Generator Systems and Neutral Earthing Resistors

0.0(0)
Studied by 0 people
call kaiCall Kai
learnLearn
examPractice Test
spaced repetitionSpaced Repetition
heart puzzleMatch
flashcardsFlashcards
GameKnowt Play
Card Sorting

1/82

flashcard set

Earn XP

Description and Tags

Vocabulary flashcards covering generator dependencies, high voltage values and transformers, cooling methods, and characteristics of Neutral Earthing Resistors.

83 Terms

1
New cards

Voltage Depends on what two things

Excitation and speed.

2
New cards

Polarization testing

Score over 2 is good

Test for one minute then 10 min

Induction testing

Time 10min

Divide by

Time 1min

3
New cards

Class makes you

Certified

Not

Qualified

4
New cards

HV Cable Insulation Generic Selection Criteria

The suitability of insulating material selected for HV transmission is determined by looking at each these properties:

Electric (dielectric) strength O Dielectric properties Thermal properties Mechanical properties Environmental suitability Processing possibilities Availability and costs

5
New cards

Neutral Earthed Resistor (NER)

A component connected to the neutral Wye that limits current flow to ground during a ground fault or phase loss. Key characteristics:

(1) only one is connected at a time across the whole ship to prevent voltage differential potential; (

2) monitored via a dedicated monitoring relay;

(3) prevents arcing during ground faults;

(4) sized to limit current flow from 1 A1\,\text{A} to 500 A500\,\text{A}; and

(5) does NOT operate in a short circuit.

6
New cards

Frequency Depends on what 2 factors

Number of poles and speed.


7
New cards

A/C Synchronous Motor Operation

Operates at a precise speed with no slip on the motor side, runs at synchronous speed or not at all, and maintains speed independently of the load.

8
New cards

Engine Size is Determined by what factor

Alternator size.

9
New cards

High Voltage Transformer is what kind?

A step-up transformer.

10
New cards

Typical High Voltage Values

4160 VAC4160\,\text{VAC} and 6,600 VAC6,600\,\text{VAC}.

11
New cards

Generator Cooling Methods

Air to air, air to water, and water to air.

12
New cards

HV Generator Special Features

Connected as a WYE wound generator and connection to ground

13
New cards

Neutral Earthing Resistor (NER)

A resistor that in a phase loss or ground will limit the current flow to the ground in a ground fault, used to prevent arcing during ground faults.

14
New cards

Neutral Earthing Resistor is connected how

Connecting only one resistor at a time (to the neutral Wye) to prevent voltage differential potential.

15
New cards

Neutral Earthing Resistor Sizing and Limitations

Can be sized to limit current flow from 1 A1\,\text{A} to 500 A500\,\text{A}, is monitored via the NER Monitoring Relay, and does NOT work in a short circuit.

16
New cards
<p>characteristics of a Neutral Earthing Resistor?</p>

characteristics of a Neutral Earthing Resistor?

A) Is a resistor that in a phase loss or ground will limit the current flow to the ground in a ground fault

b) Only one is connected at a time (to the neutral Wye) to prevent voltage differential potential

C Monitored via the NER Monitoring Relay Used to prevent arcing during ground faults

D Can be sized to limit current flow from 1A to 500A

f Does NOT work in a short circuit

17
New cards

A/C Induction Motor Operation

Most common type_of A/C motor

because:

◦ Slip between rotor and supplied frequency is only 1 to 5 %.

◦ Power converters adjust for slip with_motors_ paired to_ another

Direction of rotation is changed in PWM or by changing any two leads in the power supply.

◦ Cooled by air- the rotor has an attached fan

18
New cards

A/C Synchronous Motor Power Factor Correction

Able to operate and provide power factor corrections depending on the excitation of the rotor.

19
New cards

A/C Synchronous Motor Holding Position Condition

Holds position when a DC current is applied to both the stator and the rotor windings.

20
New cards

A/C Synchronous Motor Speed Formula

RPM=60×(Hznumber of pole pairs)\text{RPM} = 60 \times \left(\frac{\text{Hz}}{\text{number of pole pairs}}\right)

21
New cards

A/C Synchronous Motor Direction of Rotation

Changed by swapping two leads of the power supply in the power modulator.

22
New cards

A/C Synchronous Motor Cooling Method

Cooled by air through winding gaps.

23
New cards

Major advantage of pulse Width Modulator Variable Frequency Drive

can use standard induction motor

24
New cards

Major disadvantage of pulse width modulator variable frequency drive.

Will not allow power to be back fed into system for braking

25
New cards

Define Dielectric Constant

The ratio between the capacitance of the material to the capacitance of a vacuum is Dielectric constant

26
New cards

Define Dielectric Strength

The maximum electric field that the material can withstand under ideal conditions without undergoing electrical breakdown and becoming electrically conductive

27
New cards

Definition of... Breakdown or critical voltage.

The minimum voltage that causes a portion of an insulator to experience electrical breakdown and become electrically conductive is the definition of.. Breakdown or critical voltage.

28
New cards

Define partial discharge.

A spark or arc that occurs in a defect in insulation the definition of... partial discharge.

29
New cards

definition of.. Breakdown strength

The minimum voltage for spark breakdown to occur across a material of given thickness held between electrodes producing a uniform electric field iS the definitior of.. Breakdown strength

30
New cards

Insulation

Electrically nonconductive material used in bulk to wrap electrical cables or other equipment.

31
New cards

Define insulating

Support and separate electrical conductor. that do not allow current to pass through them is the definition of. Insulators.

32
New cards

Dedicated Propulsion (DP) Plant

A shipboard system that exclusively powers vessel motion without supplying house electricity, typically using slow-speed or medium diesel engines.

33
New cards

Integrated Electrical Plant (IEP)

A centralized electrical network that provides power for hotel and auxiliary services in addition to vessel propulsion.

34
New cards

Four Marine Prime Movers

Pods, diesel-mechanical propulsion, and electrical propulsion.

Slow speed diesel engine

Medium Speed Diesel engine

Gas turbine

Steam engine

35
New cards

Four Marine Prime Movers

Slow-speed diesel engines, medium-speed diesel engines, gas turbines, and steam turbines.

36
New cards

Advantages of an Integrated Electrical Plant (IEP)

Potential for lower fuel costs, flexible layout allowing generator placement anywhere, lower weight, and reduced vibration and noise

37
New cards
<p>Name 1 through ten in attached diagram</p>

Name 1 through ten in attached diagram

1 prime movers

2 generator

3 switch board

4 neutral earth resistor

5 transformer

6 transformer

7 harmonic filter

8 vfd

9 excitor

10 propulsion elect motor



38
New cards
<p>Name 1 through ten in attached diagram</p>

Name 1 through ten in attached diagram

1 prime movers

2 generator

3 switch board

4 neutral earth resistor

5 transformer

6 transformer

7 harmonic filter

8 vfd

9 excitor

10 propulsion elect motor



39
New cards

Ac induction motor operation

Power conversation adjusts for slip with motors paired to one another

40
New cards
41
New cards
42
New cards

Third Harmonic creates what problem

Heat

43
New cards

Passive Harmonic Filter works how

Absorbs frequency by creating a path of low impedance tuned to one frequency 3rd,5th,7th,9th,11t

44
New cards

Low voltage vs high voltage enclosures

Low voltage is metal enclosure

High voltage is metal clad ie. Controls and circuit breaker etc all in their own enclosure

45
New cards

ACTIVE HARMONIC FILTER WORKS HOW?

"Active" works by injecting opposing waveforms to cancel out harmonics

46
New cards

Standoff insulators


Typically made of epoxy resin ◦ Resist high vibration and heat present in marine environment

Maintain electrical isolation of current conducting materials from other materials that could conduct current but are used as a support.

47
New cards

How does "Drive Dedicated/Broadband" harmonic filter work

"Drive Dedicated/Broadband" = Tuned to 2 to 3 frequency's 3rd and 5th etc., placed on an individual drive

48
New cards

IEP DISADVANTAGES

Higher cost initially

Higher training requirements

Higher chance if Higher voltage accidents

Need to compensate for regenerated power

Increased reliance on Automation

49
New cards

Special requirements for High Voltage (HV) systems

Grounded systems, power factor corrections, increased insulation size relative to conductor size, additional safety measures, decreased motor size with increased power availability, power switching capability, and physical equipment design.

50
New cards

Disadvantages of an Integrated Electrical Plant (IEP)

Higher initial equipment cost, higher crew training requirements, greater electrical hazard, and the need to handle regenerative power.

51
New cards

What Voltage separates HV from LV?

1000 VAC

52
New cards

Name two types of propulsion electric motor...

Fixed pods, azimuthing pods, traditional PEMs with a line shaft output

53
New cards

Name three specifications for a HV generator

Three-phase; Wye wound; Brushless; Synchronous; 60Hz; 4.16 kV, 6.6 kV, 11 kV, or 13 kV; increased insulation requirements

54
New cards

Name the two most common types of shipboard HV Voltage ratings

4160

6.6kv

55
New cards

What does every PEM produce that must be taken into account in both design and operation?

Heat generation

56
New cards

Advantages of podded propulsion


Extremely maneuverable;

Can be push or pull;

can be forward facing ,

aft facing,

fixed in position,

or azimuthing 360 degrees;

No rudder required; Can use speed or pitch control or a combination of both

57
New cards

Potential Electrical Energy Hazards in HV Systems

Shock (exposure to electrical current flow), arc (discharge of electrical current through the air), arc flash, and arc blast.

58
New cards

Three Methods of Describing Arc Faults

  1. Level of energy released: In terms of system voltage and current.

  2. Type of occurrence: Prime power outage, propulsion disruption, or service interruption.

  3. Damage: Due to the cumulative, destructive effect of the energy released.


59
New cards

Five Types of Arcs

  • Open air arc: Exposed arc from conductors in a non-confined space.

  • Arc in a box: Directed via an enclosure that focuses it outwards, multiplying energy 22 to 1212 times.

  • Ejected arc: Arc plasma that hits the worker.

  • Tracking arc: Arc plasma conducting on skin or through clothing.

  • Running arc: Arc traveling along a conductor.


60
New cards

Open Air Arc

An exposed electrical arc originating from conductors in an unconfined space.

61
New cards

Arc in a Box

An electrical arc directed via an enclosure that focuses it outwards, multiplying the energy 22 to 1212 times.

62
New cards

Ejected Arc

An arc condition where arc plasma directly hits or strikes the worker.

63
New cards

Tracking Arc

An electrical arc where plasma conducts along the skin or through clothing.

64
New cards

Running Arc

An electrical arc that travels along the length of a conductor.

65
New cards

Factors Affecting Electrical Shock Severity

  1. Voltage

  2. 2. Amount of current conducted through the body

  3. 3. Path of the current through the body


66
New cards

List 5 types of Arcs

Open air arc: exposed arc from cond uctors in non confined space;

arc in a box: directed via the box focuses it outwards multiplies energy two to twelve times;

ejected arc: when arc plasma hits the worker;

tracking arc: arc plasma conducts on skin or through clothing;

running arc: along a conductor.

67
New cards

Effects of Contact with Live Conductors

Burns, nervous system damage, dismemberment, and death.

68
New cards

Describe arc flash and arc blast hazards

Exposure can result in a variety of serious injuries and may even be fatal, equipment can suffer permanent damage and nearby inflammable materials may be ignited resulting in secondary fires.

69
New cards

How the human element can contribute to accidents.

Human factors such as distraction, lack of situational awareness, fatigue, stress, you name it,

it can adversely affect your ability to realize the potentially deadly exposure you have allowed yourself to get into. Be wary

70
New cards

How does ppe mitigate risk when you wear it

. PPE is the lowest level method of risk mitigation but, it MAY save your life

71
New cards

List methods of establishing safe working conditions

LOTO

GROUNDING

TOOLBOX TALK

JSA

Qualified assistant

Permit to work

Ppe

72
New cards

Primary arc protection is ONLY

Gloves

73
New cards

After this course you are

Certified

74
New cards

2. How is a Restricted Approach Boundary determined?

Boundary is determined by system voltage and component

75
New cards

State the difference between Danger and Warning headers on equipment markings.

Metal Clad for HV and Metal Enclosure for Lv

76
New cards

Metal clad enclosure

HV uses metal clad. All components including the bus, instrumentation, and main circuit breaker are enclosed in separate metal compartments to provide

: ◦ An additional level of safety.

o Ruggedness. Ease of maintenance

77
New cards

Metal enclosed


Metal Enclosed for LV

◦ All components including the bus, instrumentation and main circuit breaker are mounted in common compartments.

78
New cards

Certified vs Qualified

Certified # Qualified, The higher risk present in HV systems implies that personnel should have proven skill before being assigned HV tasks. Qualified personnel are as defined by OSHA, are "..capable, as determined by their electrical knowledge and skills, of working safely on energized circuits." This capability includes familiarity with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials and insulated tools. This is very important concept.

79
New cards

Warning vs Danger what is voltage

What color is warning

Warning=under 600 V typically (Orange in color)

Danger=Over 600 V typically (red in color).

80
New cards

Describe the value of a trapped key system when limited personnel access is required. controls access

Keys are locked in a position that can control power or access to system or area.

81
New cards

Boundaries

3 types

Limited Approach, Restricted Approach, Arc Flash

82
New cards

1. How do you disconnect grounding cables

. Disconnect all 3 phase cables then disconnect ground. (Opposite procedure of connecting) first.

83
New cards