Objective: Measure and confirm Prospective Fault Currents (PFC) for safety and adequacy of protective devices.
Establish maximum fault current for installations.
Ensure protective devices can withstand fault current and disconnect safely.
Devices have rated maximum current to prevent explosion or failure.
Rated short-circuit capacity (fuses, circuit breakers, RCBOs).
Breaking capacity sometimes used for fuses.
Verifying breaking/short-circuit capacity against possible fault currents.
Use of a prospective fault current tester.
Familiarize with test instrument and read instructions.
Some meters display prospective fault current when set to test earth fault loop impedance.
If meter requires three leads, ensure correct connections (L-N or L-E).
If unsure, combine earth and neutral leads.
Avoid exposing self to live terminals unnecessarily.
Comply with GS38 standards during live testing.
Conduct tests at the distribution board near the supply, on the supply side of the main switch:
Single-phase installations: Test L-N (PSCC) and L-E (PEFC).
Three-phase installations: Test L1-N, L2-N, L3-N (all PSCC).
PEFC test is unnecessary for three-phase due to voltage considerations.
Single-phase: Record highest value from two tests in kilo-amperes (kA).
Three-phase: Take highest of three tests and multiply by two for a 400 V fault simulation.
Document the final result on the Electrical Installation Certificate (EIC) and schedule.
Recorded PFC must not exceed short-circuit capacities of protective devices.
Consult Table 7.2.7 in IET On-Site Guide for rated capacities; confirm capacity is visible on device.
If downstream device capacity is lower than measured, further testing needed.
PFC cannot increase beyond the value at installation's origin.
If unable to test, estimations can be obtained from distribution network operator.