Vocabulary terms, operational definitions, numerical criteria, and structural codes extracted directly from the 2021 International Building Code (IBC) practice questions and official answer key for Building Plans Examiners.
Name | Mastery | Learn | Test | Matching | Spaced | Call with Kai | Chat |
|---|
No analytics yet
Send a link to your students to track their progress
Stationary Generator Systems Standard
UL 2200
Group B Occupancy (Assembly Exception)
An assembly building with an occupant load of less than 50 persons.
Semiconductor Fabrication Facility Power Requirements
Must be provided with emergency power.
Dwelling Unit Minimum Temperature Capability
Must be capable of maintaining a minimum temperature of 68∘F.
Group A-4 Automatic Sprinkler Threshold
Required when the fire area has an occupant load of 300 or more.
Ready Access
The required access type for Class II standpipe hose connections.
Parapet Wall Requirement
A protective wall requirement applied to exterior walls of a building.
Construction Document Retention Period
Must be retained for not less than 180days from completion of the project.
Underground Buildings Power Requirements
Must be equipped with both emergency and standby power.
High-Rise Building Power Requirements
Must be provided with both emergency and standby power.
Group I-2 Maximum Sleeping Room Travel Distance
The maximum travel distance from a sleeping room to an exit access door is 50ft.
Aircraft Control Tower Automatic Sprinkler Requirement
Required when there is an occupied floor located more than 35ft above the lowest fire department access level.
High-Rise Tower Stairway Separation Distance
The minimum distance between exit stairways in a high-rise tower is 30ft.
Group I-1 Commercial Cooking Fire Extinguisher Distance
A fire extinguisher must be installed within 30ft of commercial cooking equipment.
Chimney Cricket / Saddle Requirement Threshold
Must be installed on the ridge side of any chimney with a width greater than 30in.
Group H-2 Fire Wall Rating
4hours
Permit Application Extension Period
The building official may grant an extension of up to 90days on a permit application.
Group H Exterior Wall Rating (< 5 ft Separation)
Exterior walls in a Group H occupancy with a fire separation distance of less than 5ft must have a fire resistance rating of 3hours.
Type IV Construction
Construction type characterized by exterior walls of noncombustible materials and interior elements of solid or laminated wood.
Foam Plastic Insulation Maximum Smoke Developed Index
450
Group H-2 Occupancy
Classification used for buildings and structures containing materials that pose a deflagration hazard.
Handrail Height Limits
Must be located between 34in and 38in vertically above the finished floor or stair tread nosing.
Group R
Occupancy classification designated for residential groups.
Foam Plastic Insulation Maximum Flame Spread Index
75
Polyethylene Vapor Retarder Lap Joint Minimum
Joints for poly vapor retarders under concrete slabs directly on the ground must be lapped not less than 6in.
Live Load
A variable or transient load imposed by the intended use and occupancy within a structure.
Construction Barrier Minimum Height
8ft
Structural Glass Veneer Maximum Single Piece Area
10sq ft (10ft)
Sloped Glazing Screen Distance
Screens required for sloped glazing must be located within 4in of the glass.
Public Parking Garage Vehicle Barrier Threshold
Vehicle barriers are required where there is a change in elevation of 1ft or more.
Metal Roof Shingle Valley Flashing Centerline Distance
Valley flashing must extend not less than 8in from the centerline.
Louvered Window Maximum Length
48in
Interior Door Maximum Opening Force
Must not exceed 5lbs of force.
Official Plan Approval Stamp Phrase
"Reviewed for code compliance"
Braced Wall Line
A straight line through the building plan that represents the location of lateral resistance provided by wall bracing.
Ramp Handrail Threshold Rise
Ramps require handrails when the rise exceeds 6in.
Fire Damper
A listed device installed in ducts and air transfer openings designed to close automatically upon detection of heat and resist the passage of flame.
Group A-3
Assembly occupancy designation for spaces such as libraries and places of worship without spectating.
Marquee Maximum Height
9ft when projecting less than two-thirds of the distance from the lot line to the curb line.
Group I
Occupancy classification designated for institutional facilities.
Group F
Occupancy classification designated for factory and industrial uses.
Dead Load
A permanent structural load comprised of the weight of fixed assets, structural framing, and permanent building materials.
Fireplace Combustible Clearance
Requires a minimum 2in airspace clearance between combustible materials and the fireplace structure.
Stretcher Elevator Minimum Dimensions
24in by 84in
Step Projection Limit into Public Right of Way
Steps shall not project more than 12in into the public right-of-way.
Shallow Foundation Footing Minimum Depth
12in below undisturbed ground surface.
Slab-on-Ground Minimum Thickness
321in (3.5in)
Group R-1 Fire Wall Rating
3hours
Type II Construction
Building construction type in which exterior walls and interior structural elements are constructed of noncombustible materials.
Incidental Use Area Limit
Incidental uses shall not occupy more than 10% (10percent) of the building area.
Group F-2
Occupancy classification designated for low-hazard factory industrial uses.
Transient Occupancy
Occupancy of a dwelling unit or sleeping unit for a duration of not more than 30days.
Awning Vertical Clearance Projection Limit
Awnings projecting into the public right-of-way shall not be less than 7ft vertically above the walkway.
Construction Site Walkway Live Load Capacity
Must be capable of withstanding a design live load of not less than 150psf.
Masonry Hearth Minimum Thickness
4in
Handrail Uniform Linear Load Capacity
50lbs/ft (50lbs)
Chimney Wall Minimum Thickness
4in
Group A Occupancy Standpipe Requirement (Non-Sprinklered)
A Class I standpipe system is required in non-sprinklered Group A buildings with an occupant load exceeding 1000.
Parapet Wall Exception Area Threshold
Parapets are not required on buildings having an area of not more than 1000sq ft.
Type I-A Tank Support Volume Threshold
Tanks with a capacity of 500gal or more must be supported by Type I-A construction.
Agricultural Facilities Risk Category
Category I
Draft Stop
A material, device, or construction installed to restrict the movement of air within open spaces of concealed building components such as crawl spaces, floor/ceiling assemblies, and attics.
Group A-2 Nightclub Lavatory Ratio
1 lavatory per 75 occupants.
Mezzanine Clear Height Requirement
The clear height above and below a mezzanine floor assembly shall be no less than 7ft.
Vehicle Barrier Concentrated Load Capacity
6000lbs
Group A-5
Occupancy designation for outdoor assembly areas such as stadiums and grandstands.
Fire Pump Barrier Protection Rating
Fire pumps must be protected by a fire barrier rated for 2hours.
Group H-5
Occupancy classification designated for semiconductor fabrication facilities.
Parapet Uppermost Noncombustible Face Distance
Must have noncombustible faces for the uppermost distance of 18in.
Group H-1
Occupancy classification for buildings containing materials that present a high detonation or explosive hazard.
Exterior Plaster Weep Screen Minimum Thickness
0.019in
Asphalt Felt Water Barrier Grade
No. 15 asphalt felt.
Group A-1
Occupancy classification for assembly spaces with fixed seating intended for the viewing of performing arts or motion pictures (e.g., theaters).
Open Valley Flashing Minimum Width (Asphalt Shingles)
24in wide.
Group I-3 Fire Alarm Type
A manual fire alarm system designed to alert staff.
Area of Refuge Wheelchair Space Dimensions
30in by 52in
Stair Riser Maximum Height
7in
Class A Interior Finish Flame Spread Index
0 to 25
Temporary Membrane Structure Maximum Service Life
Not more than 180days
Court
An open, uncovered space bounded on two or more sides by the exterior walls of a building or structure, open to the sky.
Smoke Barrier Fire Resistance Rating
1hour
Covered Mall Open Space Surrounding Requirement
An open space of no less than 60ft surrounding the covered mall building.
Thin Exterior Glass Veneer Minimum Thickness
0.344in
Attic Access Minimum Opening Dimensions
20in by 30in
Dwelling Unit Minimum Corridor Width
36in
Exit Passageway
An exit component that is separated from other interior spaces of a building by fire-resistance-rated construction and provides a protected path of egress travel in a horizontal direction.
Group H
Occupancy classification for high-hazard uses.
Group S
Occupancy classification for storage uses.
Crawl Space Minimum Opening Size
18in by 24in
Group H-3
Occupancy classification for buildings containing materials that readily support combustion or present a physical hazard.
Emergency Power Minimum Duration Capability
2hours
Required Exits for Occupant Load > 1000
Not less than 4 exits.
Slab-on-Ground Vapor Retarder Thickness
6mil polyethylene sheet.
Shallow Foundation Footing Minimum Width
12in
Group I-3 Clear Door Width
Clear width of not less than 28in for sleeping unit doors.
1-Hour Corridor Wall Fire Door Rating
31hour (20minutes)
Expansive Soil Index Criterion
Expansion Index greater than 20 per ASTM D4829.
Habitable Space Minimum Room Dimension
No less than 7ft in any plan dimension (excluding kitchens).
Egress Door Maximum Threshold Height
21in above the finished floor.
Group A-2 Automatic Sprinkler Threshold
Required when the fire area exceeds 5000sq ft.