Final Exam Review
Potentialing and Looping Circuits
Black = Circuit Status
Switches, Relays opened, closed
Faults
Blue = Current Flow (Electron Flow Theory)
Red = Positive Potential
Green = Positive Potential
Draw positive potential or negative potential to an open(switch or relay) and ON loads
Current and Amperage
Must have a complete path from - to +
Total amperage depends on total loads or resistance of the circuit
Parallel circuits: IT = I1 + I2 + I3
Series circuits: I is constant
3 Prime faults in electrical circuits
Open
No continuous loop = no current flow
A break in the loop where there should not be
“OL“ reading on multimeter
Short
Internal short
If a load has a specific resistance but indicates lower than normal resistance
Current flow increases
Circuit breaker will pop depending on how much of an internal short
Bypass short
Wires are touching another part of the circuit or are switched
Short to ground (STG)
Unintended path to ground (airframe)
No load or resistance but path is completed
Will have high current
Circuit breaker will pop depending on location
Added resistance
More resistance = less amperage
Higher than normal indication on multimeter
Examples:
Light will be dimmer
Landing gear or a flap motor would be slower than normal
Crimping and Wire Stripping
Use the correct size wire stripper for the size wire
Strip only insulation, do not strip or nick any of the conductor strands
Reject if any strands are nicked or broken
Strip the correct amount of insulation form the conductor
Amount of insulation depends on the terminal barrel that the wire is being crimped to
Inspection points for crimps
Proper strip length
Too much insulation stripped can cause interference with installation hardware
Too little insulation stripped will not allow proper inspection after crimping
No conductor should be showing at the end of the terminal
Exception: Daniels crimpers instructions specify that there should be some conductor visible at the end of the connector
Two crimps are made with one crimping action
Barrel to insulation
Barrel to conductor
Tug test: Slight pull to test strength of crimp to wire
Pull only: Do NOT bend or twist
Connectors
Plugs and jacks
P1 mates to J1, P2 mates to J2, ect.
Mating or demating connectors
Ensure power is OFF
Ensure proper alignment so as not to damage or bend any pins
Always use proper tools (if tools are required)
Do NOT pull on the wires
AC43.13
Use this when the manufacturer has not provided data regarding the repair or inspection being preformed
(Figured 11-2) Determining wire size
Wire size is based on the current carrying capability of the wire and the allowable voltage drop
Circuit breakers and fuses protect the wiring, not the loads
Amperage rating for circuit breakers and fuses are determined by wire size
If circuit breaker amperage rating is too high it could lead to damaged wires
If circuit breaker amperage rating is too low the circuit will not operate without tripping the circuit breaker continuously
Wire ID
Prefix letter: only used when there are two of the same type of circuits installed (ie 2 lighting circuits)
Circuit function code: L2B20
L = Lighting
F = Flight instruments
X = AC power
P = Power
W = Warning
Wire number: L2B20
This is the 2nd wire in the lighting system
Segment letter: L2B20
Wire size L2B20
20 AWG
Suffix (if used) L2B20N
N indicates the wire goes directly to ground or the negative bus
3 Things You Need for Electromagnetic Induction (Induced Voltage)
Magnetic field (coil is energized)
Can change the field by the number of windings in the coil or increasing the current for a stronger magnetic field
Conductor
Relative motion
Alternators and Related Systems
Rotor (Rotates)
Rotating electro-magnet
Strength of magnet is determined by the input current (field current)
Current travels through the brushes to the slip rings then to the rotor coil
Stator (Stationary) - Conductor
Rotor rotates inside of stator windings
3 sets of windings, 120° apart that produce AC current (3 windings = 3 phase)
Voltage is induced across the stator wires
2 types: “Wye“ type and “Delta“ type
Rectifier
Changes the 3 phase AC produced in the stator to DC
Output voltage is pulsating DC
Diodes in series and reverse bias between a power supply and a coil = rectification diode
Because the diodes are in reverse bias to the battery, they also prevent the stator coils from becoming a load to any DC source (ie battery or external power) when the Engine is not running
Capacitor
Reduces the ripple of the pulsating DC
Also reduces radio noise (static)
Alternator Inspection
Rotor
Test for open
One meter probe on each slip ring
Open rotor = OL or infinite reading on meter
Short (Internal)
One meter probe on each slip ring
Internally shorted rotor = lower resistance than normal specified by manufacturer
Short to ground (STG)
One meter probe on either slip ring and one on ground (center post)
Rotor that is STG = any other reading than OL or infinity on meter
OL = normal indication
Stator
Testing for open
For “Wye“ stator: one meter probe on a phase or one meter probe on a phase and one on neutral (must tell all 3 phases)
For “Delta“ stator: disconnect one junction of stator wires and test at that point (one meter probe on each side)
This tests all 3 phases at the same time
Normal indication on meter = <1 Ohm (check specific manufacturer’s manual)
Testing for STG
One meter probe on any phase and one on ground (Frame)
Anything other than OL or infinity is an indication of STG
Rectifier
Each diode must be tested in FWD bias and REV bias using the diode test function on mulit meter
6 diodes test total 12 times
FWD Bias = 0.5V
REV Bias = OL
Voltage Regulator (Magic Circle)
Change in RMP or change in load will change the output voltage of the alternator
Change of output voltage sensed by voltage regulator
Voltage regulator sense change and adjusts current going to the rotor (field current) as necessary
Increase field current to increase output voltage and vice versa
Alternator Schematic
Ammeter #1 - alternator ammeter
Never will indicate left of zero
Ammeter #2 - battery ammeter
Left of zero indication = battery is the source for the electrical system and is discharging
Right of zero = battery is load to the alternator and is charging
External power relay
Power must be correct polarity for the external power relay to energize
Hot bus
CTTO loads - can’t turn them off. Loads that are always on even when the battery or master switch is OFF
Clock
Door lights
Diodes
Blocking diodes (D7) - prevents hot bus from powering main bus, but allows main bus to power hot bus
Polarization diode (D5, D8) - prevents opposite polarity form entering the system
Clipping diode or voltage spike suppression diode (D1, D6, D10) - prevents opposite polarity voltage spike form the collapsing magnetic field of a coil from entering the system
Alternator run scenarios
Ammeter #1 Alternator ammeter (will never indicate left of 0)
Ammeter #2 Battery ammeter
Indicating left of 0 = battery discharging
Indicating right of = battery charging
A&P Privileges
A&P cannot repair instruments
Repair of instruments must completed by an appropriately rated repairman or repair station
Pitot Static System
Altimeter
Static
Vertical Speed Indicator
Static
Airspeed Indicator
Pitot & static
Pitot Heat
Prevents ice from blocking the pitot tube
Vacuum Pumps
Wet type pumps
Uses engine oil for lubrication
Dry type pumps
Uses dust from carbon vanes for lubrication
Sensors, sensing & Switches
Micro - switches
Takes only a small (micro) amount of movement to activate
Synchros indicate movement and can indicate in an infinite number of positions (i.e. they are synchronized with the movement of something)
Temperature Sensing
Thermocouples
EGT probes are typically chrome - Alumel combination because they can withstand the hottest temperatures
When a thermocouple fails, it typically indicates cooler than normal
CHT can be measured from either the side of the cylinder or at the spark plug
If using a spark plug gasket type CHT thermocouple, be sure to remove the original spark plus gasket
MAP (Manifold Absolute Pressure)
When engine is not running, the MAP gauge should indicate ambient pressure (Approximately 30” HG)
Normally aspirated engines typically red line around 29” HG
Turbocharged engines typically red line above 30”HG
Types of Nav Radios
GPS
Location (Position)
Provide Earth’s latitude and longitude
ADF
Bearing (Direction)
Direction to ground station
VHF Nav or VOR
Bearing (Direction)
For navigation to and from a ground station
DME
Distance
Distance to ground position
Types of Transponder
Mode A - Basic ID only
Mode C - ID and altitude (MSL)
Mode S - ID, altitude, and TCAS information
Antennas
Marconi
¼th wavelength
Need a ground plane
Hertz Di - Pole
½ wavelength
Higher frequency means shorter antenna
Modulation
Amplitude Modulation (AM)
Amplitude varies
Frequency does not change
Frequency Modulation (FM)
Frequency varies
Pulse Width Modulation (Digital)
Amplitude varies
Frequency does not change
Installation of equipment into aircraft and paperwork requirements
Major alteration
Approved data used for FAA form 337
Minor alteration
Equipment list
Notes
A open switch cannot be a fault
Potentialing and Looping Circuits
Black = Circuit Status
Switches, Relays opened, closed
Faults
Blue = Current Flow (Electron Flow Theory)
Red = Positive Potential
Green = Positive Potential
Draw positive potential or negative potential to an open(switch or relay) and ON loads
Current and Amperage
Must have a complete path from - to +
Total amperage depends on total loads or resistance of the circuit
Parallel circuits: IT = I1 + I2 + I3
Series circuits: I is constant
3 Prime faults in electrical circuits
Open
No continuous loop = no current flow
A break in the loop where there should not be
“OL“ reading on multimeter
Short
Internal short
If a load has a specific resistance but indicates lower than normal resistance
Current flow increases
Circuit breaker will pop depending on how much of an internal short
Bypass short
Wires are touching another part of the circuit or are switched
Short to ground (STG)
Unintended path to ground (airframe)
No load or resistance but path is completed
Will have high current
Circuit breaker will pop depending on location
Added resistance
More resistance = less amperage
Higher than normal indication on multimeter
Examples:
Light will be dimmer
Landing gear or a flap motor would be slower than normal
Crimping and Wire Stripping
Use the correct size wire stripper for the size wire
Strip only insulation, do not strip or nick any of the conductor strands
Reject if any strands are nicked or broken
Strip the correct amount of insulation form the conductor
Amount of insulation depends on the terminal barrel that the wire is being crimped to
Inspection points for crimps
Proper strip length
Too much insulation stripped can cause interference with installation hardware
Too little insulation stripped will not allow proper inspection after crimping
No conductor should be showing at the end of the terminal
Exception: Daniels crimpers instructions specify that there should be some conductor visible at the end of the connector
Two crimps are made with one crimping action
Barrel to insulation
Barrel to conductor
Tug test: Slight pull to test strength of crimp to wire
Pull only: Do NOT bend or twist
Connectors
Plugs and jacks
P1 mates to J1, P2 mates to J2, ect.
Mating or demating connectors
Ensure power is OFF
Ensure proper alignment so as not to damage or bend any pins
Always use proper tools (if tools are required)
Do NOT pull on the wires
AC43.13
Use this when the manufacturer has not provided data regarding the repair or inspection being preformed
(Figured 11-2) Determining wire size
Wire size is based on the current carrying capability of the wire and the allowable voltage drop
Circuit breakers and fuses protect the wiring, not the loads
Amperage rating for circuit breakers and fuses are determined by wire size
If circuit breaker amperage rating is too high it could lead to damaged wires
If circuit breaker amperage rating is too low the circuit will not operate without tripping the circuit breaker continuously
Wire ID
Prefix letter: only used when there are two of the same type of circuits installed (ie 2 lighting circuits)
Circuit function code: L2B20
L = Lighting
F = Flight instruments
X = AC power
P = Power
W = Warning
Wire number: L2B20
This is the 2nd wire in the lighting system
Segment letter: L2B20
Wire size L2B20
20 AWG
Suffix (if used) L2B20N
N indicates the wire goes directly to ground or the negative bus
3 Things You Need for Electromagnetic Induction (Induced Voltage)
Magnetic field (coil is energized)
Can change the field by the number of windings in the coil or increasing the current for a stronger magnetic field
Conductor
Relative motion
Alternators and Related Systems
Rotor (Rotates)
Rotating electro-magnet
Strength of magnet is determined by the input current (field current)
Current travels through the brushes to the slip rings then to the rotor coil
Stator (Stationary) - Conductor
Rotor rotates inside of stator windings
3 sets of windings, 120° apart that produce AC current (3 windings = 3 phase)
Voltage is induced across the stator wires
2 types: “Wye“ type and “Delta“ type
Rectifier
Changes the 3 phase AC produced in the stator to DC
Output voltage is pulsating DC
Diodes in series and reverse bias between a power supply and a coil = rectification diode
Because the diodes are in reverse bias to the battery, they also prevent the stator coils from becoming a load to any DC source (ie battery or external power) when the Engine is not running
Capacitor
Reduces the ripple of the pulsating DC
Also reduces radio noise (static)
Alternator Inspection
Rotor
Test for open
One meter probe on each slip ring
Open rotor = OL or infinite reading on meter
Short (Internal)
One meter probe on each slip ring
Internally shorted rotor = lower resistance than normal specified by manufacturer
Short to ground (STG)
One meter probe on either slip ring and one on ground (center post)
Rotor that is STG = any other reading than OL or infinity on meter
OL = normal indication
Stator
Testing for open
For “Wye“ stator: one meter probe on a phase or one meter probe on a phase and one on neutral (must tell all 3 phases)
For “Delta“ stator: disconnect one junction of stator wires and test at that point (one meter probe on each side)
This tests all 3 phases at the same time
Normal indication on meter = <1 Ohm (check specific manufacturer’s manual)
Testing for STG
One meter probe on any phase and one on ground (Frame)
Anything other than OL or infinity is an indication of STG
Rectifier
Each diode must be tested in FWD bias and REV bias using the diode test function on mulit meter
6 diodes test total 12 times
FWD Bias = 0.5V
REV Bias = OL
Voltage Regulator (Magic Circle)
Change in RMP or change in load will change the output voltage of the alternator
Change of output voltage sensed by voltage regulator
Voltage regulator sense change and adjusts current going to the rotor (field current) as necessary
Increase field current to increase output voltage and vice versa
Alternator Schematic
Ammeter #1 - alternator ammeter
Never will indicate left of zero
Ammeter #2 - battery ammeter
Left of zero indication = battery is the source for the electrical system and is discharging
Right of zero = battery is load to the alternator and is charging
External power relay
Power must be correct polarity for the external power relay to energize
Hot bus
CTTO loads - can’t turn them off. Loads that are always on even when the battery or master switch is OFF
Clock
Door lights
Diodes
Blocking diodes (D7) - prevents hot bus from powering main bus, but allows main bus to power hot bus
Polarization diode (D5, D8) - prevents opposite polarity form entering the system
Clipping diode or voltage spike suppression diode (D1, D6, D10) - prevents opposite polarity voltage spike form the collapsing magnetic field of a coil from entering the system
Alternator run scenarios
Ammeter #1 Alternator ammeter (will never indicate left of 0)
Ammeter #2 Battery ammeter
Indicating left of 0 = battery discharging
Indicating right of = battery charging
A&P Privileges
A&P cannot repair instruments
Repair of instruments must completed by an appropriately rated repairman or repair station
Pitot Static System
Altimeter
Static
Vertical Speed Indicator
Static
Airspeed Indicator
Pitot & static
Pitot Heat
Prevents ice from blocking the pitot tube
Vacuum Pumps
Wet type pumps
Uses engine oil for lubrication
Dry type pumps
Uses dust from carbon vanes for lubrication
Sensors, sensing & Switches
Micro - switches
Takes only a small (micro) amount of movement to activate
Synchros indicate movement and can indicate in an infinite number of positions (i.e. they are synchronized with the movement of something)
Temperature Sensing
Thermocouples
EGT probes are typically chrome - Alumel combination because they can withstand the hottest temperatures
When a thermocouple fails, it typically indicates cooler than normal
CHT can be measured from either the side of the cylinder or at the spark plug
If using a spark plug gasket type CHT thermocouple, be sure to remove the original spark plus gasket
MAP (Manifold Absolute Pressure)
When engine is not running, the MAP gauge should indicate ambient pressure (Approximately 30” HG)
Normally aspirated engines typically red line around 29” HG
Turbocharged engines typically red line above 30”HG
Types of Nav Radios
GPS
Location (Position)
Provide Earth’s latitude and longitude
ADF
Bearing (Direction)
Direction to ground station
VHF Nav or VOR
Bearing (Direction)
For navigation to and from a ground station
DME
Distance
Distance to ground position
Types of Transponder
Mode A - Basic ID only
Mode C - ID and altitude (MSL)
Mode S - ID, altitude, and TCAS information
Antennas
Marconi
¼th wavelength
Need a ground plane
Hertz Di - Pole
½ wavelength
Higher frequency means shorter antenna
Modulation
Amplitude Modulation (AM)
Amplitude varies
Frequency does not change
Frequency Modulation (FM)
Frequency varies
Pulse Width Modulation (Digital)
Amplitude varies
Frequency does not change
Installation of equipment into aircraft and paperwork requirements
Major alteration
Approved data used for FAA form 337
Minor alteration
Equipment list
Notes
A open switch cannot be a fault