After turning OFF / withdrawing the protective device:
Prevent accidental re-energisation.
• Remove fuse and keep it in your pocket.
• Fit a lock-off device («dolly-lock») on an MCB and retain the key.
Display a warning notice at the consumer unit:
• “DANGER – DO NOT OPERATE”.
Ethically and legally, the electrician is responsible for ensuring no one can restore power until the work is complete.
Testing Isolation
Re-prove the voltage indicator on a known live source.
Test the previously selected socket again:
If test confirms dead (no voltage between phase–neutral, phase–earth or neutral–earth) → proceed.
If still live → stop and investigate using the fault-finding flow chart (reference pg. 55 of course text).
Test Equipment
Must hold a current calibration certificate; otherwise test results are invalid even if numerically accurate.
Daily visual / functional pre-use checks:
Examine casing for cracks (impact damage ➔ risk of erroneous readings).
Verify batteries are of the same type, not depleted, not leaked.
Inspect leads & probes for intact insulation; damaged leads may expose the user to V_{L-N} or cause false readings.
Perform an open-circuit and short-circuit self-test.
Zero the instrument on the \Omega (ohms) range.
Seek assistance for any suspected inaccuracy – instruments are expensive; improper DIY repair is unethical and unsafe.
Preparation (Pre-installation Work)
Remove the socket faceplate (pattress cover) and inspect wiring:
A healthy ring final socket carries two conductors at each terminal (line, neutral, CPC).
Three conductors indicate an existing spur – BS 7671 forbids daisy-chaining another spur from the same point.
• Replace the plate and choose the next nearest socket.
Disconnect conductors to facilitate testing.
Using an ohmmeter (continuity tester), verify ring continuity as per BS 7671 + Guidance Note 3.
Cut a cable-entry port in the existing pattress; loosely re-fit the plate to aid later cable entry.
Fix a new pattress at the desired spur position; cut its entry port.
Install mini-trunking from existing to new pattress to contain and protect the cable run.
Installation of the Spur
Pull the new twin-and-earth cable through the trunking.
Strip outer sheath; sleeve the Circuit Protective Conductor (CPC) with green/yellow insulation.
Terminate cores into the new socket (L, N, CPC) following colour conventions.
At the origin socket:
Feed the other cable end into the pattress.
Strip and sleeve CPCs.
Terminate line, neutral and CPC of the spur together with their corresponding ring conductors into each terminal.
Mechanical finish: tighten screws to manufacturer torque; no copper exposed outside terminals; ensure trunking lid closes flush.
Inspection, Testing & Certification
Visual inspection checklist:
All connections tight (tug test) and correct polarity.
No sheath/cable damage; CPC sleeving present; trunking secure.
Electrical tests required by BS 7671 & GN3:
Continuity of protective conductors (CPC loop ≈ ring + spur path).
Voltage tester solely detects presence/absence of voltage.
MFT performs a suite of quantitative electrical tests and often displays digital values.
Reminder procedure:
Prove the indicator on a live supply before and after use.
For single-phase circuits, test:
• Phase–Neutral (V{L-N}),
• Phase–Earth (V{L-E}).
Neutral is classed as a live conductor ➔ must also be disconnected during isolation, which may involve removing it from the neutral bar inside the consumer unit.
Practical tip: Affix “Electrician at Work” notices; add name & phone number so occupants can contact you if you leave site with power off.
General Safety & Professional Practice
Always confirm the circuit’s identity, isolation, and securement before contact.
Maintain test instruments in calibrated, undamaged condition; ethics & traceability.
Follow all referenced standards:
GS 38 – safety of test probes/leads.
BS 7671 – Requirements for Electrical Installations (IET Wiring Regulations).