Number of single compartment sinks or laundry tubs of the same depth, or lavatories that can be serve by one trap.
0.75 m
Maximum center
0.60 m
Maximum length of tailpiece
2 times trap diameter
Minimum horizontal distance of a trap arm to vent.
more than 90o
Trap arm change of direction not requiring a cleanout.
less than 22 ½
For trap arms 75 mm Ø and larger, the change of direction not requiring a cleanout.
1.8 m max.
Developed length between the trap of a water closet from the top of closet ring to inner edge of vent.
GA 17 (1.1 mm)
Minimum thickness of exposed and readily accessible drawn brass tubing trap.
1
Maximum number of slip joint that may be used on outlet side of a trap.
51mm to 102mm
Depth or trap seals.
152mm
Minimum water seal for sand interceptors and similar clarifiers.
1.3 Lis to 3.4L/s
Rate of flow of an individual grease trap.
2
½
4
Maximum number of fixtures connected to one grease trap.
1.2 m
Maximum horizontal distance between the fixture outlet and the grease trap, so grease trap may serve as fixture trap.
0.75 m
Maximum vertical tailpipe or drain between the fixture outlet and the grease trap, so grease trap may serve as fixture trap.
51 mm
Minimum water seal for grease trap.
12.7 mm or larger
Size of solids to be screened from laundry discharge by means removable wire basket.
76 mm Ø
Minimum outlet size of a sand interceptor.
0.2 sq.m.
Minimum net opening dimension of the inlet section of a sand interceptor.
610 mm
The minimum depth of sand interceptor under the invert of the outlet pipe.
0.09 sq.m.
Increase in the area of inlet section for each 18.9 LPM or fraction thereof over 75.7 LPM.
50% of the inlet section
Minimum area of sand interceptor outlet section.
762mm
Distance of trap to vent for 32mm Ø
1067mm
Distance of trap to vent for 38mm Ø
1524mm
Distance of trap to vent for mm Ø
1829mm
Distance of trap to vent for 76 mm Ø
3048mm
Distance of trap to vent for 102 mm Ø and larger
1829mm
Maximum developed length between water closet and vent
greater than 3.4L/sec & lower than 1.3L/s. – Grease Traps shall not be installed for a facility that has an approved rate of flow of _____.
2 1/2 times – Grease Traps the total capacity of fixtures discharging to any grease trap shall not exceed ______the certified liters per minute flowrate of grease traps.
51mm min.
Grease traps shall have an approved water seal of _____ in depth or the diameter of its outlet.
0.2m2 min.
Sand interceptors shall be have a dimension of _____ for the net free opening of the inlet section & a 610mm min. depth under the invert of the outlet pipe.
0.6m
In no case any tailpiece or connections shall exceed _____ long.