) conductor.
Protection by Non-Conducting Location (Izolirane prostorije)
An indirect contact prevention method using insulating floors and walls with a resistance of at least 50kΩ (for nominal voltages up to 500V) or 100kΩ (for nominal voltages above 500V) to prevent circuit completion through the ground.

Protection by Electrical Separation (Zaštita električnim odvajanjem)
An indirect contact safety measure using an isolating transformer (transformation ratio ≈1:1, primary voltage up to 500V) feeding a single electrical consumer (≤16A) with an ungrounded secondary circuit.
Supplementary Equipotential Bonding Criterion (Z≤IaUL)
The condition verifying the impedance (Z) between simultaneously accessible conductive parts, where UL is the permissible touch voltage and Ia is the tripping current of the protective device within a specified duration.
Main Equipotential Bonding (Glavno izjednačenje potencijala)
The permanent interconnection of the main earthing terminal with extraneous conductive parts of a building, including incoming water pipes, central heating/gas supply lines, structural steel, and lightning protection systems.
Earthing System Letter Codes
Classification codes where the first letter denotes the power source relation to earth (T = directly grounded neutral, I = isolated or high impedance), and the second letter denotes the equipment exposed parts relation to earth (T = directly earthed locally, N = directly linked to the grounded neutral point).

TN-C System
A sub-type of the TN grounding arrangement in which the neutral and protective functions are integrated into a single continuous conductor (PEN) throughout the entire network; prohibited in fire- and explosion-hazard zones.

TN-S System
A configuration known as dead-neutral grounding (bezstrujno nulovanje) where the neutral (N) and protective (PE) conductors are separated throughout the entire installation and interconnected solely at the source neutral point.
TN-C-S System
A distribution system where neutral and protective functions are combined in a single PEN conductor across the upstream supply and then split into distinct, completely separated N and PE conductors at an entry bonding point.

TT System
A network grounding scheme where the source neutral is directly grounded (RB) and all accessible conductive enclosures of consumer equipment are connected to independent local earth electrodes (RA).
IT System
An electrical distribution system where all active conductors are isolated from earth or connected via a high impedance, while exposed equipment frames are bonded to earth, maintaining operation without immediate trip upon a single phase-to-ground fault.