Vocabulary flashcards covering electrical tariff structures, power factor concepts and penalties, and the principles and safety procedures for Current Transformers (CTs) and Voltage Transformers (VTs).

23 Terms

1
New cards

Electrical Tariffs

The pricing structures and methods by which the Supply Authority charges consumers for electricity, designed to cover fixed costs, running costs, and incentivise efficient grid use.

2
New cards

Fixed Costs (Tariff Basis)

Supply Authority expenditures—such as power stations, network infrastructure, and staffing—that exist regardless of whether any electricity units are consumed.

3
New cards

Running Costs (Tariff Basis)

Operational costs, primarily fuel, that fluctuate directly with the number of kWh\text{kWh} consumed.

4
New cards

Maximum Demand (MD)

The highest kW\text{kW} or kVA\text{kVA} drawn by an installation during a preset time window, typically 1515 or 30 min30\,\text{min}.

5
New cards

Load Factor

The ratio of average load to maximum demand over a specified timeframe, where a high factor represents steady consumption and a low factor represents peaky, penalised use.

6
New cards

Diversity Factor

The ratio of the sum of individual maximum demands to the coincident maximum demand of the entire group; it is always >1>1, enabling ESB to size supply equipment below total connected load.

7
New cards

Two-Part Tariff

A billing arrangement combining a daily standing charge (\text{\euro/day}) to fund network capacity and a unit charge (\text{\euro/kWh}) to cover consumed energy.

8
New cards

Time of Use / Smart Tariff

A tariff structure enabled by smart meters where electricity rates vary hour-by-hour based on grid demand, charging peak rates between 17:0017:00 and 19:0019:00.

9
New cards

Active Power (kW\text{kW})

The working component of electrical power that performs tangible work such as heat, light, and mechanical output, and is directly billed to consumers.

10
New cards

Reactive Power (kVAr\text{kVAr})

The non-working power required to sustain magnetic fields in inductive apparatus (such as motors and transformers); it is not billed directly but induces additional line current.

11
New cards

Apparent Power (kVA\text{kVA})

The vector sum of total power supplied to an alternating current circuit, expressed mathematically as kVA=kW2+kVAr2\text{kVA} = \sqrt{\text{kW}^2 + \text{kVAr}^2}.

12
New cards

Power Factor (pf\text{pf})

The ratio of active power to apparent power (kWkVA=cos⁡(ϕ)\frac{\text{kW}}{\text{kVA}} = \cos(\phi)), which lags in inductive circuits.

13
New cards

ESB Networks National Code of Practice for Customer Interface

Technical regulations mandating that commercial/industrial consumers maintain a power factor ≥0.95\ge 0.95 lagging, penalising lower values via kVA\text{kVA} MD charges and permitting refusal of connections below 0.850.85.

14
New cards

Power Factor Correction Capacitors

Capacitor banks installed in parallel (single-phase) or in star/delta (three-phase) to supply leading kVAr\text{kVAr}, thereby neutralising the lagging kVAr\text{kVAr} demanded by inductive loads.

15
New cards

Current Transformers (CTs)

Toroidal-core instrument transformers designed to scale heavy primary line currents (100 A100\,\text{A} to 4000 A4000\,\text{A}) down to standardised secondary ratings of 5 A5\,\text{A} or 1 A1\,\text{A} for meters and relays while providing isolation.

16
New cards

CT Burden

The total load in volt-amperes (VA\text{VA}) connected across a current transformer's secondary circuit, which must not exceed its rated capacity to maintain accuracy.

17
New cards

Flick Test

A primary injection check performed during current transformer installation to verify the correct polarity of primary and secondary terminals.

18
New cards

CT Open-Circuit Secondary Hazard

A severe fault condition occurring when an active current transformer's secondary loop is opened, causing the primary current to drive dangerous kilovolt spikes, core saturation, and insulation breakdown.

19
New cards

Voltage Transformers (VTs)

Laminated-core step-down instrument transformers that scale high system voltages (such as 400 V400\,\text{V} or 11 kV11\,\text{kV}) down to 110 V110\,\text{V} for measurement and protection.

20
New cards

VT Short-Circuit Secondary Hazard

A condition where a low-impedance short on a voltage transformer's secondary draws destructive currents because it acts as a voltage source, necessitating secondary fusing.

21
New cards

Ferraris Disc

An aluminium rotor inside electromechanical kWh\text{kWh} meters that experiences torque proportional to real power (kW\text{kW}) generated by the interaction of voltage and current coils.

22
New cards

Maximum Demand Meter

An instrument designed to monitor and record the highest kVA\text{kVA} consumed across consecutive 1515 or 30 min30\,\text{min} periods, equipped with a reset mechanism.

23
New cards

Smart Meter

An electronic energy meter featuring two-way communication (via PLC, RF mesh, or 4G) that monitors electrical variables second-by-second and logs consumption in 30 min30\,\text{min} intervals.