Advanced Electrical Theory - Three Phase Voltages and Systems
- Exam Date: June 11 (Wednesday)
- Time: 9:00 AM to 3:00 PM
- Duration: One day, one attempt within the specified hours.
Three Phase Voltages
- Definition: Multiple (more than one) sinusoidal voltages separated by a phase angle.
- Common System: The most common polyphase system is the three-phase system (3-Φ).
- Applications: Commonly used in industrial applications.
- Labeling: Voltages can be labeled as:
- R (Red), B (Blue), W (White)
- A, B, C
- Phase Angles:
- V_A: Starts at 0 degrees (reference).
- VB: Lags VA by 120 degrees.
- VC: Lags VB by 120 degrees (lags V_A by 240 degrees).
Three-Phase Generator
- Simultaneously produces three sinusoidal voltages separated by 120 degrees.
- Two-pole configuration (North and South).
- Output: Three outputs (A, B, C), with 'A' connected to a common ground.
- Induction Motor Example: Three-phase induction motors produce rotor current through induction, not through slip rings and brushes.
Advantages of Three-Phase Systems
- Reduced Copper Wire Size: Requires less copper to carry current from generator to load, resulting in lighter, smaller wires.
- Constant Power: Produces constant power in the load, resulting in uniform energy conversion.
- Constant Rotating Magnetic Field: Maintains constant shaft speed on motors.
Types of Three-Phase Systems
- Y-Connected (Star Connection)
- Delta-Connected
Y-Connected (Star Connection) System
- Configuration: Generator coils connected in a 'Y' shape with a neutral point.
- Coil Connections:
- Each coil (A, B, C) has a start and end point (A', B', C').
- All end points are connected together at the star point.
- The star point is usually connected to neutral and grounded.
- Components:
- Three-phase load.
- Generator (often the secondary side of a three-phase transformer).
- Phase Voltage (V_{phase}): Voltage across the coil itself (from start to end).
- Phase Current (I_{phase}): Current flowing through the phase.
- Line Current (I_{line}): Current flowing out of the star point through the phase and into the line.
- Relationship: In a star-connected system, I{phase} = I{line}.
- Line Voltage (V_{line}): Voltage between any two lines.
- Relationship: V{line} = \sqrt{3} \times V{phase}.
Key Points of Y-Connected Systems
- Magnitude of each line current equals the corresponding phase current.
- Three line voltages exist, one across each phase voltage pair.
- Magnitude of each line voltage equals \sqrt{3} times the magnitude of the phase voltage.
- There is a 30-degree phase difference between each line voltage and the nearest phase voltage.
Voltage Standards
- Australia: Phase voltage is 240V, Line voltage is 415V (240 \times \sqrt{3} = 415).
- United States: Phase voltage is 120V, Line voltage is 208V (120 \times \sqrt{3} \approx 208).
Balanced vs Unbalanced Loads
- Balanced Load: Discussed when loads are perfectly balanced in Y-connected systems.
Advantages of Three-Phase Systems (Revisited)
- Thinner conductors can be used (less copper) to transmit the same kVA (kilovolt-amperes) at the same voltage. Copper usage is reduced by approximately 25%, lowering construction and maintenance costs.
- Lighter lines are easier to install, requiring less massive supporting structures.
- Three-phase equipment and motors have better running and starting characteristics due to a more even flow of power.
- Larger motors are typically three-phase because they are self-starting and don't require additional starting circuits.
Delta-Connected System
- Configuration: The end of one coil is connected to the start of the next coil, forming a closed loop (delta shape).
- Neutral: Delta connections do not have a neutral point.
- Line Voltage (V_{line}): Voltage between any two lines.
- Phase Voltage (V_{phase}): Voltage across the coil itself.
- Relationship: In a delta-connected system, V{line} = V{phase}.
- Line Current (I{line}): I{line} = \sqrt{3} \times I_{phase}.
Phase Diagrams
- Difference of 30 degrees between line and phase voltages is illustrated using phase diagrams.
- Phase sequence: Determined by the order in which the phase voltages pass through a fixed point.
Balanced and Unbalanced Systems
Balanced Systems
- Conditions:
- Currents in each line are the same.
- Load connected to each phase has the same power factor.
- Example: A three-phase system where each phase has a purely resistive load, and 150 amperes flow in each phase. The power factor is one (resistive load).
- Advantage: Balanced loads do not require a neutral wire.
Unbalanced Systems
- Single-phase loads:
- Star-connected systems can power both single-phase and three-phase loads.
- Delta-connected systems can only power three-phase loads.
- A three-phase four-wire (star-connected) system can supply 240V to single-phase loads by connecting them between any active line and the neutral.
- The neutral is connected between the star point and ground.
Calculations for Unbalanced Systems
- When systems are unbalanced, currents and power factors differ across phases. Vector math is required to analyze such systems.
- Example: Simulating the circuit and calculating values for voltages, current and resistance.
Neutral Current in Unbalanced Systems
- Assumption: Phase currents flowing out of the star point are positive; neutral current flowing into the star point is negative.
- Calculation Method: The neutral current equals the negative of the phasor sum of the line currents.
Power in Three-Phase Systems
Single-Phase Power (Review):
- Apparent Power (S) = V × I
- True Power (P) = V × I × Power Factor
- Reactive Power (Q)
- Power Factor = P/S
Three-Phase Balanced System Apparent Power Calculation:
- S = \sqrt{3} \times V{line} \times I{line}
Where
- V_{line} is the line voltage.
- I_{line} is the line current.
Three-Phase Balanced System True Power Calculation:
- P = \sqrt{3} \times V{line} \times I{line} \times Power Factor
Where
- V_{line} is the line voltage.
- I_{line} is the line current.
Power calculations in both star and delta connections are similar, but formulas vary depending on whether phase or line values are used. In balanced systems, power calculations can be simplified; in unbalanced systems, individual phase powers must be calculated and summed.