What is the required spare capacity for the utility lead-in underground cables?
The capacity must include an additional 10% spare capacity on top of the estimated maximum building demand for normal expansion.
According to DEWA guidelines, what is the maximum number of transformers that a single 11kV Ring Main Unit (RMU) can feed?
A single RMU can feed a maximum of 2 transformers.
Under the N−1 offline criterion for an 11kV ring supply, what is the required operational capability if one feeder fails?
The remaining feeder must be capable of meeting the entire demand for a maximum duration of 6hours.
What is the maximum sustained load (summer rating) of an 11kV feeder using 3/C 300mm2 Copper XLPE cable?
175A / 3MW.
What power factor must a client maintain at the point of connection with DEWA's MV Network?
Between 0.95 (lagging) and unity.
What are the minimum clear height requirements for a single-room substation at ground floor and a transformer room at basement level?
A minimum of 3.7m for a single-room substation at ground floor, and a minimum of 3.0m for a transformer room at the basement level.
What finished floor level (FFL) elevation difference must be maintained for a substation room relative to the outside adjacent ground level towards the door side?
0.15m to 0.30m higher than the outside adjacent ground level.
What are the required floor areas and minimum room widths for single-room substations housing 1×1000/1500kVA and 2×1000/1500kVA transformers?
33m2 with a minimum width of 4.57m for 1×1000/1500kVA, and 55m2 with a minimum width of 6.1m for 2×1000/1500kVA.
In a split-room ground-floor substation, what are the spatial requirements for the RMU room housing one set of RMU controlling 2 transformers?
An area of 9.0m2 with a minimum width of 3.0m towards the door side.
What working clearances must be maintained around floor-standing panels in LV electrical rooms according to DEWA?
750mm behind floor-standing panels, and 1500mm between floor-standing panels or between a panel front and the wall.
What are the required dimensions for the main telecom room and typical floor telecom room in buildings with 100 to 300 tenants or an area exceeding 7000m2?
Main telecom room: 3m×3m×3m; Floor telecom room: 1.5m×1.5m×3m.
What are the minimum area and dimension requirements for a Fire Command Center (FCC) room?
A minimum floor area of 19m2 with a minimum single dimension of 3m.
What are the maximum permissible motor ratings for 1-phase and 3-phase motors without requiring specific DEWA approval for bulk supply?
Up to 3.7kW (5HP) for 1-phase motors, and up to 110kW (150HP) for 3-phase motors.
What ambient temperature variation range must motor starter thermal overload relays compensate for automatically?
Between 2.8∘C and 48∘C.
At what DEWA service feeder ratings is centralized power factor correction via capacitor banks mandatory for commercial and residential installations?
Feeders of 200A and above for commercial premises, and feeders of 400A and above for residential premises.
What is the maximum number of floors that a single busbar riser can supply in Dubai versus Abu Dhabi?
A maximum of 12 floors in Dubai, and a maximum of 10 floors in Abu Dhabi.
What are the minimum conductor cross-sectional areas permitted for lighting circuits and utility socket circuits?
2.5mm2 for lighting circuits and 4mm2 for utility sockets.
What is the required mounting height range for tap-off units installed in a busbar riser from the finished floor level?
Between 500mm and 1800mm from the finished floor level.
At what circuit breaker rating threshold at the point of supply must metering via Current Transformers (CTs) be provided?
160A and above (direct-connected meters are used up to 125A).
What are the specification requirements for a consumer's main earth electrode regarding rod diameter, installation depth, spacing, and resistance?
A 20mm diameter copper core bonded earth rod installed to a minimum depth of 3m, spaced at least 6m apart if multiple rods are installed, with total earth electrode resistance not exceeding 1Ω.
In a Faraday Cage Lightning Protection System, what are the mesh sizes and down conductor spacings specified for Class I and Class IV LPS?
Class I: mesh size of 5m×5m with down conductor spacing of 10m; Class IV: mesh size of 20m×20m with down conductor spacing of 20m.
How are Class II and Class III luminaires classified based on their protection against electric shock?
Class II features double insulation, while Class III luminaires are supplied at Safety Extra Low Voltage (SELV).
What are the recommended Ingress Protection (IP) ratings for outdoor installations, mechanical plant rooms, and bathrooms?
IP65 for outdoor installations, IP65 for mechanical plant rooms, and IP44 for bathrooms.
How are correlated colour temperatures (CCT) categorized into Warm, Intermediate, and Cool appearances?
Warm: below 3300K (reddish); Intermediate: 3300–5300K (white); Cool: above 5300K (bluish).
According to CIBSE guidelines, what are the recommended illuminance levels (lux) for reception desks, kitchens with meal cooking, and general corridors?
Reception desk: 300lux; Kitchen with meal cooking: 500lux; Corridors: 100lux.
What is the maximum allowable travel distance to reach the nearest manual call point (break glass) along escape routes in parking areas?
The travel distance must not exceed 45m.
What is the minimum retention period required for CCTV recordings under SIRA regulations for multi-floor buildings?
Recordings must be retained for at least 31days for all cameras.
What are the maximum horizontal cable distance and combined patch/line cord length limits for Cat-6 structured cabling?
Maximum horizontal cabling distance is 90m between outlet and patch panel, and the sum length of all patch and line cords for one outlet must not exceed 10m.
Under SIRA regulations, at what building size does providing 24/7 security guards become mandatory for multi-floor residential buildings?
Mandatory for buildings with 50 residential units and above (optional for buildings with less than 50 units).