What is the purpose of directional signs?
To mark the ways of egress.
Where are DIRECTIONAL SIGNS put?
Where the exit location or travel path is unclear.
Where do the exit signs go?
Over or immediately adjoining required exit openings.
Where must stairway signs be located in previously built (existing) buildings?
At every stairway on every floor.
Do exit and directional signs need to be clearly visible from all approaches?
Yes
What must STAIRWELL IDENTIFICATION signs show?
The stairwell letter or direction/floor number the door opens to.
Where must STAIRWELL IDENTIFICATION signs be posted at?
Inside every interior stairwell, on every floor, next to the stairwell door.
What is the minimum height for stairwell identification lettering?
6 inches.
What additional information should be near stairwell doors?
Which floors have re-entry locations.
What must an AREA OF RESCUE assistance sign display?
“AREA OF RESCUE ASSISTANCE” and the international accessibility symbol.
What is the minimum lettering height for an area of rescue sign?
3 inches.
Where must TACTILE area-of-refuge signs be located?
At each door to an area of refuge.
When must an area-of-refuge sign be illuminated?
When exit sign illumination is required.
Where are directional signs to rescue assistance required?
At inaccessible exits and wherever needed to show the direction.
Which standard must the study guide's signage follow?
ICC/ANSI A117.1-2003, Section 703.
Illumination
must be internally illuminated by a ten-watt or larger incandescent lamp so smoke/power failures can be seen
What is the purpose of a high-rise voice communication system?
Provide clear instructions through a public address system.
What is the main function of the Fire Alarm Control Panel (FACP)?
Process signals from detectors and trigger notification appliances.
What does the RED alarm light on the FACP indicate?
An active alarm condition.
What does an AMBER SUPERVISORY light indicate? (FACP)
A portion of the fire protection system is disabled, such as a closed sprinkler valve.
What does a TROUBLE signal indicate? (FACP)
A system fault, such as a disconnected wire or low battery.
What instructions can a voice communication system provide?
Direct occupants to safe floors or instruct them to evacuate.
What appliances can provide occupant notifications?
Audible sirens, horns, and visual strobes.
Why are both audible and visual notification appliances important?
To alert all occupants, including people with disabilities.
What type of communication system is required for firefighters?
A two way voice communication system.

Who uses the two-way voice communication system?
firefighters when in communication with incident commander.
Where are firefighter phones installed?
On every fifth floor in the buildings stairwell.
What goes between the fire command panel, elevators and elevator lobbies?
speakers

How many speakers required in stairwells?
One speaker on every fifth floor in required stairwells.
Where are speakers required in large office areas?
Office areas exceeding 5,000 square feet.
How far apart must corridor speakers be placed?
At intervals of at least 75 feet and at exit stair doors.
What is the first line of defense in a high-rise building?
The fire detection system.
What is the purpose of a high-rise fire detection system?
Provide early warning and facilitate a rapid response.
How do smoke detectors sense smoke?
Through photoelectric or ionization methods.
What does an intermittently blinking light on a hard-wired smoke detector indicate?
Normal operation.
What does a solid light on a hard-wired smoke detector indicate?
The detector has been triggered.
How do fixed-temperature heat detectors activate?
When a preset temperature is reached.
How do rate-of-rise heat detectors activate?
When ambient temperature rises suddenly, such as 12°F to 15°F per minute.
How do water-flow detectors detect water movement?
A movable vane detects water movement in sprinkler or standpipe systems.
Where does a water-flow detector send its alarm signal?
To the Fire Alarm Control Panel (FACP).
What monitors the high-rise fire alarm system?
A UL-listed central station monitoring service.
What can cause the monitoring service to notify the fire department?
Sprinkler water flow or activated heat or smoke detector.

Where are smoke detectors required? (FANNY,ELLIE,RAINY,PLUMS,EL, CORA)
Fan rooms, electrical rooms, return air ducts, plenums, elevator lobbies, and corridors.
Where are smoke detectors required in residential units?
Within 15 feet of the entrance to all sleeping rooms.
Where are heat detectors required?
Storage rooms, boiler rooms, and furnace rooms.

What happens when duct smoke detectors activate?
The mechanical ventilation system shuts down to prevent smoke from spreading.