Vocabulary practice flashcards covering fundamental PLC operation, ladder logic programming, Grafcet/SFC sequential control, diagnostic procedures, and industrial automation technology.

38 Terms

1
New cards

Scan Cycle (PLC)

The sequential three-stage operational cycle executed continuously by a PLC in RUN mode: reading inputs into the Process Image Input (PII), executing the user application program rungs, and updating field actuators via the Process Image Output (PIO).

2
New cards

Process Image Input (PII)

A dedicated internal memory area updated once at the start of each scan cycle that buffers physical input states, ensuring program execution remains immune to contact bounce or mid-scan sensor fluctuations.

3
New cards

Watchdog Timer (WDT)

A dedicated hardware/software supervisory timer that monitors scan duration; if an infinite loop (deadlock) or software fault causes the scan time to exceed the preset limit, the CPU halts and shifts into STOP mode.

4
New cards

First Scan Flag

A special system status bit (such as SM0.1SM0.1 in Siemens S7-200 or S:1/15S:1/15 in Allen-Bradley SLC 500) that remains TRUE for exactly one scan cycle upon transitioning from STOP to RUN to initialize preset values and routine parameters.

5
New cards

Immediate I/O Instruction

A specialized PLC command (such as %I0.0:P\%I0.0:P or %Q0.0:P\%Q0.0:P) that bypasses the process image update tables to read directly from input hardware or write immediately to physical output terminals during program execution.

6
New cards

Double Coil Hazard

A programming defect where the same physical output coil is programmed across multiple rungs; the logic result evaluated on the final rung overwrites the earlier rungs before the PIO writes to field hardware.

7
New cards

Optocoupler (Opto-isolator)

An optical coupling component integrated within PLC I/O modules that transmits signals via light, providing galvanic electrical isolation between field voltages and internal 5 VDC5\,\text{VDC} microprocessor circuitry.

8
New cards

Sinking Input Module

A DC input module configuration where conventional electric current flows into the module terminal from an external sourcing sensor, with the module common reference terminal (COM) connected to 0 VDC0\,\text{VDC}.

9
New cards

Sourcing Input Module

A DC input module configuration where current originates from the module terminal and flows out toward an external sinking (NPN) field sensor, with the module common terminal (COM) tied to positive voltage (+24 VDC+24\,\text{VDC}).

10
New cards

Relay Output Module

A mechanical contact output interface capable of switching both AC and DC voltages with high current tolerance, characterized by physical contact wear and slow switching speeds unsuitable for high-frequency pulsing.

11
New cards

Transistor Output Module

A solid-state semiconductor output interface designed strictly for DC loads that provides high-speed switching capabilities and virtually unlimited mechanical switching lifespan, suitable for pulse generation (PTO/PWM).

12
New cards

Bit Memory (\%M / Work Bit)

An internal relay memory area used within ladder logic to retain intermediate Boolean states, sequence markers, or interlocking flags without occupying physical output hardware terminals.

13
New cards

Retentive Memory

A non-volatile memory area sustained during primary power failures by a battery backup or supercapacitor, holding variables such as production counts and machine statuses across power cycles.

14
New cards

Instance Data Block (Instance DB)

A memory block specifically allocated to an individual call of a Function Block (FB) in Siemens architectures to preserve its static variables (VAR_STATIC\text{VAR\_STATIC}), timers, and internal counters across successive scan cycles.

15
New cards

Function (FC) vs. Function Block (FB)

An FC is a stateless subroutine without dedicated memory that uses temporary variables (VAR_TEMP\text{VAR\_TEMP}), whereas an FB maintains internal state memory between execution cycles via an assigned Instance DB.

16
New cards

State Conflict (Signal Overlap)

A sequential control issue where identical limit sensor patterns occur at different stages of a process (e.g., A+B+A−B−A+ B+ A- B-); resolved by assigning step memory flags (MStepM_{\text{Step}}) to track progression.

17
New cards

Initial Step (Grafcet / SFC)

The designated starting point in a sequential functional chart, depicted by a double-bordered square, which activates automatically upon PLC system initialization or transition to RUN mode.

18
New cards

Action Qualifier N (Non-stored)

A Grafcet action property where the commanded output remains energized only while the governing step is active, automatically de-energizing the moment the step deactivates.

19
New cards

Action Qualifier S (Set / Stored)

A Grafcet action property that latches an output continuously ON even after its step deactivates, requiring an explicit Reset (R) action in a subsequent step to turn it OFF.

20
New cards

OR Divergence (Grafcet)

A conditional sequence branching represented by a single horizontal line where only one path is activated based on whichever downstream transition evaluates to TRUE first.

21
New cards

AND Divergence (Grafcet)

A parallel branching structure indicated by a double horizontal line that simultaneously activates all underlying sequence paths once the single upstream transition condition becomes TRUE.

22
New cards

Seal-In Circuit (Latch Circuit)

A ladder configuration where a normally open (NO) contact from the output coil is wired in parallel with a momentary start pushbutton to maintain electrical conduction after the pushbutton is released.

23
New cards

Hardware Interlock

A hardwired protective circuit using physically cross-wired normally closed (NC) auxiliary contacts between reversing contactors to prevent phase-to-phase short circuits if software or contacts mechanically fail.

24
New cards

Positive Edge Detection (-[P]-)

A ladder logic instruction that detects a low-to-high (0→10 \rightarrow 1) transition, generating a single-scan TRUE pulse to prevent repeated counts from contact chatter or prolonged input closure.

25
New cards

Negative Edge Detection (-[N]-)

A ladder logic instruction that detects a high-to-low (1→01 \rightarrow 0) transition, producing a TRUE pulse for exactly one scan cycle when the monitored operand turns OFF.

26
New cards

Retentive On-Delay Timer (TONR)

A timer instruction that accumulates elapsed time while its input condition is TRUE and preserves the current value (ETET) when the input drops to FALSE, resuming count upon re-enable until an explicit Reset (RR) executes.

27
New cards

High-Speed Counter (HSC)

A dedicated hardware-based counter integrated directly into the PLC processor that tallies high-frequency pulse trains (10 kHz10\,\text{kHz} to several hundred kHz\text{kHz}) independently of the CPU scan cycle.

28
New cards

Live Zero (4–20 mA Standard)

An analog signaling standard where 4 mA4\,\text{mA} represents 0%0\% process scale; a reading falling to 0 mA0\,\text{mA} indicates an abnormal open-circuit or severed cable condition rather than zero process value.

29
New cards

Master Control Relay (MCR)

A zone-level instruction boundary where de-energizing the master condition unconditionally forces all internal standard non-retentive coils to de-energize (00), regardless of the individual rung logic states.

30
New cards

Forcing (Force Table)

A software debugging operation that writes fixed Boolean or numerical values directly into the physical I/O boundary, locking points regardless of field inputs or program evaluation results.

31
New cards

Diagnostic Buffer

A non-volatile internal CPU log that archives hardware faults, software exceptions, memory overflows, and execution stoppages alongside timestamps and error codes for root-cause analysis.

32
New cards

Lockout / Tagout (LOTO)

A standard electrical safety maintenance procedure: notifying operators, de-energizing the primary disconnect, securing it with an individual padlock, applying a warning tag, and testing for zero energy before servicing.

33
New cards

Safety PLC (Fail-Safe Controller)

A specialized PLC (such as Siemens S7-1200F/1500F) identifiable by a yellow housing, equipped with redundant processing cores executing parallel voting logic to drive the system to a de-energized fail-safe state upon mismatch.

34
New cards
<p>Two-Tank Chemical Mixing System</p>

Two-Tank Chemical Mixing System

A dual-vessel mixing process governed by inputs PB (operates both Tank 1 and Tank 2 for 30 s30\,\text{s}), PB1 (Tank 1 for 30 s30\,\text{s}), and PB2 (Tank 2 for 30 s30\,\text{s}), with leak sensors S1/S2 triggering emergency alarm Q0.2.

35
New cards
<p>Water Drainage and Agitation System</p>

Water Drainage and Agitation System

An automated tank process where pressing PB1 opens supply valve MV1 and runs agitator motor M until reaching high-level sensor TLB1; MV1 and M then halt, and drain valve MV2 discharges liquid down to low-level sensor TLB2.

36
New cards
<p>Two-Route Traffic Light Intersection</p>

Two-Route Traffic Light Intersection

A 4-way traffic junction automation schema orchestrating Route 1 (Green 60 s60\,\text{s}, Yellow 10 s10\,\text{s}, Red 60 s60\,\text{s}) against Route 2 (Green 50 s50\,\text{s}, Yellow 10 s10\,\text{s}, Red 70 s70\,\text{s}) across a total 130 s130\,\text{s} cycle.

37
New cards
<p>Material Dispensing and Conveyor System</p>

Material Dispensing and Conveyor System

A bulk filling station where Motor 1 transports a dispenser arm from limit switch LS1 (Point A) to LS2 (Point B), Pump 1 fills the receiver tank to sensor S1, and discharge valve V1 and Pump 2 drain it to sensor S2 before return.

38
New cards
<p>Paint Mixing System X</p>

Paint Mixing System X

A batch mixing process where Valve 1 and Valve 2 fill a tank to sensor S1, a motor agitates with 5 forward/reverse cycles (5 s5\,\text{s} forward, 5 s5\,\text{s} reverse), Valve X drains to sensor S2, and the system halts after 3 batches.