Explain how single line diagrams are connected to the site electrical safety program
With up to date, correct, lines we can lock out the right equipment
Provide the proper connecting info for upstream power distribution systems
Determine the capacity and flash hazard of downstream equipment. Flash Hazard determines level of PPE
Document the bus bracing for the MCC
Let us know if equipment is overdutied or not
Accuracy of these lines are audited for the electrical KEA
Explain the differences between class 1 and class 2 hazardous locations
Class 1 - Ignitable concentrations of flammable gases, vapors or liquids
Class 2 - Ignitable concentrations of Combustible Dusts
Class 1 Division 1 vs Class 1 Division 2
Div 1 - Ignitable concentrations of flammable gases, vapors, or liquids CAN exist all of the time or some of the time under normal operations
Div 2 - Ignitable concentrations of flammable gases, vapors, or liquids NOT likely to exist under normal operation
Identify Hazardous Locations in Department
HDL Process Tank Farm
LFE Tank Farm
Perfume Storage
Determine Rating of a device by observing the device nameplate
Devices should have labeling designating UL Hazard Classification
Explain what each symbol is in a Single Line for an MCC
Covered “Fed From”
Incoming Breaker (Frame and Trip)
Horizontal Bus Ampacity
Combination Starter Symbol (With frame, fuse size, starter size)
Extents of MCC
External Wiring
Wire Labeling
Field Disconnects
Motor HP
Transformer Size and Config
Describe the different voltages that you would encounter in these panels
480/277v AC, depending on the 480v transformer secondary feeding the panel
Locate a lighting panel, point out the components
Main disconnect is generally at the top or bottom of panel, larger than the other breakers in there
Describe which components remain energized in a panel after a breaker has been de - energized
All breakers besides the one that is de energized, incoming cables, Bus bar, All wiring not connected to de-energized breaker
Describe the different levels of PPE required to work on energized Panels
Class 0-4, refer to PCP 650 PPE Matrix
Explain the operation of the electrical safety door interlock with NEMA switch
Door switch prevents door from being accidently being opened and helps prevent exposing energized components. Use a flat head screwdriver to override the safety for trouble shooting
Explain why operating switches or indicating lamps should not be installed on a local disconnect
The holes in the panel degrade the structural integrity of the disconnect
White, Grey Wire
Grounded Conductor (Neutral)
Black Wire
Line or Load Wire AC or DC over 24V
Blue Wire
24V Control Power
Green/Bare Wire
Grounding Conductor
Yellow Wire
Fed From outside source
Red Wire
120v AC control power
Brown Orange Yellow Wires
480v AC, A,B,C phase
Red, Black, Blue
208v AC, A,B,C 3 Phase
Identify the instances under which temporary installation of wire is permitted
Only there for less than 90 days, and approved by the Electrical System Owner or ESO, Found in NEC 590
What does UPS stand for?
Uninterruptible Power Supply (Battery Back-Up)
Describe which loads are currently connected to your UPS
Rack Module Controls - DC modules to prevent a UL in motion from coming to an immediate stop (brake coil collapses) and so ACTIV will always know where inventory is.
Data Center servers
HDL Process TDC & PLC systems.
What is a Manual Transfer Switch?
Used to transfer power supply from an MCC to generator. Switch from "Normal" (MCC) to "Off" to "Aux" (generator). To use stop at off when switching. Do NOT switch under load. Not to be used as a disconnect. Arc flash could possibly energize other side of switch.
What is an Automatic Transfer Switch?
Automatically transfers power supply from an MCC to a generator. Does the transfer under load. Used in critical systems, such as distribution center or hospitals.
Explain how to correctly lock-out / tag out when an ATS is involved.
Lock out all possible sources of power, upstream and downstream. Remember that arc flash could energize either side.
Describe how equipment (MCC's / PDP's etc.) should be labeled if a generator is/can be connected
Caution: fed from two sources.
Explain the function of a Ground Fault Circuit Interrupter.
To detect current imbalance between hot & neutral and open the circuit.
Identify the current trip threshold for a GFCI designed for personnel protection.
5 mA
Describe the current trip threshold of a GFCI breaker for equipment protection. Explain what would happen if this device were installed to provide personnel protection.
30 mA
People could receive a potentially fatal shock without the GFCI tripping
Using a hand sketch of a GFCI circuit diagram, explain the theory of operation for a GFCI breaker or receptacle.
Hand sketch of two conductors with current transformer around BOTH phases.
If the same amount of current flowing to the load on the hot wire does NOT come back on the neutral, the GFCI will trip.
Explain how the test circuit in a GFCI works. Determine if a GFCI can be tested de-energized.
Test circuit drains a small amount of current (> 5 mA) from the circuit and trips the GFCI.
GFCI cannot be tested de-energized.
Identify the physical locations requiring a GFCI according to the National Electrical Code (include residential, commercial, and industrial settings).
Garages, Outdoors, Kitchens, Bathrooms, Hot Tubs, Pools, (anywhere within 10 ft of water source). Commercial and Industrial areas where portable cord-connected devices are used (except for office areas)
Identify the tasks requiring a GFCI according to NFPA 70E.
Testing of GFCI’s required by 70E.
Installation Requirements set by NEC.
Required In areas that have high risk of water, moisture, or earth ground contact
Explain why a GFCI will trip on a ground fault but not a short circuit.
Short circuit has all the current going to the load on the hot wire and returning from the load on the neutral – so NO current imbalance.
A ground fault lets current out of the normal circuit path – so Current Imbalance trips the unit.
Determine if any of your department substation breakers have Ground Fault protection. If so, explain the sensing mechanism for the ground fault and determine if this is for personnel or equipment protection.
No
Explain why a GFCI receptacle will function properly to provide personnel protection, even if a dedicated ground conductor is wired to the receptacle.
The ground wire is not in the sensing circuit. [Sensing circuit only uses the Hot & Neutral.] Doesn’t matter if ground is there or not for the GFCI to work.
Explain the testing requirements for a GFCI and why testing is important.
Test every month.
Legally required.
Explain what a Arc Fault Circuit Interrupter is and how it works.
Arc Fault interrupter senses the varying current spikes and trips based on a threshold set by the manufacturer.