Domestic Electrical Installer – Section 1 Part A, Module 6: Electrical Inspection, Testing & Documentation

Pre-Work Survey: Core Questions and Decision Points

  • Earthing Arrangement

    • Identify whether the supply is TN-S, TN-C-S (PME), TN-C, TT, or IT.
    • Determine the supply characteristics (nominal voltage, prospective fault current, Ze, supplier’s service position).
    • Significance:
    • Influences disconnection times, Zs limits, and whether additional protective devices (e.g.
      RCDs) are mandatory.
  • Maximum Disconnection Time (BS 7671)

    • For final circuits 60 A supplying socket outlets ≤32\,\text{A}: 0.4\,\text{s} (TN systems).
    • For TT systems: 0.2\,\text{s} (for the same circuits) or 0.4\,\text{s} if RCD-protected.
    • Distribution circuits: 5\,\text{s} (TN) or 1\,\text{s} (TT).
    • Disconnection time ensures that touch-voltage U_T remains below safe thresholds during earth faults.
  • Isolation & Switching Requirements

    • Provide a main isolator: manually operated, mechanically linked, capable of switching all live conductors.
    • Verify functional switching devices for normal operation (e.g. switches, plug & socket, contactors).
    • Check for devices for emergency switching (e.g. emergency stop push-buttons).
    • Confirm safe isolation procedure:
    1. Identify circuit.
    2. Isolate using a secure, lockable device.
    3. Prove dead with a GS38-compliant voltage tester.
    4. Retest the instrument on a known live source.
  • Required Labels & Notices (Typical Examples)

    • Main switch/fuse labels (identification of circuits, supply type).
    • RCD test instructions (“Test quarterly” etc.).
    • Bonding connection points.
    • Periodic inspection & testing sticker (next due date).
    • Warning notices for dual supply or photovoltaic back-feed if present.
  • Earth Fault Loop Impedance Z_s Check

    • Measure Zs = Ze + (R1 + R2).
    • Verify measured value < maximum tabulated Z_s in BS 7671 Appendix 3 (adjust for ambient T\alpha).
    • Lower Z_s ⇒ faster protective-device operation.
  • Need for RCD or RCBO?

    • Mandatory if:
    • Earthing system is TT (main protective measure).
    • Socket outlets ≤32\,\text{A} for general use (unless labelled & documented for a specific item).
    • Cables buried <50\,\text{mm} in walls without earthed metallic covering.
    • Bathrooms, shower rooms, outdoors, etc.
    • RCBO offers combined overcurrent + residual current protection with individual circuit discrimination.
  • Special Locations (Section 7 of BS 7671)

    • Bathrooms (701), swimming pools/fountains (702), saunas (703), camping/marinas (708/709), medical locations (710).
    • Each imposes extra IP ratings, RCD sensitivities (e.g. 30\,\text{mA}), SELV or PELV requirements.
  • Risks & Hazards Identified

    • Direct contact with live parts during testing.
    • Stored energy (capacitors) in equipment under test.
    • Arc-flash or short-circuit when probing conductors.
    • Inadvertent reconnection by others (lack of control/LOTO).
    • Trip hazards from test leads, ladders, confined spaces.

Safety Responsibilities of the Electrical Inspector

  • Legal & Standard Requirements

    • Comply with Electricity at Work Regulations 1989.
    • Follow BS 7671, GS38 (HSE Guidance Note) for test probes/leads.
  • Safe Working Procedures

    • Always apply the safe isolation routine before touching conductors.
    • Use dual working (second competent person) for high-risk tests.
    • Ensure test instruments:
    • Carry a valid calibration certificate.
    • Meet CAT III/IV ratings suitable for supply category.
  • Environmental Checks

    • Adequate lighting, access, ventilation.
    • Absence of water/moisture where equipment is opened.
    • Confirm structural integrity (no asbestos disturbance).
  • Documentation Before Testing

    • Review previous EICR or minor works certificates.
    • Produce a risk assessment & method statement (RAMS).
    • Record supply parameters (voltage, Ze, PFC/PSSC) to establish reference values.

Testing Process: Overview & Context

  • Pre-Work Survey

    • Combines visual inspection + desk study of drawings, O&M manuals.
    • Determines what tests are required (continuity, insulation resistance, polarity, RCD, functional).
  • Sequence (Typical)

    1. Continuity of protective conductors.
    2. Ring final circuit continuity.
    3. Insulation resistance.
    4. Polarity.
    5. Earth-fault loop impedance.
    6. RCD/RCBO testing (trip-time, trip-current).
    7. Functional tests (switching, indicating devices, interlocks).
  • Example Numerical Reference

    • If a 32 A Type B MCB protecting a socket circuit in a TN-CS system requires a 0.4\,\text{s} disconnection, maximum Zs from BS 7671 Table 41.3 is 1.37\,\Omega; measured Zs must be <1.37\,\Omega.

Ethical, Practical & Professional Considerations

  • Duty of Care: Inspector must refuse to energise an installation that presents danger, regardless of commercial pressure.
  • Record Keeping: Accurate test results form part of statutory documents that may be subpoenaed in litigation.
  • Continuous Competence: Keep skills & knowledge current with CPD, amendments to BS 7671, and manufacturer updates.
  • Client Education: Explain findings (e.g. need for RCDs) and residual risks in plain language.