Vocabulary practice flashcards covering fundamental PLC operation, ladder logic programming, Grafcet/SFC sequential control, diagnostic procedures, and industrial automation technology.
Scan Cycle (PLC)
The sequential three-stage operational cycle executed continuously by a PLC in RUN mode: reading inputs into the Process Image Input (PII), executing the user application program rungs, and updating field actuators via the Process Image Output (PIO).
Process Image Input (PII)
A dedicated internal memory area updated once at the start of each scan cycle that buffers physical input states, ensuring program execution remains immune to contact bounce or mid-scan sensor fluctuations.
Watchdog Timer (WDT)
A dedicated hardware/software supervisory timer that monitors scan duration; if an infinite loop (deadlock) or software fault causes the scan time to exceed the preset limit, the CPU halts and shifts into STOP mode.
First Scan Flag
A special system status bit (such as SM0.1 in Siemens S7-200 or S:1/15 in Allen-Bradley SLC 500) that remains TRUE for exactly one scan cycle upon transitioning from STOP to RUN to initialize preset values and routine parameters.
Immediate I/O Instruction
A specialized PLC command (such as %I0.0:P or %Q0.0:P) that bypasses the process image update tables to read directly from input hardware or write immediately to physical output terminals during program execution.
Double Coil Hazard
A programming defect where the same physical output coil is programmed across multiple rungs; the logic result evaluated on the final rung overwrites the earlier rungs before the PIO writes to field hardware.
Optocoupler (Opto-isolator)
An optical coupling component integrated within PLC I/O modules that transmits signals via light, providing galvanic electrical isolation between field voltages and internal 5VDC microprocessor circuitry.
Sinking Input Module
A DC input module configuration where conventional electric current flows into the module terminal from an external sourcing sensor, with the module common reference terminal (COM) connected to 0VDC.
Sourcing Input Module
A DC input module configuration where current originates from the module terminal and flows out toward an external sinking (NPN) field sensor, with the module common terminal (COM) tied to positive voltage (+24VDC).
Relay Output Module
A mechanical contact output interface capable of switching both AC and DC voltages with high current tolerance, characterized by physical contact wear and slow switching speeds unsuitable for high-frequency pulsing.
Transistor Output Module
A solid-state semiconductor output interface designed strictly for DC loads that provides high-speed switching capabilities and virtually unlimited mechanical switching lifespan, suitable for pulse generation (PTO/PWM).
Bit Memory (\%M / Work Bit)
An internal relay memory area used within ladder logic to retain intermediate Boolean states, sequence markers, or interlocking flags without occupying physical output hardware terminals.
Retentive Memory
A non-volatile memory area sustained during primary power failures by a battery backup or supercapacitor, holding variables such as production counts and machine statuses across power cycles.
Instance Data Block (Instance DB)
A memory block specifically allocated to an individual call of a Function Block (FB) in Siemens architectures to preserve its static variables (VAR_STATIC), timers, and internal counters across successive scan cycles.
Function (FC) vs. Function Block (FB)
An FC is a stateless subroutine without dedicated memory that uses temporary variables (VAR_TEMP), whereas an FB maintains internal state memory between execution cycles via an assigned Instance DB.
State Conflict (Signal Overlap)
A sequential control issue where identical limit sensor patterns occur at different stages of a process (e.g., A+B+A−B−); resolved by assigning step memory flags (MStep) to track progression.
Initial Step (Grafcet / SFC)
The designated starting point in a sequential functional chart, depicted by a double-bordered square, which activates automatically upon PLC system initialization or transition to RUN mode.
Action Qualifier N (Non-stored)
A Grafcet action property where the commanded output remains energized only while the governing step is active, automatically de-energizing the moment the step deactivates.
Action Qualifier S (Set / Stored)
A Grafcet action property that latches an output continuously ON even after its step deactivates, requiring an explicit Reset (R) action in a subsequent step to turn it OFF.
OR Divergence (Grafcet)
A conditional sequence branching represented by a single horizontal line where only one path is activated based on whichever downstream transition evaluates to TRUE first.
AND Divergence (Grafcet)
A parallel branching structure indicated by a double horizontal line that simultaneously activates all underlying sequence paths once the single upstream transition condition becomes TRUE.
Seal-In Circuit (Latch Circuit)
A ladder configuration where a normally open (NO) contact from the output coil is wired in parallel with a momentary start pushbutton to maintain electrical conduction after the pushbutton is released.
Hardware Interlock
A hardwired protective circuit using physically cross-wired normally closed (NC) auxiliary contacts between reversing contactors to prevent phase-to-phase short circuits if software or contacts mechanically fail.
Positive Edge Detection (-[P]-)
A ladder logic instruction that detects a low-to-high (0→1) transition, generating a single-scan TRUE pulse to prevent repeated counts from contact chatter or prolonged input closure.
Negative Edge Detection (-[N]-)
A ladder logic instruction that detects a high-to-low (1→0) transition, producing a TRUE pulse for exactly one scan cycle when the monitored operand turns OFF.
Retentive On-Delay Timer (TONR)
A timer instruction that accumulates elapsed time while its input condition is TRUE and preserves the current value (ET) when the input drops to FALSE, resuming count upon re-enable until an explicit Reset (R) executes.
High-Speed Counter (HSC)
A dedicated hardware-based counter integrated directly into the PLC processor that tallies high-frequency pulse trains (10kHz to several hundred kHz) independently of the CPU scan cycle.
Live Zero (4–20 mA Standard)
An analog signaling standard where 4mA represents 0% process scale; a reading falling to 0mA indicates an abnormal open-circuit or severed cable condition rather than zero process value.
Master Control Relay (MCR)
A zone-level instruction boundary where de-energizing the master condition unconditionally forces all internal standard non-retentive coils to de-energize (0), regardless of the individual rung logic states.
Forcing (Force Table)
A software debugging operation that writes fixed Boolean or numerical values directly into the physical I/O boundary, locking points regardless of field inputs or program evaluation results.
Diagnostic Buffer
A non-volatile internal CPU log that archives hardware faults, software exceptions, memory overflows, and execution stoppages alongside timestamps and error codes for root-cause analysis.
Lockout / Tagout (LOTO)
A standard electrical safety maintenance procedure: notifying operators, de-energizing the primary disconnect, securing it with an individual padlock, applying a warning tag, and testing for zero energy before servicing.
Safety PLC (Fail-Safe Controller)
A specialized PLC (such as Siemens S7-1200F/1500F) identifiable by a yellow housing, equipped with redundant processing cores executing parallel voting logic to drive the system to a de-energized fail-safe state upon mismatch.

Two-Tank Chemical Mixing System
A dual-vessel mixing process governed by inputs PB (operates both Tank 1 and Tank 2 for 30s), PB1 (Tank 1 for 30s), and PB2 (Tank 2 for 30s), with leak sensors S1/S2 triggering emergency alarm Q0.2.

Water Drainage and Agitation System
An automated tank process where pressing PB1 opens supply valve MV1 and runs agitator motor M until reaching high-level sensor TLB1; MV1 and M then halt, and drain valve MV2 discharges liquid down to low-level sensor TLB2.

Two-Route Traffic Light Intersection
A 4-way traffic junction automation schema orchestrating Route 1 (Green 60s, Yellow 10s, Red 60s) against Route 2 (Green 50s, Yellow 10s, Red 70s) across a total 130s cycle.

Material Dispensing and Conveyor System
A bulk filling station where Motor 1 transports a dispenser arm from limit switch LS1 (Point A) to LS2 (Point B), Pump 1 fills the receiver tank to sensor S1, and discharge valve V1 and Pump 2 drain it to sensor S2 before return.

Paint Mixing System X
A batch mixing process where Valve 1 and Valve 2 fill a tank to sensor S1, a motor agitates with 5 forward/reverse cycles (5s forward, 5s reverse), Valve X drains to sensor S2, and the system halts after 3 batches.