Flashcards covering electrical system design guidelines, DEWA substation regulations, LV distribution, power factor correction, earthing, lighting design, telecom, and life safety systems.

Last updated 6:32 PM on 10/8/26
Name
Mastery
Learn
Test
Matching
Spaced
Call with Kai
Chat

No analytics yet

Send a link to your students to track their progress

29 Terms

1
New cards

What is the required spare capacity for the utility lead-in underground cables?

The capacity must include an additional 10%10\% spare capacity on top of the estimated maximum building demand for normal expansion.

2
New cards

According to DEWA guidelines, what is the maximum number of transformers that a single 11 kV11\,\text{kV} Ring Main Unit (RMU) can feed?

A single RMU can feed a maximum of 22 transformers.

3
New cards

Under the N−1N-1 offline criterion for an 11 kV11\,\text{kV} ring supply, what is the required operational capability if one feeder fails?

The remaining feeder must be capable of meeting the entire demand for a maximum duration of 6 hours6\,\text{hours}.

4
New cards

What is the maximum sustained load (summer rating) of an 11 kV11\,\text{kV} feeder using 3/C 300 mm23/\text{C } 300\,\text{mm}^2 Copper XLPE cable?

175 A175\,\text{A} / 3 MW3\,\text{MW}.

5
New cards

What power factor must a client maintain at the point of connection with DEWA's MV Network?

Between 0.950.95 (lagging) and unity.

6
New cards

What are the minimum clear height requirements for a single-room substation at ground floor and a transformer room at basement level?

A minimum of 3.7 m3.7\,\text{m} for a single-room substation at ground floor, and a minimum of 3.0 m3.0\,\text{m} for a transformer room at the basement level.

7
New cards

What finished floor level (FFL) elevation difference must be maintained for a substation room relative to the outside adjacent ground level towards the door side?

0.15 m0.15\,\text{m} to 0.30 m0.30\,\text{m} higher than the outside adjacent ground level.

8
New cards

What are the required floor areas and minimum room widths for single-room substations housing 1×1000/1500 kVA1 \times 1000/1500\,\text{kVA} and 2×1000/1500 kVA2 \times 1000/1500\,\text{kVA} transformers?

33 m233\,\text{m}^2 with a minimum width of 4.57 m4.57\,\text{m} for 1×1000/1500 kVA1 \times 1000/1500\,\text{kVA}, and 55 m255\,\text{m}^2 with a minimum width of 6.1 m6.1\,\text{m} for 2×1000/1500 kVA2 \times 1000/1500\,\text{kVA}.

9
New cards

In a split-room ground-floor substation, what are the spatial requirements for the RMU room housing one set of RMU controlling 22 transformers?

An area of 9.0 m29.0\,\text{m}^2 with a minimum width of 3.0 m3.0\,\text{m} towards the door side.

10
New cards

What working clearances must be maintained around floor-standing panels in LV electrical rooms according to DEWA?

750 mm750\,\text{mm} behind floor-standing panels, and 1500 mm1500\,\text{mm} between floor-standing panels or between a panel front and the wall.

11
New cards

What are the required dimensions for the main telecom room and typical floor telecom room in buildings with 100100 to 300300 tenants or an area exceeding 7000 m27000\,\text{m}^2?

Main telecom room: 3 m×3 m×3 m3\,\text{m} \times 3\,\text{m} \times 3\,\text{m}; Floor telecom room: 1.5 m×1.5 m×3 m1.5\,\text{m} \times 1.5\,\text{m} \times 3\,\text{m}.

12
New cards

What are the minimum area and dimension requirements for a Fire Command Center (FCC) room?

A minimum floor area of 19 m219\,\text{m}^2 with a minimum single dimension of 3 m3\,\text{m}.

13
New cards

What are the maximum permissible motor ratings for 1-phase and 3-phase motors without requiring specific DEWA approval for bulk supply?

Up to 3.7 kW3.7\,\text{kW} (5 HP5\,\text{HP}) for 1-phase motors, and up to 110 kW110\,\text{kW} (150 HP150\,\text{HP}) for 3-phase motors.

14
New cards

What ambient temperature variation range must motor starter thermal overload relays compensate for automatically?

Between 2.8 ∘C2.8\,^\circ\text{C} and 48 ∘C48\,^\circ\text{C}.

15
New cards

At what DEWA service feeder ratings is centralized power factor correction via capacitor banks mandatory for commercial and residential installations?

Feeders of 200 A200\,\text{A} and above for commercial premises, and feeders of 400 A400\,\text{A} and above for residential premises.

16
New cards

What is the maximum number of floors that a single busbar riser can supply in Dubai versus Abu Dhabi?

A maximum of 1212 floors in Dubai, and a maximum of 1010 floors in Abu Dhabi.

17
New cards

What are the minimum conductor cross-sectional areas permitted for lighting circuits and utility socket circuits?

2.5 mm22.5\,\text{mm}^2 for lighting circuits and 4 mm24\,\text{mm}^2 for utility sockets.

18
New cards

What is the required mounting height range for tap-off units installed in a busbar riser from the finished floor level?

Between 500 mm500\,\text{mm} and 1800 mm1800\,\text{mm} from the finished floor level.

19
New cards

At what circuit breaker rating threshold at the point of supply must metering via Current Transformers (CTs) be provided?

160 A160\,\text{A} and above (direct-connected meters are used up to 125 A125\,\text{A}).

20
New cards

What are the specification requirements for a consumer's main earth electrode regarding rod diameter, installation depth, spacing, and resistance?

A 20 mm20\,\text{mm} diameter copper core bonded earth rod installed to a minimum depth of 3 m3\,\text{m}, spaced at least 6 m6\,\text{m} apart if multiple rods are installed, with total earth electrode resistance not exceeding 1 Ω1\,\Omega.

21
New cards

In a Faraday Cage Lightning Protection System, what are the mesh sizes and down conductor spacings specified for Class I and Class IV LPS?

Class I: mesh size of 5 m×5 m5\,\text{m} \times 5\,\text{m} with down conductor spacing of 10 m10\,\text{m}; Class IV: mesh size of 20 m×20 m20\,\text{m} \times 20\,\text{m} with down conductor spacing of 20 m20\,\text{m}.

22
New cards

How are Class II and Class III luminaires classified based on their protection against electric shock?

Class II features double insulation, while Class III luminaires are supplied at Safety Extra Low Voltage (SELV).

23
New cards

What are the recommended Ingress Protection (IP) ratings for outdoor installations, mechanical plant rooms, and bathrooms?

IP65\text{IP}65 for outdoor installations, IP65\text{IP}65 for mechanical plant rooms, and IP44\text{IP}44 for bathrooms.

24
New cards

How are correlated colour temperatures (CCT) categorized into Warm, Intermediate, and Cool appearances?

Warm: below 3300 K3300\,\text{K} (reddish); Intermediate: 3300–5300 K3300\text{--}5300\,\text{K} (white); Cool: above 5300 K5300\,\text{K} (bluish).

25
New cards

According to CIBSE guidelines, what are the recommended illuminance levels (lux) for reception desks, kitchens with meal cooking, and general corridors?

Reception desk: 300 lux300\,\text{lux}; Kitchen with meal cooking: 500 lux500\,\text{lux}; Corridors: 100 lux100\,\text{lux}.

26
New cards

What is the maximum allowable travel distance to reach the nearest manual call point (break glass) along escape routes in parking areas?

The travel distance must not exceed 45 m45\,\text{m}.

27
New cards

What is the minimum retention period required for CCTV recordings under SIRA regulations for multi-floor buildings?

Recordings must be retained for at least 31 days31\,\text{days} for all cameras.

28
New cards

What are the maximum horizontal cable distance and combined patch/line cord length limits for Cat-6 structured cabling?

Maximum horizontal cabling distance is 90 m90\,\text{m} between outlet and patch panel, and the sum length of all patch and line cords for one outlet must not exceed 10 m10\,\text{m}.

29
New cards

Under SIRA regulations, at what building size does providing 24/7 security guards become mandatory for multi-floor residential buildings?

Mandatory for buildings with 5050 residential units and above (optional for buildings with less than 5050 units).