Domestic Electrical Installer – Section 1 Part A, Module 6: Electrical Inspection, Testing & Documentation
Pre-Work Survey: Core Questions and Decision Points
Earthing Arrangement
- Identify whether the supply is TN-S, TN-C-S (PME), TN-C, TT, or IT.
- Determine the supply characteristics (nominal voltage, prospective fault current, Ze, supplier’s service position).
- Significance:
- Influences disconnection times, Zs limits, and whether additional protective devices (e.g.
RCDs) are mandatory.
Maximum Disconnection Time (BS 7671)
- For final circuits 60 A supplying socket outlets ≤32\,\text{A}: 0.4\,\text{s} (TN systems).
- For TT systems: 0.2\,\text{s} (for the same circuits) or 0.4\,\text{s} if RCD-protected.
- Distribution circuits: 5\,\text{s} (TN) or 1\,\text{s} (TT).
- Disconnection time ensures that touch-voltage U_T remains below safe thresholds during earth faults.
Isolation & Switching Requirements
- Provide a main isolator: manually operated, mechanically linked, capable of switching all live conductors.
- Verify functional switching devices for normal operation (e.g. switches, plug & socket, contactors).
- Check for devices for emergency switching (e.g. emergency stop push-buttons).
- Confirm safe isolation procedure:
- Identify circuit.
- Isolate using a secure, lockable device.
- Prove dead with a GS38-compliant voltage tester.
- Retest the instrument on a known live source.
Required Labels & Notices (Typical Examples)
- Main switch/fuse labels (identification of circuits, supply type).
- RCD test instructions (“Test quarterly” etc.).
- Bonding connection points.
- Periodic inspection & testing sticker (next due date).
- Warning notices for dual supply or photovoltaic back-feed if present.
Earth Fault Loop Impedance Z_s Check
- Measure Zs = Ze + (R1 + R2).
- Verify measured value < maximum tabulated Z_s in BS 7671 Appendix 3 (adjust for ambient T\alpha).
- Lower Z_s ⇒ faster protective-device operation.
Need for RCD or RCBO?
- Mandatory if:
- Earthing system is TT (main protective measure).
- Socket outlets ≤32\,\text{A} for general use (unless labelled & documented for a specific item).
- Cables buried <50\,\text{mm} in walls without earthed metallic covering.
- Bathrooms, shower rooms, outdoors, etc.
- RCBO offers combined overcurrent + residual current protection with individual circuit discrimination.
Special Locations (Section 7 of BS 7671)
- Bathrooms (701), swimming pools/fountains (702), saunas (703), camping/marinas (708/709), medical locations (710).
- Each imposes extra IP ratings, RCD sensitivities (e.g. 30\,\text{mA}), SELV or PELV requirements.
Risks & Hazards Identified
- Direct contact with live parts during testing.
- Stored energy (capacitors) in equipment under test.
- Arc-flash or short-circuit when probing conductors.
- Inadvertent reconnection by others (lack of control/LOTO).
- Trip hazards from test leads, ladders, confined spaces.
Safety Responsibilities of the Electrical Inspector
Testing Process: Overview & Context
Ethical, Practical & Professional Considerations
- Duty of Care: Inspector must refuse to energise an installation that presents danger, regardless of commercial pressure.
- Record Keeping: Accurate test results form part of statutory documents that may be subpoenaed in litigation.
- Continuous Competence: Keep skills & knowledge current with CPD, amendments to BS 7671, and manufacturer updates.
- Client Education: Explain findings (e.g. need for RCDs) and residual risks in plain language.