RNPCP - CHAPTER 10 TRAPS AND INTERCEPTORS

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/33

encourage image

There's no tags or description

Looks like no tags are added yet.

34 Terms

1
New cards

3

Number of single compartment sinks or laundry tubs of the same depth, or lavatories that can be serve by one trap.

2
New cards

0.75 m

Maximum center

3
New cards

0.60 m

Maximum length of tailpiece

4
New cards

2 times trap diameter

Minimum horizontal distance of a trap arm to vent.

5
New cards

more than 90o

Trap arm change of direction not requiring a cleanout.

6
New cards

less than 22 ½

For trap arms 75 mm Ø and larger, the change of direction not requiring a cleanout.

7
New cards

1.8 m max.

Developed length between the trap of a water closet from the top of closet ring to inner edge of vent.

8
New cards

GA 17 (1.1 mm)

Minimum thickness of exposed and readily accessible drawn brass tubing trap.

9
New cards

1

Maximum number of slip joint that may be used on outlet side of a trap.

10
New cards

51mm to 102mm

Depth or trap seals.

11
New cards

152mm

Minimum water seal for sand interceptors and similar clarifiers.

12
New cards

1.3 Lis to 3.4L/s

Rate of flow of an individual grease trap.

13
New cards

2

½

14
New cards

4

Maximum number of fixtures connected to one grease trap.

15
New cards

1.2 m

Maximum horizontal distance between the fixture outlet and the grease trap, so grease trap may serve as fixture trap.

16
New cards

0.75 m

Maximum vertical tailpipe or drain between the fixture outlet and the grease trap, so grease trap may serve as fixture trap.

17
New cards

51 mm

Minimum water seal for grease trap.

18
New cards

12.7 mm or larger

Size of solids to be screened from laundry discharge by means removable wire basket.

19
New cards

76 mm Ø

Minimum outlet size of a sand interceptor.

20
New cards

0.2 sq.m.

Minimum net opening dimension of the inlet section of a sand interceptor.

21
New cards

610 mm

The minimum depth of sand interceptor under the invert of the outlet pipe.

22
New cards

0.09 sq.m.

Increase in the area of inlet section for each 18.9 LPM or fraction thereof over 75.7 LPM.

23
New cards

50% of the inlet section

Minimum area of sand interceptor outlet section.

24
New cards

762mm

Distance of trap to vent for 32mm Ø

25
New cards

1067mm

Distance of trap to vent for 38mm Ø

26
New cards

1524mm

Distance of trap to vent for mm Ø

27
New cards

1829mm

Distance of trap to vent for 76 mm Ø

28
New cards

3048mm

Distance of trap to vent for 102 mm Ø and larger

29
New cards

1829mm

Maximum developed length between water closet and vent

30
New cards

greater than 3.4L/sec & lower than 1.3L/s. – Grease Traps shall not be installed for a facility that has an approved rate of flow of _____.

31
New cards

2 1/2 times – Grease Traps the total capacity of fixtures discharging to any grease trap shall not exceed ______the certified liters per minute flowrate of grease traps.

32
New cards

51mm min.

Grease traps shall have an approved water seal of _____ in depth or the diameter of its outlet.

33
New cards

0.2m2 min.

Sand interceptors shall be have a dimension of _____ for the net free opening of the inlet section & a 610mm min. depth under the invert of the outlet pipe.

34
New cards

0.6m

In no case any tailpiece or connections shall exceed _____ long.