Flashcards covering Chapter 4 Building Systems from IFSTA: stairway construction, elevator systems and emergency operations, vertical utility chases, and HVAC smoke management.

52 Terms

1
New cards

What dual role do most stairs serve in a multistory building?

Stairs enable access to multiple levels of the structure and provide a means of egress during an emergency.

2
New cards

What distinct responsibilities do the building design team and building owner or management bear regarding life safety systems?

The building design team ensures systems initially provide the intended fire and life safety; the building owner and management must subsequently maintain those systems.

3
New cards

What are convenience stairs, and what is their typical code-mandated design limit?

Convenience stairs are stairs that are not part of the means of egress; per building code limitations, they are generally open and connect only two levels.

4
New cards

What stairway access requirement applies to buildings that are four or more stories in height?

They may be required to include a stairway that extends to the roof to access rooftop mechanical equipment, identified by signage in the stairway.

5
New cards

What are the two primary components that make up an individual stair step?

The tread (commonly referred to as the run) and the riser (commonly referred to as the rise).

6
New cards

Why do prefabricated steel and precast concrete stairs present an elevated collapse hazard to firefighters during a fire?

Their connections are subject to highly concentrated loads, have little to no redundancy, and can completely fail when heated.

7
New cards

How can the open well-hole of return stairs aid fire department operations?

If of sufficient size, the well-hole can assist in the vertical deployment of fire department hose lines into a building.

8
New cards

What is the structural difference between modern scissor stair layouts and older scissor stair layouts?

Modern scissor stairs allow ingress and egress at each floor landing, whereas older designs return to every second floor, restricting egress to one corridor on even floors and the opposite corridor on odd floors.

9
New cards

Why do scissor stairs pose a tactical challenge for firefighters during hose line deployment?

The entry door from a specific stairwell onto the building floor alternates from level to level, altering the required hose lengths for fire attack on each floor.

10
New cards

What specific radius requirement must curved stairs satisfy under building codes?

The small radius of the full circle (BB) must be greater than or equal to twice the widest part of the stair tread (AA) (B≥2AB \ge 2A), with a minimum run width usually of 10 inches10\text{ inches} (250 mm250\text{ mm}).

11
New cards

Under what circumstance are spiral stairs generally permitted as part of the means of egress?

Because they are difficult to traverse, spiral stairs are generally allowed as part of the means of egress only within private residences.

12
New cards

What are folding stairs, and where are they most commonly installed?

Folding stairs are ladders added after construction to provide access to an attic space without a permanent stairway, typically located away from functional spaces in residential occupancies.

13
New cards

What are the structural features and slope of a ship's ladder?

A ship's ladder is a steeply angled stair device with a slope of 50∘50^\circ to 70∘70^\circ, equipped with flat surface rungs that overlap each other and handrails, designed for space-constrained applications.

14
New cards

How does the staggered design of an alternating tread device improve occupant egress safety at steep angles?

It increases tread depth at steep angles to save space while allowing a safer, face-forward descent without placing both feet on the same level.

15
New cards

What three architectural arrangements can serve as an acceptable area of refuge in a means of egress?

A stairway landing in a smokeproof enclosure, a balcony located adjacent to an exterior stair, or a protected vestibule adjacent to an exit enclosure.

16
New cards

Why are exterior fire escapes prohibited in new building construction?

They are inherently unstable because anchor points can fail without warning due to freeze-thaw cycles, weathering, environmental age, and inadequate mortar.

17
New cards

When do building codes mandate smokeproof stair enclosures?

For stairs serving buildings five stories or higher, and for stairs serving floor levels more than 30 feet30\text{ feet} (10 m10\text{ m}) below the level of exit discharge.

18
New cards

What is the fundamental difference between active and passive fire protection systems?

Active systems use moving mechanical or electrical parts requiring a power source or system activation (such as sprinklers and alarms); passive systems rely on stationary construction and materials to contain fire and smoke (such as fire walls and enclosures).

19
New cards

How does an active smokeproof stair enclosure maintain tenability during a fire?

A dedicated mechanical air-handling system forces air into the stairwell to generate positive pressure, keeping smoke out even when an enclosure door is opened to the fire floor.

20
New cards

How does a passive smokeproof enclosure keep smoke from infiltrating an exit stairway?

It routes occupants through a transitional space—such as an open-air balcony, an exterior-vented vestibule, or a smoke shaft—that exhausts smoke to the outside before it reaches the stair enclosure.

21
New cards

What safeguards prevent the failure of fire barriers where mechanical conveyor systems penetrate them?

Automatic stop controls, physical breaks in the conveyor line, multiple layers of doors or shutters, and water spray fixed fire suppression systems.

22
New cards

Under NFPA 13, what protection arrangement is commonly required for floor openings around escalators serving more than two floors?

An 18-inch18\text{-inch} (450 mm450\text{ mm}) deep draft curtain combined with a row of automatic sprinklers installed on all sides outside the draft curtain.

23
New cards

What standard establishes safety requirements for new elevators, escalators, and moving walkways in the United States?

ASME A17.1/CSA B44, Safety Code for Elevators and Escalators, published by the American Society of Mechanical Engineers.

24
New cards

How is movement controlled in a hydraulic elevator without the use of mechanical brakes?

Fluid is pumped under pressure into a cylinder containing a ram to raise the car; draining the fluid allows the car to lower by gravity, with speed controlled solely by the flow of hydraulic fluid.

25
New cards

Why are traction elevators the standard elevator type in buildings over six stories tall?

They are fast, energy-efficient, and do not possess the practical height limitations inherent to hydraulic or drum elevators.

26
New cards

How do hoist cables transmit motion to the car in a traction elevator system?

Hoist cables pass over a grooved drive sheave at the top of the hoistway and connect to counterweights; friction between the cables and the sheave drives the car up and down.

27
New cards

Why were hole-less and roped hydraulic elevators developed as alternatives to conventional hydraulic systems?

To eliminate the need for a deep well drilled into the ground for the ram, avoiding the risk of hydraulic fluid leaking into the soil and groundwater.

28
New cards

What is the practical height limitation for geared traction elevators, and what type is used for greater heights?

Geared elevators are limited to 250 feet250\text{ feet} (76.2 m76.2\text{ m}) because the gearing reduces drum speed; gearless elevators have no gearing restrictions and are used in taller high-rise buildings.

29
New cards

How do the mechanical brakes operate differently during normal stops on traction elevators with AC motors versus DC motors?

On AC motors, the mechanical brakes directly assist in stopping the car at the floor; on DC motors, the motor stops the car dynamically and the mechanical brakes engage only to hold the car in place.

30
New cards

How does a pneumatic vacuum elevator move its car between floors?

It uses a sealed vertical polycarbonate tube where air pressure is decreased above the car and increased below it to ascend, and reversed to descend, without any cables.

31
New cards

What is the function of elevator car safeties?

They are tapered pairs of steel jaws that wedge against the guide rails to bring an overspeeding or free-falling elevator car to a complete stop.

32
New cards

What is the limitation of elevator pit buffers during an uncontrolled descent?

Buffers (springs or hydraulic pistons) act only as shock absorbers to stop a car traveling at its normal operating speed; they cannot safely stop a free-falling car.

33
New cards

What safety purpose does an electrical shunt trip serve in an elevator hoistway or machine room?

It de-energizes the elevator electrical power supply before water discharge occurs from an activated sprinkler head.

34
New cards

Why do building codes require venting at the top of elevator hoistways?

To vent hot gases and smoke to the exterior and prevent them from mushrooming (spreading horizontally) into the upper floors of the building.

35
New cards

How many elevators are permitted in a single elevator hoistway under model building codes?

Up to three elevators may be placed in a single hoistway; four or more elevators require a minimum of two separate hoistways, with no more than four elevators in any single enclosure.

36
New cards

What rescue feature is mandated for single-car blind hoistways in high-rise express elevator zones?

Emergency access doors must be provided in the shaft where there are no typical hoistway landings, generally spaced every three floors.

37
New cards

What is a sky lobby in high-rise building design?

An intermediate transfer floor located high in a building that serves as a common discharge and loading level connecting two separate elevator systems serving different vertical zones.

38
New cards

How does a double-deck elevator system coordinate floor service?

Two cars permanently connected vertically move together in the same shaft; typically, the bottom car serves odd-numbered floors and the top car serves even-numbered floors.

39
New cards

What sequence occurs mechanically to open elevator car and hoistway doors simultaneously?

The car stops; the driving vane on the car door engages a roller that unlocks the hoistway door; the motor-driven car door pushes the hoistway door open.

40
New cards

What standard provides guidelines for emergency personnel performing rescues from stalled elevators?

ASME Standard A17.4, Guide for Emergency Personnel.

41
New cards

What are the rules regarding passenger emergency exit panels on elevator cars?

Top exits open outward and can all be opened from the exterior; side exits allow lateral transfer between cars in a shared hoistway and must have electrical interlocks that disable car movement when opened.

42
New cards

What threshold of vertical travel triggers mandatory Phase I emergency recall under the International Fire Code (IFC)?

Vertical travel exceeding 25 feet25\text{ feet} (7.5 m7.5\text{ m}) for passenger elevators.

43
New cards

What actions occur automatically when Phase I elevator recall is initiated?

Cars are prevented from serving the fire floor, recalled directly to the terminal lobby (or designated alternate floor), car doors open and remain open, and internal floor-selection and stop buttons are rendered inoperative.

44
New cards

How does an elevator operate once placed into Phase II firefighter service?

A key switch in the car overrides recall; floor-call buttons on individual floors remain inoperable, doors must be manually opened with the 'Door Open' button, the emergency stop button is enabled, and the electric eye safety is disabled.

45
New cards

What fire protection features are required for refuse and laundry chutes?

Noncombustible construction, fire-rated doors and shaft enclosures, automatic sprinklers at the top and in the terminal room, and intake openings located in separate dedicated rooms rather than open corridors.

46
New cards

What design requirements apply to commercial kitchen grease exhaust ducts?

They must run vertically to the exterior avoiding horizontal runs or dips where grease collects, and must be enclosed in fire-resistive shaft construction when penetrating rated floors or roofs.

47
New cards

Why do unprotected vertical pipe chases pose a fire hazard in buildings?

They create continuous, unenclosed vertical channels through floors that spread smoke, heat, and toxic gases throughout the structure.

48
New cards

At what fan capacity do building codes require duct smoke detectors to automatically shut down HVAC fans?

For fans with airflow capacities exceeding 2,000 cubic feet per minute2{,}000\text{ cubic feet per minute} (60 m3/min60\,\text{m}^3\text{/min}).

49
New cards

Why does the use of replacement refrigerants such as butane and propane pose a hazard during fire operations?

Butane and propane are flammable hydrocarbon gases that can ignite or explode if piping or chillers are damaged by fire.

50
New cards

What is the fire hazard of using building interstitial spaces, such as drop-ceiling plenums, for HVAC return air?

They allow smoke and fire to travel unimpeded above compartments, obscure the location of fire extension, and expose unprotected structural members to high heat.

51
New cards

Under NFPA 90A, what fire-resistance rating is required for HVAC duct shaft enclosures?

A 1-hour1\text{-hour} fire rating for buildings fewer than four stories in height, and a 2-hour2\text{-hour} fire rating for buildings four stories or higher.

52
New cards

How does an HVAC system operating in smoke control mode create a 'pressure sandwich' around a fire?

It exhausts smoke from the fire floor directly outside without recirculation, while continuing to supply clean air to the floors above and below to create higher pressure zones that contain smoke spread.