Technical Protection Measures in Electrical Installations

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/25

flashcard set

Earn XP

Description and Tags

Vocabulary practice flashcards covering technical protective measures against direct and indirect electrical contact, physiological effects of electric currents, and earthing distribution systems (TN, TT, and IT).

26 Terms

1
New cards

Electric Shock (Strujni udar)

The instant of contact with an energized conductor and the initial physiological impact of electric current experienced by a human being.

2
New cards
<p>Direct Contact (Direktni dodir)</p>

Direct Contact (Direktni dodir)

Accidental human contact with conductive parts of an installation or electrical load that are energized under normal operating conditions, such as bare conductors, fuse terminals, switches, and lamp sockets.

3
New cards

Indirect Contact (Indirektni dodir)

Human contact with exposed conductive parts of electrical equipment (such as metallic enclosures of motors, cookers, or boilers) that are not energized during normal operation, but become live due to an insulation breakdown.

4
New cards

Human Body Resistance Components

The total impedance opposing current flow through a human body, consisting of three elements: input contact resistance, internal body resistance, and output contact resistance.

5
New cards

Thermal Effect of Electric Current

The conversion of electrical energy into thermal energy within tissue resistance, elevating body temperature, destroying tissue, causing severe internal burns, fluid loss, and potentially charring.

6
New cards

Mechanical Effect of Electric Current

The physiological consequence of current passage producing violent involuntary muscle spasms and uncontrolled reflex movements, creating severe risks of falls and physical injury when working at heights.

7
New cards

Chemical Effect of Electric Current

The action occurring during the flow of direct current (DC\text{DC}) where the body fluids act as an electrolyte, causing permanent tissue damage through electrolytic decomposition.

8
New cards

Perception Threshold (1 mA1\,\text{mA} at 50 Hz50\,\text{Hz})

The lowest alternating current intensity detectable by the human body, producing the initial sensation of current flow and a slight muscle twitch.

9
New cards

Let-Go Threshold Current (Struja otpuštanja)

The maximum current limit at which an individual holding an energized conductor can still release their grip; defined as 10 mA10\,\text{mA} for women and 15 mA15\,\text{mA} for men at 50 Hz50\,\text{Hz}.

10
New cards

Ventricular Fibrillation Threshold (100 mA100\,\text{mA} at 50 Hz50\,\text{Hz})

A lethal alternating current magnitude that triggers uncoordinated cardiac flutter (fibrillation) and heart failure when sustained through the body for longer than 1–2 s1\text{--}2\,\text{s} (or 3 s3\,\text{s}).

11
New cards

Protection by Insulation of Live Parts

A direct contact protection measure consisting of a durable insulating coating applied to energized conductors that cannot be removed without complete destruction; paints, clear varnishes, and enamels are not recognized as acceptable protective insulation.

12
New cards

Protection by Barriers or Enclosures

A direct contact prevention method enclosing energized parts in sturdy housings or partitions that can only be unlocked or dismantled using a dedicated key or tool following power disconnection.

13
New cards

Protection by Obstacles (Zapreke)

A safety provision designed to prevent unintentional physical approach or accidental touch of energized equipment during normal operation and maintenance, removable without tools but secured against accidental displacement.

14
New cards
<p>Protection by Placing Out of Reach (Zaštita stavljanjem van dohvata ruke)</p>

Protection by Placing Out of Reach (Zaštita stavljanjem van dohvata ruke)

A measure ensuring that simultaneously accessible conductive parts at differing electrical potentials are separated beyond arm's reach, requiring a minimum vertical clearance of 2.5 m2.5\,\text{m} and a horizontal clearance of 1.25 m1.25\,\text{m}.

15
New cards

Residual Current Device (Zaštitna strujna sklopka - RCD / FI)

A protection device operating on the vector sum of currents in multi-phase systems; automatically disconnects supply in under 0.1 s0.1\,\text{s} when differential fault current exceeds its rating (typically ≤30 mA\le 30\,\text{mA}).

16
New cards
<p>Class II Equipment (Oprema klase II)</p>

Class II Equipment (Oprema klase II)

Electrical devices that utilize double insulation (basic plus supplementary) or reinforced insulation to protect against indirect contact without connecting metallic enclosures to a protective earth (PE\text{PE}) conductor.

17
New cards

Protection by Non-Conducting Location (Izolirane prostorije)

An indirect contact prevention method using insulating floors and walls with a resistance of at least 50 kΩ50\,\text{k}\Omega (for nominal voltages up to 500 V500\,\text{V}) or 100 kΩ100\,\text{k}\Omega (for nominal voltages above 500 V500\,\text{V}) to prevent circuit completion through the ground.

18
New cards
<p>Protection by Electrical Separation (Zaštita električnim odvajanjem)</p>

Protection by Electrical Separation (Zaštita električnim odvajanjem)

An indirect contact safety measure using an isolating transformer (transformation ratio ≈1:1\approx 1:1, primary voltage up to 500 V500\,\text{V}) feeding a single electrical consumer (≤16 A\le 16\,\text{A}) with an ungrounded secondary circuit.

19
New cards

Supplementary Equipotential Bonding Criterion (Z≤ULIaZ \le \frac{U_L}{I_a})

The condition verifying the impedance (ZZ) between simultaneously accessible conductive parts, where ULU_L is the permissible touch voltage and IaI_a is the tripping current of the protective device within a specified duration.

20
New cards

Main Equipotential Bonding (Glavno izjednačenje potencijala)

The permanent interconnection of the main earthing terminal with extraneous conductive parts of a building, including incoming water pipes, central heating/gas supply lines, structural steel, and lightning protection systems.

21
New cards

Earthing System Letter Codes

Classification codes where the first letter denotes the power source relation to earth (T\text{T} = directly grounded neutral, I\text{I} = isolated or high impedance), and the second letter denotes the equipment exposed parts relation to earth (T\text{T} = directly earthed locally, N\text{N} = directly linked to the grounded neutral point).

22
New cards
<p>TN-C System</p>

TN-C System

A sub-type of the TN grounding arrangement in which the neutral and protective functions are integrated into a single continuous conductor (PEN\text{PEN}) throughout the entire network; prohibited in fire- and explosion-hazard zones.

23
New cards
<p>TN-S System</p>

TN-S System

A configuration known as dead-neutral grounding (bezstrujno nulovanje) where the neutral (N\text{N}) and protective (PE\text{PE}) conductors are separated throughout the entire installation and interconnected solely at the source neutral point.

24
New cards

TN-C-S System

A distribution system where neutral and protective functions are combined in a single PEN\text{PEN} conductor across the upstream supply and then split into distinct, completely separated N\text{N} and PE\text{PE} conductors at an entry bonding point.

25
New cards
<p>TT System</p>

TT System

A network grounding scheme where the source neutral is directly grounded (RBR_B) and all accessible conductive enclosures of consumer equipment are connected to independent local earth electrodes (RAR_A).

26
New cards

IT System

An electrical distribution system where all active conductors are isolated from earth or connected via a high impedance, while exposed equipment frames are bonded to earth, maintaining operation without immediate trip upon a single phase-to-ground fault.