waterseal trap

Each plumbing fixture, excepting those having integral traps, shall be separately trapped by an approved-type _____

2
New cards

three (3)

One trap may serve a set of not more than _____ single compartment sinks or laundry tubs of the same depth or three (3) lavatories immediately adjacent to each other and in the same room if the waste outlets are not more than 0.75 meter apart and the trap is centrally located when three (3) compartments are installed.

3
New cards

1 trap arm

1 trap is equal to

4
New cards

Integral Trap

Kind of trap for water closet

5
New cards

P-Trap

Kind of trap for lavatory, shower drain and floor drain

6
New cards

Drum Trap

Kind of trap for bath tub

7
New cards

food waste disposal unit

Each such _____ shall be connected to a separate trap.

8
New cards

0. 6 meter

The vertical distance between a fixture outlet and the trap weir shall be as short as practicable, but in no case shall the tailpiece from any fixture exceed _____ in length.

9
New cards

siphonage and back-pressure

Each plumbing fixture trap. except as otherwise provided in this Code shall be protected against _____ and ____ by a properly placed vent pipe.

10
New cards

in no case less than two times the diameter of the trap arm

Minimum distance from vent to trap.

11
New cards

ninety (90)

A trap arm may change direction without the use of a cleanout when such change of direction does not exceed _____ degrees.

12
New cards

76 mm

But for trap arms ____ in diameter and larger, the change of direction not exceeding 22%, no cleanout is required and for change of direction greater than 22% a cleanout is required at the bend

13
New cards

water closets

The vent pipe opening from a soil or waste pipe, except for _____ and similar fixtures, shall not be below the weir of the trap.

14
New cards

0.76 m

Distance of trap arm to vent: 32 mm dia. trap

15
New cards

1.07 m

Distance of trap arm to vent: 38 mm dia. trap

16
New cards

1.52 mm

Distance of trap arm to vent: 51 mm dia. trap

17
New cards

1.83 mm

Distance of trap arm to vent: 76 mm dia. trap

18
New cards

3.05 mm

Distance of trap arm to vent: 102 mm dia. trap

19
New cards

1.8 meters or 6 feet

The developed length between the trap of a water closet or similar fixture measured from the top of closet ring (closet flange) to inner edge of vent shall not exceed ______________.

20
New cards

Gauge 17 B & S (1.1 mm)

Gauge of exposed and readily accessible brass tubing trap.

21
New cards

trap arm

The trap size should be the same size as the (____________) to which it is connected.

22
New cards

self-cleaning

Each trap, except one for an interceptor or similar device shall be ____________.

23
New cards

brass

An exposed and readily accessible drawn ______________ tubing trap, not less than Gauge 17 B & S (1.1 mm) may be used on fixtures discharging domestic sewage but shall exclude urine.

24
New cards

drum trap

No ____ shall be installed without a vent.

25
New cards

True - but may be installed if permitted by AA for special condition

T or F: Drum trap is prohibited

26
New cards

1) S trap

2) Bell trap

3) Crown-vented trap

Prohibited traps (3)

27
New cards

102 mm

Each fixture trap shall have a water seal of not less than 51 mm and not more than _____ deep except where a deeper seal is found necessary.

28
New cards

erect and true

Traps shall be set ___________ with respect to their water seals.

29
New cards

backwater valve

When subject to reverse flow of sewage or liquid waste, such floor drains shall be equipped with an approved ___________ valve.

30
New cards

shut-off valve

When automatic trap priming devices are installed, they shall be accessible for maintenance and provided by an accessible ____________ valve.

31
New cards

Interceptors or clarifiers

_________________ shall be provided when, in the judgment of the Administrative Authority, they are necessary for the proper handling of liquid wastes containing grease, flammable wastes, sand, solids, acid or alkaline substances, or other ingredients harmful to the building drainage system, the public or private sewer and sewage disposal system.

32
New cards

152 mm

Interceptors or clarifiers for sand and similar heavy solids shall be so designed and located as to be readily accessible for cleaning and shall have a water seal of not less than _____ deep.

33
New cards

screening device

Every fish, fowl and animal slaughter house or establishments and every fish, fowl and meat packing or curing establishments shall drain or discharge through a __________ device and thence into a grease interceptor (clarifier) for proper disposal of effluents.

34
New cards

grease trap

A ______________ is not required for individual dwelling units or for any private living quarters.

35
New cards

3.4 liters

No individual grease trap shall be installed for a facility that has an approved rate of flow of more than _____ per second nor less than 1.3 L/s,

36
New cards

Flow control

__________________ devices shall be so designed that the flow through such device or devices shall at no time be greater than the rated capacity of the grease trap.

37
New cards

two and one-half

The total capacity of fixtures discharging into any such grease trap shall not exceed _____ times the certified liters per minute flow rate of the grease trap.

38
New cards

four (4)

No more than _____ separate fixture shall be connected to or discharged into one grease trap.

39
New cards

1.2 meters,

0.75 meters

An approved-type grease trap may be used as a fixture outlet and the grease trap for a single fixture when the horizontal distance between the fixture outlet and the grease trap does not exceed _______________ and the vertical tailpipe or drain does not exceed _______________ meters.

40
New cards

51 mm

Each grease trap shall have an approved water seal of not less than _____ in depth or the diameter of its outlet whichever is greater.

41
New cards

18 kg

Table 10-2

Grease retention capacity for 1 fixture connected with required flow rate of 76L/min

42
New cards

23 kg

Table 10-2

Grease retention capacity for 2 fixture connected with required flow rate of 95L/min

43
New cards

32 kg

Table 10-2

Grease retention capacity for 3 fixture connected with required flow rate of 132L/min

44
New cards

45 kg

Table 10-2

Grease retention capacity for 4 fixture connected with required flow rate of 189L/min

45
New cards

Number of meals per peak hour

Sizing of Grease Interceptors

NWRF = interceptor size

N stands for _____

46
New cards

Waste Flow Rate

Sizing of Grease Interceptors

NWRF = interceptor size

W stands for _____

47
New cards

Retention times

Sizing of Grease Interceptors

NWRF = interceptor size

R stands for _____

48
New cards

Storage Factor

Sizing of Grease Interceptors

NWRF = interceptor size

F stands for _____

49
New cards

6 gallon (22.7L)

Waste Flow rate with dishwashing machine

50
New cards

5 gallon ( 18.9L)

Waste Flow rate without dishwashing machine

51
New cards

2 gallon (7.6L)

Waste Flow rate for single service kitchen

52
New cards

1 gallon (3.8L)

Waste Flow rate with food waste disposer

53
New cards

2.5 hrs

Retention time for commercial kitchen waste dishwasher

54
New cards

1.5 hrs

Retention time for single service kitchen single serving

55
New cards

1

Storage Factors for Fully equipped commercial kitchen - 8hrs

56
New cards

2

Storage Factors for Fully equipped commercial kitchen - 16hrs

57
New cards

3

Storage Factors for Fully equipped commercial kitchen - 24hrs

58
New cards

1.5

Storage Factors for Single Service kitchen

59
New cards

wire basket

Laundry equipment that does not have integral strainers shall discharge into an interceptor having a _____

60
New cards

one

Multiple floor drains may discharge into __________ sand interceptor.

61
New cards

76 mm

The outlet pipe of sand interceptor shall be the same size as the inlet size of the oil interceptor, the minimum being ________ and the baffle shall have two (2) openings of the same diameter as the outlet pipe and at the same invert as the outlet pipe.

62
New cards

two (2)

The sand interceptor shall have an interior baffle for full separation of the interceptor into ___________ sections.

63
New cards

staggered

The openings of the sand interceptor shall be ______________ so that there cannot be a straight line flow between any inlet pipe and the outlet pipe.

64
New cards

0.2 sqm

The sand interceptor shall have a minimum dimension of ___________ for the net free opening of the inlet section.

65
New cards

610 mm

Minimum depth under the invert of the outlet pipe of a sand interceptor.

66
New cards

0.09 sqm

For each 18.9 L per minute flow or fraction thereof over 75.7 L per minute the area of the sand interceptor inlet section is to be increased by _____.

67
New cards

fifty (50) percent

The outlet section of sand interceptor shall at all times have a minimum area of _____ of the inlet section.