Vocabulary flashcards covering generator dependencies, high voltage values and transformers, cooling methods, and characteristics of Neutral Earthing Resistors.
Voltage Depends on what two things
Excitation and speed.
Polarization testing
Score over 2 is good
Test for one minute then 10 min
Induction testing
Time 10min
Divide by
Time 1min
Class makes you
Certified
Not
Qualified
HV Cable Insulation Generic Selection Criteria
The suitability of insulating material selected for HV transmission is determined by looking at each these properties:
Electric (dielectric) strength O Dielectric properties Thermal properties Mechanical properties Environmental suitability Processing possibilities Availability and costs
Neutral Earthed Resistor (NER)
A component connected to the neutral Wye that limits current flow to ground during a ground fault or phase loss. Key characteristics:
(1) only one is connected at a time across the whole ship to prevent voltage differential potential; (
2) monitored via a dedicated monitoring relay;
(3) prevents arcing during ground faults;
(4) sized to limit current flow from 1A to 500A; and
(5) does NOT operate in a short circuit.
Frequency Depends on what 2 factors
A/C Synchronous Motor Operation
Operates at a precise speed with no slip on the motor side, runs at synchronous speed or not at all, and maintains speed independently of the load.
Engine Size is Determined by what factor
Alternator size.
High Voltage Transformer is what kind?
A step-up transformer.
Typical High Voltage Values
4160VAC and 6,600VAC.
Generator Cooling Methods
Air to air, air to water, and water to air.
HV Generator Special Features
Connected as a WYE wound generator and connection to ground
Neutral Earthing Resistor (NER)
A resistor that in a phase loss or ground will limit the current flow to the ground in a ground fault, used to prevent arcing during ground faults.
Neutral Earthing Resistor is connected how
Connecting only one resistor at a time (to the neutral Wye) to prevent voltage differential potential.
Neutral Earthing Resistor Sizing and Limitations
Can be sized to limit current flow from 1A to 500A, is monitored via the NER Monitoring Relay, and does NOT work in a short circuit.

characteristics of a Neutral Earthing Resistor?
A) Is a resistor that in a phase loss or ground will limit the current flow to the ground in a ground fault
b) Only one is connected at a time (to the neutral Wye) to prevent voltage differential potential
C Monitored via the NER Monitoring Relay Used to prevent arcing during ground faults
D Can be sized to limit current flow from 1A to 500A
f Does NOT work in a short circuit
A/C Induction Motor Operation
Most common type_of A/C motor
because:
◦ Slip between rotor and supplied frequency is only 1 to 5 %.
◦ Power converters adjust for slip with_motors_ paired to_ another
Direction of rotation is changed in PWM or by changing any two leads in the power supply.
◦ Cooled by air- the rotor has an attached fan
A/C Synchronous Motor Power Factor Correction
Able to operate and provide power factor corrections depending on the excitation of the rotor.
A/C Synchronous Motor Holding Position Condition
Holds position when a DC current is applied to both the stator and the rotor windings.
A/C Synchronous Motor Speed Formula
RPM=60×(number of pole pairsHz)
A/C Synchronous Motor Direction of Rotation
Changed by swapping two leads of the power supply in the power modulator.
A/C Synchronous Motor Cooling Method
Cooled by air through winding gaps.
Major advantage of pulse Width Modulator Variable Frequency Drive
can use standard induction motor
Major disadvantage of pulse width modulator variable frequency drive.
Will not allow power to be back fed into system for braking
Define Dielectric Constant
The ratio between the capacitance of the material to the capacitance of a vacuum is Dielectric constant
Define Dielectric Strength
The maximum electric field that the material can withstand under ideal conditions without undergoing electrical breakdown and becoming electrically conductive
Definition of... Breakdown or critical voltage.
The minimum voltage that causes a portion of an insulator to experience electrical breakdown and become electrically conductive is the definition of.. Breakdown or critical voltage.
Define partial discharge.
A spark or arc that occurs in a defect in insulation the definition of... partial discharge.
definition of.. Breakdown strength
The minimum voltage for spark breakdown to occur across a material of given thickness held between electrodes producing a uniform electric field iS the definitior of.. Breakdown strength
Insulation
Electrically nonconductive material used in bulk to wrap electrical cables or other equipment.
Define insulating
Support and separate electrical conductor. that do not allow current to pass through them is the definition of. Insulators.
Dedicated Propulsion (DP) Plant
A shipboard system that exclusively powers vessel motion without supplying house electricity, typically using slow-speed or medium diesel engines.
Integrated Electrical Plant (IEP)
A centralized electrical network that provides power for hotel and auxiliary services in addition to vessel propulsion.
Four Marine Prime Movers
Pods, diesel-mechanical propulsion, and electrical propulsion.
Slow speed diesel engine
Medium Speed Diesel engine
Gas turbine
Steam engine
Four Marine Prime Movers
Slow-speed diesel engines, medium-speed diesel engines, gas turbines, and steam turbines.
Advantages of an Integrated Electrical Plant (IEP)
Potential for lower fuel costs, flexible layout allowing generator placement anywhere, lower weight, and reduced vibration and noise

Name 1 through ten in attached diagram
1 prime movers
2 generator
3 switch board
4 neutral earth resistor
5 transformer
6 transformer
7 harmonic filter
8 vfd
9 excitor
10 propulsion elect motor

Name 1 through ten in attached diagram
1 prime movers
2 generator
3 switch board
4 neutral earth resistor
5 transformer
6 transformer
7 harmonic filter
8 vfd
9 excitor
10 propulsion elect motor
Ac induction motor oeration
Power conversation adjusts for slip with motors paired to one another
Third Harmonic creates what problem
Heat
Passive Harmonic Filter works how
Absorbs frequency by creating a path of low impedance tuned to one frequency 3rd,5th,7th,9th,11t
Low voltage vs high voltage enclosures
Low voltage is metal enclosure
High voltage is metal clad ie. Controls and circuit breaker etc all in their own enclosure
ACTIVE HARMONIC FILTER WORKS HOW?
"Active" works by injecting opposing waveforms to cancel out harmonics
Standoff insulators
Typically made of epoxy resin ◦ Resist high vibration and heat present in marine environment
Maintain electrical isolation of current conducting materials from other materials that could conduct current but are used as a support.
How does "Drive Dedicated/Broadband" harmonic filter work
"Drive Dedicated/Broadband" = Tuned to 2 to 3 frequency's 3rd and 5th etc., placed on an individual drive
IEP DISADVANTAGES
Higher cost initially
Higher training requirements
Higher chance if Higher voltage accidents
Need to regenerate power
Special requirements for High Voltage (HV) systems
Grounded systems, power factor corrections, increased insulation size relative to conductor size, additional safety measures, decreased motor size with increased power availability, power switching capability, and physical equipment design.
Disadvantages of an Integrated Electrical Plant (IEP)
Higher initial equipment cost, higher crew training requirements, greater electrical hazard, and the need to handle regenerative power.
What Voltage separates HV from LV?
1000 VAC
Name two types of propulsion electric motor...
Fixed pods, azimuthing pods, traditional PEMs with a line shaft output
Name three specifications for a HV generator
Three-phase; Wye wound; Brushless; Synchronous; 60Hz; 4.16 kV, 6.6 kV, 11 kV, or 13 kV; increased insulation requirements
Name the two most common types of shipboard HV Voltage ratings
4160
6.6kv
What does every PEM produce that must be taken into account in both design and operation?
Heat generation
Advantages of podded propulsion
Extremely maneuverable; Can be push or pull; can be forward facing , aft facing, fixed in position, or azimuthing 360 degrees; No rudder required; Can use speed or pitch control or a combination of both
Potential Electrical Energy Hazards in HV Systems
Shock (exposure to electrical current flow), arc (discharge of electrical current through the air), arc flash, and arc blast.
Three Methods of Describing Arc Faults
Level of energy released: In terms of system voltage and current.
Type of occurrence: Prime power outage, propulsion disruption, or service interruption.
Damage: Due to the cumulative, destructive effect of the energy released.
Five Types of Arcs
Open air arc: Exposed arc from conductors in a non-confined space.
Arc in a box: Directed via an enclosure that focuses it outwards, multiplying energy 2 to 12 times.
Ejected arc: Arc plasma that hits the worker.
Tracking arc: Arc plasma conducting on skin or through clothing.
Running arc: Arc traveling along a conductor.
Open Air Arc
An exposed electrical arc originating from conductors in an unconfined space.
Arc in a Box
An electrical arc directed via an enclosure that focuses it outwards, multiplying the energy 2 to 12 times.
Ejected Arc
An arc condition where arc plasma directly hits or strikes the worker.
Tracking Arc
An electrical arc where plasma conducts along the skin or through clothing.
Running Arc
An electrical arc that travels along the length of a conductor.
Factors Affecting Electrical Shock Severity
Voltage
2. Amount of current conducted through the body
3. Path of the current through the body
List 5 types of Arcs
Open air arc: exposed arc from cond uctors in non confined space; arc in a box: directed via the box focuses it outwards multiplies energy two to twelve times; ejected arc: when arc plasma hits the worker; tracking arc: arc plasma conducts on skin or through clothing; running arc: along a conductor.
Effects of Contact with Live Conductors
Burns, nervous system damage, dismemberment, and death.
Describe arc flash and arc blast hazards
Exposure can result in a variety of serious injuries and may even be fatal, equipment can suffer permanent damage and nearby inflammable materials may be ignited resulting in secondary fires.
How the human element can contribute to accidents.
Human factors such as distraction, lack of situational awareness, fatigue, stress, you name it, 7 it can adversely affect your ability to realize the potentially deadly exposure you have allowed yourself to get into. Be wary
How does ppe mitigate risk when you wear it
. PPEis the lowest level method of risk mitigation but, it MAY save your life
List methods of establishing safe working conditions
LOTO
GROUNDING
TOOLBOX TALK
JSA
Qualified assistant
Permit to work
Ppe
Primary arc protection is ONLY
Gloves
After this course you are
Qualified
2. How is a Restricted Approach Boundary determined?
. Boundary is determined by system voltage and component
State the difference between Danger and Warning headers on equipment markings.
Metal Clad for HV and Metal Enclosure for LV.
Certified vs Qualified
Certified # Qualified, The higher risk present in HV systems implies that personnel should have proven skill before being assigned HV tasks. Qualified personnel are as defined by OSHA, are "..capable, as determined by their electrical knowledge and skills, of working safely on energized circuits." This capability includes familiarity with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials and insulated tools. This is very important concept.
Warning vs Danger what is voltage
What color is warning
. 5. Warning=under 600 V typically (Orange in color)Danger=Over 600 V typically (red in color).
s. Describe the value of a trapped key system when limited personnel access is required. controls access
Keys are locked in a position that can control power or access to system or area.
Boundaries
3 types
. Limited Approach, Restricted Approach, Arc Flash
1. How do you disconnect grounding cables
. Disconnect all 3 phase cables then disconnect ground. (Opposite procedure of connecting) first.