JFRD Engine Company Engineer Manual (Eighth Edition)

Historical Background and Apparatus Fleet

  • On January 2, 1870, Jacksonville's second volunteer fire company, The Mechanics Steam Engine Company, was formed on Adams Street between Main and Laura Streets.

    • The Mechanics purchased the State of Florida's first steam engine, which was rated to throw a water stream 200 feet200\,\text{feet} at a discharge rate of 250 GPM250\,\text{GPM}.

  • Training curricula and pump operations manuals developed by former Jacksonville Fire and Rescue Department (JFRD) Fire Chief Miles R. Bowers were subsequently adopted by the Florida State Fire College, remaining foundational to statewide pump operations instruction.

  • JFRD operates an active municipal fleet comprising more than 60 frontline engine companies citywide, alongside specialized pumping apparatus including water tankers, wildland brush trucks, airport crash trucks, and fireboats.

Historical pumper and crew of the Jacksonville Fire and Rescue Department

Preventive Maintenance Protocols

  • Operational apparatus readiness requires routine scheduled inspections, proactive upkeep, and immediate reporting of mechanical defects to the Tactical Support Facility (TSF).

  • Daily apparatus inspection results and discrepancies must be logged at the start of each shift via the JFRD Portal (located under the Tactical Support tab, within Daily Apparatus Management).

  • Immediate notification to the company officer and corresponding company logbook entries are required for any safety hazards, out-of-service components, or damaged, lost, or stolen tools.

  • Health and Safety Warning: Diesel exhaust is classified by NFPA and NIOSH as a known human carcinogen; there is no safe threshold of human exposure, mandating direct capture and active avoidance on station aprons and fire scenes.

Daily Engine and Chassis Inspection
  • Shift relief conference: Conduct a face-to-face debrief with the off-going engineer regarding mechanical status, handling characteristics, and recent operational history.

  • Fluid level verification:

    • Inspect motor oil, transmission fluid, radiator coolant, power steering fluid, and diesel exhaust fluid (DEF).

    • Rule on fluid placement: The engineer (or assigned relief operator) is the only member authorized to add fluids (DEF, diesel, unleaded, or oils) into an apparatus.

    • The company officer must independently verify that the correct fluid type and specification are added before pouring.

    • Both the engineer and company officer are held equally liable and subject to formal disciplinary action for catastrophic damage resulting from improper fluid placement.

  • Tank fluid verification:

    • Water booster tank levels and foam concentrate tank levels must be visually inspected directly inside the tank cells and compared against digital pump panel gauges.

  • Chassis and running gear checks:

    • Air brake pressure must read greater than 100 PSI100\,\text{PSI} in both front and rear split systems prior to moving.

    • Tires and wheels: Inspect cold inflation pressures, lug nut torque/witness marks, axle oil hub seals for weeping, and tread depth.

    • Minimum legal tread depth on front steer tires is 4/32 inch4/32\,\text{inch} (or flush with tread wear indicator bars).

    • Cab safety components: Confirm proper mechanical operation and positive latching of all passenger seat belts, and check windshield wiper blades/washers.

    • Lighting and alarms: Start the motor, run until it achieves normal operating temperature, and verify cab instrumentation, brake lights, directional signals, emergency lighting, audible sirens, and floodlighting.

Daily Fire Pump and Mechanical Inspection
  • Operational pump sequence:

    • Chock wheels, set parking brake, engage pump shift into pump gear, confirm green cab indicator lights, and place automatic transmission into drive.

    • Open the TANK-TO-PUMP valve and verify static pressure builds on the master discharge gauge.

    • Actuate the electric or air primer until water discharges freely to the pavement beneath the pump body.

    • Test electronic pressure governor functions in both PSI mode and RPM mode across varying engine speeds.

    • On two-stage pump models, actuate the electric transfer valve between VOLUME and PRESSURE to verify full mechanical gate travel.

    • Discharge water through at least one hoseline discharge to confirm water flow.

    • Cycle open and fully close both the driver-side and passenger-side 5 inch5\,\text{inch} intake valves (BIV or PIV); remove protective caps to drain accumulated water.

  • Post-pump shutdown servicing:

    • Disengage the fire pump, return transmission to neutral, and manually cycle all quarter-turn discharge and auxiliary valve pull-rods through their full range of motion.

    • Open all low-point drain valves and bleeder petcocks.

    • Momentarily open the main PUMP DRAIN valve to purge sediment, scale, and grit settled at the bottom of the pump casing.

Under-Cab and Underside Inspection Procedures
  • Prepare the cab interior: Secure or remove all loose equipment, thermal imagers, tools, and fluid bottles prior to activating the hydraulic tilt mechanism.

  • Cab tilt safety warning:

    • Personnel must never place any portion of their body beneath the cab structure while it is raising or lowering.

    • When fully elevated, physically verify that the mechanical cab tilt safety lock/pin is fully seated.

    • Never allow the lowered cab to rest unsupported upon the hydraulic lift cylinder or strut, as this introduces structural damage to the assembly.

  • Structural and powertrain checks under the cab:

    • Inspect serpentine drive belts for tension, cracking, fraying, and alignment.

    • Inspect the commercial battery banks for acid corrosion, loose terminal clamps, and casing cracks.

    • Crawl beneath the chassis to examine the engine oil pan, Allison transmission housing, midship pump transfer case, split-shaft driveline, and water piping for leaks.

    • Air brakes must be mechanically applied before crawling under the apparatus; never enter underneath an apparatus while the diesel motor is running.

Underside and engine compartment inspection during cab tiltEngineer performing routine under-chassis apparatus inspection
Daily Tool and Medical Equipment Check
  • Automated External Defibrillator (AED): Change and charge lithium battery packs; run automated self-diagnostic circuits; verify pads, razors, and pediatric pads.

  • Medical Oxygen Cylinders: Cylinder pressure must register greater than 1000 PSI1000\,\text{PSI}; restock bag-valve-masks, non-rebreathers, and nasal cannulas.

  • Emergency Medical Services (EMS) bags: Inventory advanced life support (ALS) diagnostic items, cervical immobilization collars, trauma dressings, and spine boards.

  • Pneumatic Air Chisel: Connect directly to a dedicated high-pressure SCBA cylinder; supply cylinder pressure must exceed 4000 PSI4000\,\text{PSI}.

    • Operating warning: Never depress the pneumatic chisel trigger unless the chisel bit is placed firmly against a sacrificial solid material to avoid cylinder piston ejection.

  • Self-Contained Breathing Apparatus (SCBA): Inspect packs, facepieces, regulators, and cylinder pressures in accordance with JFRD SOG 421.

  • Pre-connected fire hose beds: Confirm all crosslays and rear attack beds are neatly stacked, free of twists, with nozzles set to the proper GPM/pattern settings and cleared of internal debris.

  • Portable Chainsaws:

    • Inspect chain cutting teeth for sharpness and guide bar for binding.

    • Verify proper chain tension and direction of travel.

    • Top off fuel and bar lubricant reservoirs; bar lubricant on JFRD engines is standard clean motor oil.

    • Run the saw to verify clutch and oiler engagement.

  • Battery-powered hydraulic extrication tools (eDRAULIC):

    • Confirm battery pack charges and verify the electric pump motor function.

    • When returning hydraulic spreaders to vehicle brackets, store them with approximately a 12 inch\frac{1}{2}\,\text{inch} air gap between the tips to relieve static hydraulic pressure and prevent metal-to-metal binding.

  • Portable gasoline-powered motor maintenance:

    • Run auxiliary generators under load for approximately 5 minutes5\,\text{minutes} after checking crankcase oil and coolant.

    • Fuel shutdown procedure: Close the manual inline fuel petcock on all portable gas motors and run them until the carburetor runs completely dry and stalls; this purges the fuel system and avoids gumming caused by ethanol fuel additives.

Weekly Inspection and Servicing Schedules
  • Comprehensive weekly maintenance occurs every Monday under the direction of the station captain.

  • Cab and body conditioning: Deep clean interior floor mats, clean all glass/mirrors, account for map books and master gate keys, clean the thermal imaging camera (TIC), and apply automotive paste wax to exterior paint on a monthly schedule.

  • Roll-up compartment doors: Clean debris and aged grease from aluminum side tracks; apply dry silicone spray only. Apply light oil to door hinges, cycle multiple times, and wipe off all excess oil.

  • Pneumatic air reservoir draining: Locate the manual drain pull-cords or petcocks on all chassis compressed air tanks beneath the frame rails; purge accumulated condensation until the discharging air is completely dry.

  • Pump and plumbing servicing:

    • Remove all discharge caps, suction caps, elbows, and appliances. Clean male and female threads with a wire brush, check rubber swivel gaskets, and apply food-grade machinery grease.

    • Verify that protective zinc/metal intake mesh strainers are present inside all 212 inch2\frac{1}{2}\,\text{inch} auxiliary pony intakes.

    • Cycle and lubricate all mechanical pump valve controls; note excessive friction on linkage rods.

  • Intake valve servicing (BIV and PIV):

    • Disassemble the unit from the pump steamer connection. Inspect the valve body for rust, scale, and foreign debris.

    • Clean and apply food-grade grease to the internal gear mechanism, external threads, and air bleeder valve.

    • If the large Storz swivel ring binds, wash with warm soapy water and work the swivel until it rotates freely.

  • Steamer intake strainers:

    • Inspect the metal intake strainer screens recessed inside the 6 inch6\,\text{inch} steamer inlets.

    • These screens serve a dual purpose as galvanic sacrificial anodes to protect the internal cast iron and bronze pump casing from galvanic corrosion.

    • Strainers naturally oxidize over time; if severe pitting or physical deterioration occurs, obtain an immediate replacement from TSF. The strainer screen must seat tightly inside the inlet barrel to function.

Sacrificial intake strainer inside fire pump steamer connection
  • Pump backflushing evolution:

    • Connect a pressurized supply line from a city fire hydrant directly into an engine discharge port with the fire pump disengaged.

    • Open each discharge valve and intake valve sequentially to backflush sediment, sand, and scale out through the bottom of the pump body (crosslay plumbing does not require backflushing).

    • Following backflushing, immediately reconnect to the on-board tank, open the TANK-TO-PUMP valve, engage the fire pump, and activate the primer to ensure the pump body is filled with clean water and reprimed.

Pump backflushing evolution through engine discharge connections
  • Tool and equipment care:

    • Hand tools: Wash striking surfaces with mild soap and water; dry thoroughly. Coat bare steel tool heads with light water-displacing oil. Apply raw linseed oil to natural wood handles.

    • Ground ladders: Wash with mild soap and water; lubricate folding roof hook spring assemblies with light oil. Inspect heat sensor labels for dark chemical change (indicating heat exposure) and check ladder compartment slides.

    • Fire hose nozzles: Immerse nozzle bodies in warm soapy water and cycle internal ball shutoffs, spin teeth, and gallonage selectors. Never apply petroleum-based lubricants or grease to fire hose nozzles.

    • Hard suction hoses: Wash threads and clean female swivel rings using warm soapy water.

    • Chain saws: Remove guide bar and cutting chain; blow out clutch drums and air filters using compressed air; flip the bar to balance wear; reassemble and set chain tension.

    • Pneumatic cutting tools: Clean bodies with soap and water; apply 5 drops of approved air tool oil directly into the tool's air inlet port prior to test operation.

    • Battery tools: Cycle, inspect, and complete charge cycles on all portable equipment and TICs.

    • Life safety ropes: Inspect structural core and sheath integrity in accordance with JFRD SOG 419.

    • Mechanical winches: Mount and test winch controllers at all chassis connection receiver points.

    • Heavy rescue hand tools: Clean high-lift jacks, wipe steel components with light oil, wash transport chains, and inspect links. Clean come-along ratchets with a dry cloth; sparingly oil gear pawls; never apply oil or lubricants to the wire rope cable; verify that the wire cable dries fully to prevent core corrosion.

Approved Lubricants and Chemical Additives
  • Application note: All lubricants must be used sparingly; excess grease or oil attracts abrasive road grit and particulate matter, damaging seals and bearings.

  • Light Oil: Liquid Wrench, WD-40, or comparable water-displacing aerosol lubricants for bare metal surfaces, tool heads, and hinge pins.

  • Air Tool Oil: Manufacturer-supplied low-viscosity lubricating oil applied directly to pneumatic tool inlets.

  • Two-Cycle Engine Oil: Premium synthetic oil blended into unleaded gasoline for two-cycle small power engines.

  • Silicone Spray: High-grade dry spray intended for rollup door tracks and slide-out equipment trays. Leaves no oily residue; do not apply to heavy mechanical rotating gears.

  • Powdered Graphite: Dry lubricant applied to mechanical pump valve control rods, linkage pivot points, and sliding shafts.

  • Food-Grade Machinery Grease: The only authorized grease for pump discharge threads, suction connections, and appliance swivels.

  • Fuel Stabilizer: Chemical additive blended into all freshly acquired unleaded small-equipment fuel cans upon delivery.

  • Diesel Exhaust Fluid (DEF): Aqueous urea solution conforming to ISO 22241 used in selective catalytic reduction engines to reduce NOxNO_x exhaust emissions.

Return-to-Service Checks Following Maintenance
  • Following major unscheduled or scheduled maintenance at TSF, City Fleet Management, or an outside commercial truck vendor, the engine must undergo functional verification prior to re-entering service.

  • Extended shop service (>24 hours>24\,\text{hours} or spanning two shifts):

    • The on-duty crew must conduct a complete daily apparatus and pump check-off before loading equipment and booking in-service.

  • Same-day turnaround service (returned within the same shift):

    • Visually confirm the booster tank is 100%100\% full.

    • Engage pump and verify governor functions in PSI and RPM modes.

    • Check air brake system operating pressures and service stopping ability.

    • Verify that all loose tools, hoses, and equipment are accounted for.

Emergency Scene Positioning and Vehicle Operations

  • Apparatus positioning dictates operational safety, access, and handline reach at all emergency scenes, conforming to JFRD SOG 402 and SOG 406.

Emergency Medical Incidents
  • Single-family residential dwellings: Give initial priority positioning to the responding rescue unit (ambulance) to maintain direct access to the stretcher.

    • On high-speed or congested thoroughfares, angle the engine to act as a barrier to shield patient loading operations.

  • Multi-family apartments and institutional high-rises:

    • Where courtyard or driveway access is restricted, position the engine outside the main access gates or away from building canopies, preserving the closest entrance for rescue access.

Roadway and Highway Emergencies
  • Protect the work zone: Angle the engine across active travel lanes at a 45∘45^\circ angle to physically deflect oncoming traffic away from responders and victims.

  • Environmental and mechanical hazards: Spot the vehicle uphill and upwind of fuel spills or chemical vapor leaks.

  • Account for auxiliary vehicle noise and engine exhaust: Position the diesel exhaust discharge away from triage, extrication, and patient treatment locations.

  • Nighttime roadway operations: Turn off forward-facing headlights when the engine is angled toward oncoming traffic to avoid blinding approaching motorists; deploy retroreflective directional lighting and traffic cones.

Structural Fire Incidents
  • Single-story residential structures: The first-arriving engine and first-due ladder company position along the structural front.

    • Spot the engine to pull attack lines from crosslays while preserving the street frontage directly in front of the structure for aerial apparatus outriggers and ladder turntable placement.

  • Multi-story residential and commercial structures:

    • Position the engine well clear of building corners.

    • Leaving the structural corners open enables the aerial ladder company to place its turntable where the aerial ladder can scrub two exterior building faces simultaneously.

Engine company positioning on residential structure fire
Safety Clearances and Roadway Restrictions
  • Overhead hazards: Never spot an apparatus beneath active overhead electrical transmission lines.

  • Structural collapse: Maintain a minimum distance from burning exterior masonry walls equivalent to 1.5×1.5\times the height of the building.

  • Hose protection: Keep rubber fire hose away from the hot diesel exhaust tailpipe.

  • Structural weight limits: Do not drive onto private bridges, residential docks, or private residential driveways unless actively executing emergency suppression operations.

  • Standing water hazards: Never drive fire apparatus through standing floodwaters deeper than the structural centerline of the vehicle's wheels.

  • Equipment rack access: Maintain an unobstructed clear zone at the tailboard of at least 5 feet5\,\text{feet} on the officer's side of the engine to allow the hydraulic ladder storage rack to swing outward and lower ground ladders.

Hydraulic ladder rack lowering on the officer side of the engine
Apparatus Backing Protocols and Spotter Signals
  • Prior to backing any JFRD apparatus, a designated spotter must be positioned on the engineer's (driver's) side of the apparatus, positioned 5 to 10 feet5\text{ to }10\,\text{feet} behind the rear tailboard.

  • The engineer and spotter must maintain continuous eye-to-eye contact through the driver's side exterior rearview mirror.

  • If the spotter disappears from the engineer's view for any reason, the vehicle must be brought to an immediate stop.

  • Standard backing hand signals:

    • Stop Signal: Both arms raised with forearms vertical and closed fists held facing forward.

    • Proceed Backing Signal: Both arms raised with open palms bent at the elbows, motioning in an inward beckoning sweep toward the spotter's chest.

    • Turn Left or Turn Right Signal: Both open hands extended together pointing in the desired direction of tailboard travel.

Spotter hand signal demonstrating apparatus STOPSpotter hand signal demonstrating PROCEED BACKINGSpotter hand signal demonstrating directional turn during backing

Fireground Water Sources and Distribution Systems

Municipal Pressurized Water Networks
  • The primary pressurized water supply for the City of Jacksonville is operated and maintained by JEA, consisting of artesian wells, treatment plants, elevated water towers, and an underground gridded main network.

  • Gridded loop networks allow pressurized water to flow toward an operating hydrant from multiple directions simultaneously, reducing localized friction loss and stabilizing static pressure.

  • Municipal water mains range from 6 inches6\,\text{inches} to 24 inches24\,\text{inches} in internal diameter, carrying an average static operating pressure of approximately 70 PSI70\,\text{PSI}.

  • Dead-end mains: Found on cul-de-sacs and dead-end roads; they receive water from only one direction, resulting in reduced available volume, elevated friction loss, and rapid residual pressure drops under fire flow conditions.

  • Independent municipal networks: Atlantic Beach, Neptune Beach, and the Town of Baldwin operate independent municipal water utilities that rely on localized water storage towers and variable static head pressures.

Grid network of municipal water mains supplying multiple hydrants
City Fire Hydrants
  • Standard JEA municipal hydrants are painted chrome yellow.

  • Thread configurations:

    • One large central steamer port: 412 inch4\frac{1}{2}\,\text{inch} National Standard Thread (NST).

    • Two side discharge ports: 212 inch2\frac{1}{2}\,\text{inch} National Standard Thread (NST).

    • Internal barrel connection to the main: 6 inch6\,\text{inch} intake diameter.

    • Average municipal static pressure: approximately 70 PSI70\,\text{PSI}.

  • Water main distribution sizing:

    • Residential distributions: 6 inch6\,\text{inch} to 10 inch10\,\text{inch} mains.

    • Commercial and industrial zones: 8 inch8\,\text{inch} to 24 inch24\,\text{inch} mains.

  • Missing or damaged steamers: If an older hydrant lacks a 412 inch4\frac{1}{2}\,\text{inch} steamer port, or if the port threads are stripped, high volume can still be achieved by connecting 5 inch5\,\text{inch} supply hose to one 212 inch2\frac{1}{2}\,\text{inch} port using an adapter, or by connecting both 212 inch2\frac{1}{2}\,\text{inch} ports into a siamese appliance.

Private Water Distribution Systems
  • Private systems serve commercial complexes, industrial plants, schools, and high-density apartments, receiving water through private artesian wells or via a dedicated municipal feed equipped with an inline meter and backflow preventer.

  • Backflow preventers are sized to match the diameter of the underground main and include check valves that isolate the public water grid from private contamination.

  • Hydrant identification and colors:

    • Private hydrants have historically been painted red, though private systems installed or repainted since 2016 are transitioning to solid white.

    • Standard commercial/apartment private hydrants operate with static pressures of approximately 70 PSI70\,\text{PSI}.

  • High-hazard industrial private systems: Refineries, chemical plants, and port facilities often maintain dedicated private fire pumps producing static main pressures in excess of 175 PSI175\,\text{PSI}, designed to supply master streams directly without engine pressure boosting.

  • NFPA Hydrant Bonnet and Cap Color Classification:

    • Blue: 1500 GPM1500\,\text{GPM} or greater rated capacity.

    • Green: 1000 to 1499 GPM1000\text{ to }1499\,\text{GPM} rated capacity.

    • Orange: 500 to 999 GPM500\text{ to }999\,\text{GPM} rated capacity.

    • Red: Below 500 GPM500\,\text{GPM} rated capacity.

  • Reclaimed water hydrants: Finished in purple; connected to non-potable tertiary sewage/irrigation networks and intended strictly for utility flushing—never connect to purple hydrants for structural fire suppression.

  • Highway sound barriers: Limited-access highways feature circular 12 inch12\,\text{inch} access ports cut into concrete sound walls to enable crews to advance supply lines to municipal hydrants located on adjoining neighborhood streets.

Backflow preventer assembly on commercial private water systemPrivate industrial high-pressure hydrant
Static Water Supplies and Dry Hydrants
  • Static sources have no head pressure; water must be drafted by lowering pump casing pressure below ambient atmospheric pressure (14.7 PSI14.7\,\text{PSI} at sea level).

  • Apparatus water booster tank:

    • Configured above the pump intake manifold to take advantage of positive static head pressure.

    • Connected via a 3 inch3\,\text{inch} to 4 inch4\,\text{inch} internal TANK-TO-PUMP valve.

    • Flow limitations: Internal tank baffles, piping geometry, and valve design restrict maximum gravity-fed flow from an on-board tank to 700 to 800 GPM700\text{ to }800\,\text{GPM} across all JFRD engines.

    • Refill restrictions: Booster tanks must be filled solely from clean, potable municipal city fire hydrants; never refill directly from unverified private or raw static sources.

  • Dry hydrants:

    • A non-pressurized pipe assembly constructed of schedule 40/80 PVC, ductile iron, or stainless steel connecting to a deep pond, lake, or commercial retention basin, terminating in an exterior 412 inch4\frac{1}{2}\,\text{inch} NST male connection.

    • Pre-operational inspection: Verify clear road access, confirm that seasonal water levels cover the submerged strainer by at least 18 inches18\,\text{inches}, and inspect the internal barrel for trash, dead vegetation, or cracked pipe.

Dry hydrant design installed at retention pond

Fire Pump Mechanical Theory, Design, and Components

  • JFRD frontline engines utilize midship-mounted Waterous centrifugal pumps installed on Pierce chassis, rated at capacities of 1500 GPM1500\,\text{GPM}, 1750 GPM1750\,\text{GPM}, or 2000 GPM2000\,\text{GPM}.

  • Structural pump assemblies consist of:

    • Intake manifold: Lower cast bronze/iron manifold distributing intake water directly into the impeller eyes.

    • Discharge manifold: Upper manifold collecting pressurized water from the volutes for routing to individual discharge valves.

    • Impeller and volute assembly: One or two bronze impellers mounted on a high-tensile steel shaft.

    • Split-shaft pump transfer case: Heavy gear casing mounted in-line along the vehicle driveshaft to transfer torque from the diesel engine (Caterpillar C12/C13 or Cummins ISL series) to the pump.

Cutaway rendering of midship fire pump manifold and gear casing
Centrifugal Pump Dynamics
  • Operational characteristics:

    • Impellers rotate continuously when engaged; water is spun through centrifugal force from the central eye radially outward across curved vanes into the volute chamber, which widens to convert velocity into static pressure.

    • Flow-through design: Water under external supply pressure can freely pass through an idle pump body and exit open discharge valves even when the fire pump is disengaged.

    • Additive incoming pressure: Positive intake pressure adds directly to the pressure generated by the rotating impellers (Total Discharge Pressure=Intake Pressure+Pump Pressure\text{Total Discharge Pressure} = \text{Intake Pressure} + \text{Pump Pressure}).

    • Impeller slippage: Because there is no positive displacement seal between the spinning impeller and the volute casing, discharge lines can be shut down without stalling the engine; however, the ongoing fluid shear rapidly generates friction heat within the water.

    • Centrifugal pumps cannot move or pump air.

    • Dry run warning: Centrifugal pumps cannot run dry; mechanical packing seals and bronze clearance rings will overheat and suffer catastrophic binding if operated without water for more than a few minutes.

Pneumatic Pump Shift
  • A pneumatic three-position toggle switch in the cab controls an air-actuated shift cylinder that slides a heavy internal ring gear within the transfer case.

    • ROAD: Transmission torque is directed through the rear driveshaft to the drive axle wheels.

    • PUMP: Driveshaft torque to the rear axle is disengaged; the internal gear engages the pump impeller transmission.

    • NEUTRAL: Center position; used only for mechanical failures when executing manual pump shifts.

  • Operating rule: When shifting between ROAD and PUMP, move the toggle smoothly without stopping in NEUTRAL, and pause several seconds before shifting the automatic transmission from neutral to drive.

In-cab pneumatic pump shift control plate
Pump Testing and Certified Performance (NFPA 1911)
  • JFRD pumps are factory acceptance tested and certified annually by Underwriters Laboratories (UL) drafting from an open water pit under strict atmospheric conditions.

  • Performance ratings at draft:

    • 100%100\% rated capacity at 150 PSI150\,\text{PSI} net pump discharge pressure (PDP).

    • 70%70\% rated capacity at 200 PSI200\,\text{PSI} net pump discharge pressure (PDP).

    • 50%50\% rated capacity at 250 PSI250\,\text{PSI} net pump discharge pressure (PDP).

  • When fed by a positive pressure municipal hydrant or relay engine, a centrifugal pump can easily exceed its tested UL draft capacity.

Centrifugal pump certification data plate
Single-Stage and Two-Stage Pump Operations
  • Single-Stage pumps utilize one large double-suction impeller. High pressures require higher engine RPM.

  • Two-Stage pumps utilize two identical impellers balanced on a common shaft, operated in one of two configurations via a heavy internal transfer valve:

    • PRESSURE (Series) setting: The internal transfer valve directs the incoming water supply solely to the eye of the first impeller. The first impeller boosts the pressure (e.g., to 60 PSI60\,\text{PSI}) and discharges it directly into the eye of the second impeller, which boosts the pressure again (e.g., to 120 PSI120\,\text{PSI}). Each impeller generates approximately 50%50\% of the final discharge pressure. Used for high-pressure operations such as high-rise standpipes.

    • VOLUME (Parallel/Capacity) setting: The transfer valve splits the incoming water stream, delivering 50%50\% of the water volume simultaneously to each impeller eye. Both impellers discharge together in parallel into the common discharge manifold. Volume is doubled while pressure remains equal.

  • Operational transfer valve rules:

    • Standard position: Two-stage pumps must be operated in VOLUME during normal structural operations, relay pumping, and whenever discharge requirements exceed 50%50\% of the pump's rated capacity.

    • Attempting to deliver high volume while locked in PRESSURE will choke the pump and restrict total GPM.

    • The transfer valve is operated by an electric-over-hydraulic actuator with no intermediate positions.

    • Manual override: If the electrical switch fails, manually turn the mechanical shaft using a 34 inch\frac{3}{4}\,\text{inch} socket and ratchet wrench.

    • Pressure spike warning: To prevent water hammer, reduce engine RPM to idle before changing the transfer valve position; do not drop pressure rapidly if handline crews are inside a fire building.

Hale midship impellers showing single-stage and two-stage assembliesElectric transfer valve control panel
Intake and Discharge Plumbing, Valves, and Gauges
  • Intake configuration: All incoming ports connect into an open intake manifold, which is monitored by a single Master Intake Gauge.

    • Standard layout: Two 6 inch6\,\text{inch} steamer intakes (one per side), two 212 inch2\frac{1}{2}\,\text{inch} auxiliary pony intakes, and, on selected engines, a 5 inch5\,\text{inch} electric front intake.

    • Hazardous materials engines (E-7 and E-21): Equipped with an additional direct tank fill intake inside the tailboard compartment to route external hydrant or tanker water directly into the tank for inline foam proportioning.

  • Intake valves:

    • Ball Intake Valve (BIV): Less restrictive, flows in excess of 2000 GPM2000\,\text{GPM}, and is vacuum-certified for drafting.

    • Piston Intake Valve (PIV): Flow-restrictive internal piston mechanism; not rated for drafting operations.

    • Pressure relief valves: Both BIV and PIV contain internal adjustable spring-loaded relief valves preset to open at 150 PSI150\,\text{PSI} to vent excess line surges out through bottom dump ports. The pump body also contains an internal intake relief valve factory set at 150 PSI150\,\text{PSI}.

  • Valve handles and slow-close requirements:

    • Standard handline discharges utilize manual quarter-turn ball valves with mechanical pull handles; when opened, handles can be locked in place by twisting 45∘45^\circ.

    • Large-diameter valves (3 inch3\,\text{inch} or larger) must utilize slow-operating gear wheels or electric actuators requiring 15 to 20 seconds15\text{ to }20\,\text{seconds} to cycle between fully open and fully closed to mitigate destructive water hammer.

  • Master compound gauges:

    • Master Intake Gauge: Registers positive pressure (0 to 600 PSI0\text{ to }600\,\text{PSI}) and vacuum (0 to −30 inHg0\text{ to }-30\,\text{inHg}, inches of mercury).

    • Master Discharge Gauge: Displays total discharge manifold pressure (0 to 600 PSI0\text{ to }600\,\text{PSI}).

    • Individual Line Gauges: Display individual line discharge pressure (0 to 400 PSI0\text{ to }400\,\text{PSI}).

Ball Intake Valve (BIV) with Storz connectionSlow-operating discharge handwheel control and gaugeMaster pump compound intake and discharge gauges
Auxiliary Priming Systems
  • The primer is an electrically driven positive displacement rotary pump that evacuates trapped air from the centrifugal pump body, creating a partial vacuum so atmospheric pressure pushes water upward through the hard suction hose.

  • Standard priming time: 45 seconds45\,\text{seconds} to prime through a single steamer hose; up to 90 seconds90\,\text{seconds} when drafting through dual steamer connections.

  • Engines with front intakes have two independent priming pumps that must be actuated simultaneously when utilizing the front intake to draft.

  • Optimal engine speed for priming is 1000 to 1200 RPM1000\text{ to }1200\,\text{RPM}.

  • Alternative air bleed methods: If the primer fails, partially open the overhead deck gun discharge valve (the highest physical point on the pump plumbing) or slightly open the TANK FILL valve to vent trapped air into the booster tank.

Dual primer controls for front intake equipped engines
Thermal Auxiliary Cooling Controls
  • Pump Cooler / Re-circulating Line: Directs a continuous low-volume stream of water (<25 GPM<25\,\text{GPM}) from the pump discharge manifold back into the booster tank. Keeps static water in the pump cool when handlines are closed.

    • Warning: If operating from a pressurized hydrant or relay supply line, leaving this valve open will eventually overfill and vent water through the booster tank roof vent.

  • Engine Cooler / Auxiliary Cooler: An internal closed-circuit heat exchanger; cool discharge water is circulated through a closed metal coil within the motor's engine radiator. Prevents engine overheating during stationary pumping operations under heavy loads. Pump water and motor coolant never mix.

Engine Cooler valve control knobPump Re-Circulating Line valve control knob
Diesel Engine Operating Parameters
  • Oil Pressure:

    • Idle speed: minimum of 15 PSI15\,\text{PSI}.

    • Operating pumping speed: 35 to 45 PSI35\text{ to }45\,\text{PSI}.

  • Coolant Temperature: Fully warmed normal range is 180o to 220oF180^\text{o}\text{ to }220^\text{o}\text{F}.

  • Electrical System Voltage: 13.0 to 14.5 volts13.0\text{ to }14.5\,\text{volts}.

  • Transmission Temperature: Normal operating limit is under 300oF300^\text{o}\text{F}.

Pressure Control Systems and Electronic Governors

  • JFRD utilizes microprocessor-based electronic pressure governors—the FRC Pump Boss 200 and Pump Boss Max—integrating throttle control and line pressure relief into a single unit.

  • The governor controls engine RPM by monitoring signals from a high-speed piezoelectric pressure transducer tapped directly into the pump discharge manifold.

Pump Boss 200 electronic governor panelPump Boss Max digital electronic pressure governor
PSI Mode (Pressure Governing)
  • When set in PSI mode, the governor maintains a constant pump discharge pressure (PDP) regardless of fluctuations in incoming hydrant pressure or changes in flow from opening or closing handline nozzles.

  • The governor functions like an automotive cruise control, automatically increasing or decreasing engine RPM to maintain the set discharge pressure.

  • Mandatory PSI mode operations:

    • Advancing and operating interior attack handlines.

    • Supplying elevated ladder pipes or portable master monitors.

    • Supplying commercial automatic sprinkler or standpipe systems.

  • Automatic cutoff: If discharge pressure requirements exceed 300 PSI300\,\text{PSI}, the internal software disables the pressure sensor, requiring the operator to switch to RPM mode.

RPM Mode (Throttle Control)
  • In RPM mode, the pressure sensor feedback loop is bypassed. The unit functions as a manual electronic throttle, holding engine speed steady at the selected RPM regardless of changes in discharge pressure.

  • No automatic pressure relief is provided in RPM mode; pressure surges pass directly into hoselines.

  • Mandatory RPM mode operations:

    • Initial drafting evolutions from a static water source.

    • Supplying or operating as an intermediate engine in a relay pumping operation.

    • Initial charging of 5 inch5\,\text{inch} large diameter supply hose (LDH).

    • Operation during an electronic pressure transducer failure or PSI mode malfunction.

    • Pumping operations where discharge pressures exceed 300 PSI300\,\text{PSI}.

Operational Steps for Pressure Governors
  • The operator must execute four steps in order:

    1. Engage the pump.

    2. Open the TANK TO PUMP valve.

    3. Open the selected discharge valve.

    4. Operate the governor.

  • Diagnostic error alerts: The pressure sensor must detect positive discharge pressure before the governor will throttle up in PSI mode. If air is trapped in the pump body, the unit locks engine speed at idle and flashes LO SUPPLY or LO PRESSURE.

  • Factory Presets:

    • Engine PSI preset: 125 PSI125\,\text{PSI}.

    • Tanker PSI preset: 50 PSI50\,\text{PSI}.

    • RPM preset (both engines and tankers): 1100 RPM1100\,\text{RPM}.

  • Cavitation safety return: If discharge pressure drops below 30 PSI30\,\text{PSI} while running in PSI mode (indicating complete loss of water supply), the governor automatically drops engine speed to idle to protect the pump from cavitation damage.

  • Low residual alert: If incoming intake residual pressure drops below 10 PSI10\,\text{PSI}, the governor may drop engine speed to idle; to maintain flow under tight water supply conditions, shift into RPM mode.

Fire Hose Inventories, Nozzle Dynamics, and Appliances

Minimum Engine Company Hose Inventory
  • Large Diameter Hose (5 inch5\,\text{inch}): 1000 feet1000\,\text{feet} (loaded flat, with Storz couplings).

  • Medium Diameter Hose (212 inch2\frac{1}{2}\,\text{inch}): 1000 feet1000\,\text{feet} (loaded flat, male coupling forward/on top).

  • Pre-connected Attack Lines (134 inch1\frac{3}{4}\,\text{inch} or 1.88 inch1.88\,\text{inch}): Two 200 foot200\,\text{foot} crosslays.

  • High-Rise Hose Pack: 195 feet195\,\text{feet} of true 212 inch2\frac{1}{2}\,\text{inch} high-rise hose (three 65 foot65\,\text{foot} sections).

  • Apartment Hose Pack: 100 feet100\,\text{feet} of 134 inch1\frac{3}{4}\,\text{inch} hose with wye and nozzle.

  • Booster Hose: 200 feet200\,\text{feet} of 1 inch1\,\text{inch} rubber-jacketed line on reel.

  • Wildland Forestry Hose: 200 feet200\,\text{feet} of 1 inch1\,\text{inch} woven jacket hose.

  • Hard Suction Hose: Two 10 foot10\,\text{foot} sections of 6 inch6\,\text{inch} suction hose (one heavy-duty, one lightweight drafting).

  • Soft Intake Hose: One 25 foot25\,\text{foot} section of 6 inch6\,\text{inch} flexible soft supply hose.

Rear hose bed containing 5-inch large diameter hose flat load
Large Diameter Hose (5 inch5\,\text{inch}) Technical Parameters
  • Couplings: Sexless, quarter-turn 5 inch5\,\text{inch} Storz locking connections.

  • Loading guidelines: Hose must be packed flat with couplings staggered across the bed; couplings must never flip over during layout.

  • Layout rules:

    • When securing to an intake valve, ensure there is no right-hand twist in the hose body, which can unlock the Storz coupling upon pressurization.

    • If using a mechanical hose clamp, apply it on the supply side close to a coupling, positioned at least 25 feet25\,\text{feet} behind the engine tailboard to accommodate line stretch.

    • Supply lines connected to hydrants on working incidents must be 5 inch5\,\text{inch} or larger.

  • Vehicular crossing warnings:

    • Crossing charged 5 inch5\,\text{inch} hose is strictly prohibited except in absolute emergencies.

    • Any emergency crossing must be made at an angle across the hose, never perpendicular, and permitted only for high-clearance vehicles.

    • Apparatus must never run over a 5 inch5\,\text{inch} aluminum Storz coupling.

  • Hydraulic capacity and friction limits:

    • Flowing 1400 GPM1400\,\text{GPM} creates approximately 10 PSI10\,\text{PSI} friction loss per 100 feet100\,\text{feet} of hose.

    • The practical maximum flow limit of single 5 inch5\,\text{inch} supply hose is 1600 GPM1600\,\text{GPM}.

    • Operating safety boundaries: Never exceed 200 PSI200\,\text{PSI} working discharge pressure; maintain a minimum of 10 PSI10\,\text{PSI} residual pressure.

Storz Adapters and Pump Fittings
  • 5 inch5\,\text{inch} Storz to 6 inch6\,\text{inch} male adapter: Vacuum-certified adapter utilizing an internal compression gasket; allows connecting hard suction or 6 inch6\,\text{inch} soft intake hose directly to a Ball Intake Valve (BIV).

  • 4 inch4\,\text{inch} female to 5 inch5\,\text{inch} Storz: Threaded adapter mounted permanently to the pump's Large Diameter Discharge (LDH) port.

  • 412 inch4\frac{1}{2}\,\text{inch} female to 5 inch5\,\text{inch} Storz: Primary municipal hydrant adapter, attached to the exposed end of 5 inch5\,\text{inch} hose in the hose bed.

  • 212 inch2\frac{1}{2}\,\text{inch} female to 5 inch5\,\text{inch} Storz: Enables connection of 5 inch5\,\text{inch} supply line to the 212 inch2\frac{1}{2}\,\text{inch} side discharge ports of a fire hydrant.

Storz adapters: 5-inch Storz to 6-inch male, 4-inch to 5-inch Storz, and hydrant fittings
212 inch2\frac{1}{2}\,\text{inch} Hose, Appliances, and Nozzles
  • Loading: Packed with the male coupling facing out on top to allow fast deployments.

  • Smooth Bore Handline Tips (50 PSI50\,\text{PSI} Nozzle Pressure):

    • 1 inch1\,\text{inch} tip: flows 200 GPM200\,\text{GPM}.

    • 118 inch1\frac{1}{8}\,\text{inch} tip: flows 250 GPM250\,\text{GPM}.

    • 114 inch1\frac{1}{4}\,\text{inch} tip: flows 300 GPM300\,\text{GPM}.

    • Friction Loss allowance: Add a baseline of 10 PSI10\,\text{PSI} friction loss per 100 feet100\,\text{feet} of 212 inch2\frac{1}{2}\,\text{inch} hose at a standard 250 GPM250\,\text{GPM} flow.

    • Maximum safe handline flow: 300 GPM300\,\text{GPM} represents the maximum safe limit for manual handline handling.

  • Akron Turbojet 212 inch2\frac{1}{2}\,\text{inch} Fog Nozzle:

    • Rated for 100 PSI100\,\text{PSI} nozzle pressure.

    • Selectable gallonage settings: 125,150,200, and 250 GPM125, 150, 200,\text{ and }250\,\text{GPM}.

    • Break-apart design: Features an integrated ball-valve playpipe with unscrewable nozzle tip, allowing connection of a 134 inch1\frac{3}{4}\,\text{inch} line to extend reach.

    • Warning: Rotating the front protective bumper fully clockwise shuts off water flow regardless of handle bale position.

Smooth bore stacked tip nozzle assembly on a 2.5-inch hose line
134 inch1\frac{3}{4}\,\text{inch} Attack Hoselines and Nozzles
  • Akron Turbojet Adjustable Gallonage Nozzle:

    • Five selectable positions: 30,95,125,150, and 200 GPM30, 95, 125, 150,\text{ and }200\,\text{GPM}.

    • JFRD tactical interior standard: All pre-connected attack lines must be set to either the 150 GPM150\,\text{GPM} or 200 GPM200\,\text{GPM} position prior to advancing into a structure.

    • Elevation allowance: Add 5 PSI5\,\text{PSI} PDP per building floor above ground level.

  • Variant operating pressures:

    • 75 PSI75\,\text{PSI} Model (Standard engine issuance):

      • Pumping 150 GPM150\,\text{GPM} requires an initial PDP of 125 PSI125\,\text{PSI}.

      • Pumping 200 GPM200\,\text{GPM} requires an initial PDP of 150 PSI150\,\text{PSI}.

      • Kink notice: 75 PSI75\,\text{PSI} nozzles are more prone to hose kinking; if lines kink, the engineer can increase PDP by 10 to 25 PSI10\text{ to }25\,\text{PSI}.

    • 100 PSI100\,\text{PSI} Model (HazMat team and specialized engines):

      • Pumping 150 GPM150\,\text{GPM} requires an initial PDP of 150 PSI150\,\text{PSI}.

      • Pumping 200 GPM200\,\text{GPM} requires an initial PDP of 175 PSI175\,\text{PSI}.

Akron Turbojet variable-flow handline fog nozzles
Booster Hose, Hard Suction, and Specialized Packs
  • Booster reel hose: 200 feet200\,\text{feet} of 1 inch1\,\text{inch} rubber hose equipped with a 1 inch1\,\text{inch} Akron Turbojet nozzle (13,25,40, and 60 GPM13, 25, 40,\text{ and }60\,\text{GPM} at 100 PSI100\,\text{PSI} NP). Used for overhaul and small exterior fires. Avoid sustained high-pressure, low-flow pumping to prevent pump overheating.

  • Hard suction hose: Two 10 foot10\,\text{foot} sections with 6 inch6\,\text{inch} connections.

    • Heavy-duty suction hose: High vacuum/pressure rating; used for drafting or hooking up to a pressurized hydrant.

    • Lightweight drafting hose: Flexible corrugated hose used strictly for drafting; cannot withstand positive hydrant pressure.

  • Low-level strainer: Carried on tankers and select engines; painted red with 6 inch6\,\text{inch} female threads. Features a jet siphon port to draft water down to within a few inches of a portable basin floor.

  • Soft intake hose: 25 feet25\,\text{feet} in length, painted red, 6 inch6\,\text{inch} diameter; capable of flowing in excess of 2000 GPM2000\,\text{GPM} when connected directly to a steamer port.

  • High-Rise Pack:

    • Three shoulder bundles containing 65 feet65\,\text{feet} each (195 feet195\,\text{feet} total) of 212 inch2\frac{1}{2}\,\text{inch} lightweight hose.

    • Equipped with a lightweight shutoff bale, mini-stream shaper, and short stack tips (118 inch1\frac{1}{8}\,\text{inch} and a 12 inch\frac{1}{2}\,\text{inch} low-flow tip that discharges 40 GPM40\,\text{GPM} at 30 PSI30\,\text{PSI} NP).

    • High-Rise accessory bag contents: Inline pressure gauge, 212 inch2\frac{1}{2}\,\text{inch} gate valve, lightweight 45∘45^\circ elbow, 112 inch×212 inch1\frac{1}{2}\,\text{inch} \times 2\frac{1}{2}\,\text{inch} increaser, 112 inch1\frac{1}{2}\,\text{inch} fog nozzle, two spanners, marking chalk, 6 wooden door wedges, 6 latch straps, 6 glow sticks, 14 to 18 inch14\text{ to }18\,\text{inch} pipe wrench, flat and Phillips screwdrivers, Allen wrench set, and an 8 inch8\,\text{inch} adjustable crescent wrench.

  • Apartment Pack: Two 50 foot50\,\text{foot} sections (100 feet100\,\text{feet} total) of 134 inch1\frac{3}{4}\,\text{inch} hose, a 212 inch×112 inch2\frac{1}{2}\,\text{inch} \times 1\frac{1}{2}\,\text{inch} gated wye, and an adjustable nozzle.

  • Specialized distributor nozzles:

    • Attic distributor nozzles: Supplied via 112 inch1\frac{1}{2}\,\text{inch} or 212 inch2\frac{1}{2}\,\text{inch} pipe lengths from the floor below; discharges an umbrella spray pattern up to 40 feet40\,\text{feet} in diameter (150 GPM150\,\text{GPM} for 112 inch1\frac{1}{2}\,\text{inch} at 100 PSI100\,\text{PSI}; 400 to 550 GPM400\text{ to }550\,\text{GPM} for 212 inch2\frac{1}{2}\,\text{inch} at 100 PSI100\,\text{PSI}).

    • Cellar nozzle: Drops through floor openings to flow 500 GPM500\,\text{GPM} at 50 PSI50\,\text{PSI} with a 40 foot40\,\text{foot} circular coverage area.

JFRD High Rise Pack hose and equipment component bundleAttic and cellar distributor penetration nozzles

Foam Systems, Agents, and Incident Proportioning

Chemical Foam Agents
  • Class A Foam: A synthetic hydrocarbon surfactant that reduces the surface tension of water, improving fuel penetration on Class A materials (brush, rubbish, structural overhaul). Educted at 14%\frac{1}{4}\%, 12%\frac{1}{2}\%, or 1%1\%. Never use on Class B fires.

  • Class B Foam: National Foam Universal Green 3% (Alcohol-Resistant Synthetic Foam). Used on both non-polar hydrocarbon fuels (gasoline, diesel) and polar solvents (alcohols, ketones). Educted at an invariant 3%3\% setting across all fuels.

  • Ethanol warning: Because commercial gasoline contains up to 10%10\% ethanol, Universal Green 3% combined with physical aeration is mandatory to achieve extinguishing expansion ratios.

  • Dedicated On-Board Apparatus Foam Tanks:

    • Engines 7 and 21: Equipped with an onboard automatic foam proportioning system and a 100 gallon100\,\text{gallon} Universal Green foam tank.

    • Foam 37: Industrial tanker carrying 2500 gallons2500\,\text{gallons} of Universal Green concentrate.

    • Crash Trucks at Stations 16 and 56: Carry 3%3\% Mil-Spec AFFF formulated for non-polar aviation fuels.

    • Chemical incompatibility warning: Mil-Spec AFFF and Universal Green are chemically incompatible and will gel if mixed in tanks or plumbing; however, they may be applied onto the same fire simultaneously through separate delivery devices.

  • Minimum On-Board Station Inventory Requirements:

    • Engines: Minimum of three 5-gallon pails (15 gallons15\,\text{gallons}) of Class B foam, and one 5-gallon pail (5 gallons5\,\text{gallons}) of Class A foam.

    • Tankers: Minimum of fifteen 5-gallon pails (75 gallons75\,\text{gallons}) of Class B foam, and five 5-gallon pails (25 gallons25\,\text{gallons}) of Class A foam.

Foam Proportioning Hardware and Hydraulics
  • Akron Inline Foam Eductor:

    • Rated for a fixed flow of 125 GPM125\,\text{GPM}.

    • Metering dial adjustable from 14%\frac{1}{4}\% to 6%6\%.

    • Hydraulic inlet pressure requirement: Must receive an inlet pressure of exactly 200 PSI200\,\text{PSI} to function properly.

    • If inlet pressure is below 200 PSI200\,\text{PSI}, venturi suction draws excess concentrate (yielding an overly rich mix and draining foam supplies prematurely), while line flow drops below 125 GPM125\,\text{GPM}.

  • Nozzle matching and aeration attachments:

    • The attack nozzle must be set to match the eductor rating: precisely 125 GPM125\,\text{GPM}.

    • The nozzle bale must be opened fully; partially closing the bale creates backpressure that shuts down the venturi draft.

    • The Akron Foam Aeration Tube must be snapped onto the Turbojet nozzle when discharging Universal Green 3% to achieve mechanical air aspiration and foam blanket expansion.

  • Distance limits from eductor to nozzle:

    • When using a 75 PSI75\,\text{PSI} fog nozzle: maximum distance of 250 feet250\,\text{feet} of 134 inch1\frac{3}{4}\,\text{inch} hose.

    • When using a 100 PSI100\,\text{PSI} fog nozzle: maximum distance of 150 feet150\,\text{feet} of 134 inch1\frac{3}{4}\,\text{inch} hose.

  • High-Capacity Eductors: Engines 7, 21, and select regional pumpers carry the Akron 250 GPM250\,\text{GPM} eductor and aerator tube. Handline requirements: 212 inch2\frac{1}{2}\,\text{inch} hose, an Akron 212 inch2\frac{1}{2}\,\text{inch} nozzle flowing 250 GPM250\,\text{GPM}, with up to 300 feet300\,\text{feet} of hose and an inlet pressure of 200 PSI200\,\text{PSI}.

Akron inline foam eductor showing pickup tubeAkron foam aeration tube snapped onto the nozzle tip
Application Tactics and Foam Management
  • Application rule: Foam blankets must remain static to extinguish flammable liquid fires; dike, dam, and divert running liquid pools before application.

  • Three-dimensional pressurized fuel fires: Foam alone will not suppress gravity-fed or pressurized fuel sprays; combine with dry chemical agent (Purple K) for a dual-agent attack.

  • Blanket thickness: Apply foam using gentle bounce-off, roll-on, or rain-down methods until a uniform 4 inch4\,\text{inch} foam blanket covers the entire fuel surface.

  • Verify vapor suppression: Check perimeter air with a photoionization or combustible gas indicator (LEL meter).

  • Reapplication: Reapply foam every 5 to 15 minutes5\text{ to }15\,\text{minutes}.

  • Twenty-five percent drain time: The duration required for 25%25\% of the water to drain from the foam matrix is 90 minutes90\,\text{minutes} using seawater, and 300 minutes300\,\text{minutes} using fresh municipal water.

Extrication Tools, Ground Ladders, and Portable Extinguishers

Engine Company Ground Ladders
  • 24 foot24\,\text{foot} Extension Ladder: Reaches first-story residential roofs, second-story window sills, and second-story residential balconies.

  • 14 foot14\,\text{foot} Roof Ladder: Provides roof access on single-story structures, high-ceiling interior reach, and operates on pitched roofs with folding roof hooks deployed.

  • 10 foot10\,\text{foot} Folding Attic Ladder: Accesses residential scuttle holes, narrow interior attic openings, and small elevated openings.

Engine company standard complement of ground ladders
Vehicle Extrication Complement
  • Mechanical tools: High-lift mechanical jack with vehicle lifting attachments; three lengths of alloy rescue chain (6 foot6\,\text{foot}, 12 foot12\,\text{foot}, and 15 foot15\,\text{foot}); one J-hook with shackle; one mechanical cable come-along winch; three wooden step chocks; one box of ladder wedge cribbing; and dimensional 4×4 inch4\times 4\,\text{inch} hardwood cribbing.

  • Pneumatic air chisel: Provided with three specialized cutting bits: long flat chisel, short flat chisel, and a panel cutter.

  • Powered hydraulic rescue tools (spreaders, cutters, and telescopic rams): Conventional hydraulic pump models or self-contained battery-powered eDRAULIC units.

Battery-powered eDRAULIC extrication rescue tool
Portable Fire Extinguishers
  • Pressurized Water: 212 gallon2\frac{1}{2}\,\text{gallon} capacity; range of 30 feet30\,\text{feet}; UL rating 2A2A.

  • Carbon Dioxide (CO2CO_2): 20 pound20\,\text{pound} capacity; range of 8 feet8\,\text{feet}; UL rating 10B:C10B:C.

  • Purple K Dry Chemical (PKP - Potassium Bicarbonate):

    • Standard model: 18 pound18\,\text{pound} cylinder; range of 18 feet18\,\text{feet} for 18 seconds18\,\text{seconds}; UL rating 80B:C80B:C.

    • High-flow model (distinguished by a red handle): 30 pound30\,\text{pound} cylinder; range of 18 feet18\,\text{feet} discharged in 8 seconds8\,\text{seconds}; UL rating 20B:C20B:C.

  • Class D dry powder extinguishers (MET-L-X and LITH-X): Used on combustible metals (magnesium, titanium, lithium); deployed via an external cartridge discharge nozzle.

Portable extinguisher complement: CO2, Pressurized Water, and Purple K

Advanced Fireground Pumping Operations

Water Supply Estimation and Residual Pressure Drop Methods
  • Estimating available supply: Record static intake pressure before opening any discharge. Once water is flowing, observe the residual intake pressure. The drop from static to residual determines available line capacity:

    • Residual drop less than 10%10\%: Can supply three (3) additional lines of equal flow.

    • Residual drop between 10%10\% and 20%20\%: Can supply two (2) additional lines of equal flow.

    • Residual drop between 20%20\% and 25%25\%: Can supply one (1) additional line of equal flow.

    • Residual drop greater than 25%25\%: Water supply is nearly exhausted; only a lower-volume line can be added.

  • Example: Static pressure reads 65 PSI65\,\text{PSI}. A deck gun is charged flowing 800 GPM800\,\text{GPM}, dropping residual pressure to 55 PSI55\,\text{PSI}. The drop is 10 PSI10\,\text{PSI}.     1065=0.1538(15.4% drop)\frac{10}{65} = 0.1538 \quad (15.4\%\text{ drop})     Because the drop falls between 10%10\% and 20%20\%, the main can support two additional lines of equal volume (2×800=1600 GPM2\times 800 = 1600\,\text{GPM} additional capacity).

  • Booster tank transition: When switching from tank water directly to a hydrant while lines are flowing, static pressure is bypassed; assume a standard baseline static pressure of 70 PSI70\,\text{PSI}.

Pumping Multiple Lines and Pressure Gating
  • Throttle management: Throttle the fire pump to supply the line requiring the highest pressure.

  • Pressure gating: Manually gate down the discharge valves supplying lines that require lower pressure, observing the individual line pressure gauge (not the master discharge gauge).

  • Water flow requirement: Water must be flowing through a line to accurately set and gate discharge pressure; static lines cannot be gated down.

  • Locking handles: Once dialed in, rotate the mechanical pull handle 45∘45^\circ to lock the internal ball valve in place.

Elevated Master Streams and Ladder Pipes
  • Supply guidelines:

    • Position the engine within 100 feet100\,\text{feet} of the ladder truck turntable.

    • Initial pump discharge pressure: 150 PSI150\,\text{PSI} for all nozzle configurations.

    • Supply via 5 inch5\,\text{inch} hose connected directly to the ladder truck's side or rear waterway intake.

    • Mid-ship aerials have side intakes; rear-mount aerials have a single rear intake.

  • Flow limits: Standard JFRD ladder truck waterways are limited to flows between 1000 and 1250 GPM1000\,\text{and }1250\,\text{GPM} (tower ladders excluded). Never exceed 200 PSI200\,\text{PSI} supply pressure.

Engine pumping water into the rear waterway intake of a ladder truck
Engine Deck Guns and Ground-Based Master Monitors
  • Apparatus deck gun: When discharged from the engine carriage, elevate the barrel assembly. If detached and mounted to the portable ground stinger base, never elevate the barrel into an upper extension.

  • Deck Gun Master Stream Nozzle Hydraulics:

    • Fog Master Nozzle: 100 PSI100\,\text{PSI} nozzle pressure; selectable flows of 500,750,1000, and 1250 GPM500, 750, 1000,\text{ and }1250\,\text{GPM}.

    • Smooth Bore Master Stream Tips (80 PSI80\,\text{PSI} nozzle pressure):

      • 138 inch1\frac{3}{8}\,\text{inch}: flows 500 GPM500\,\text{GPM}.

      • 112 inch1\frac{1}{2}\,\text{inch}: flows 600 GPM600\,\text{GPM}.

      • 134 inch1\frac{3}{4}\,\text{inch}: flows 800 GPM800\,\text{GPM}.

      • 2 inch2\,\text{inch}: flows 1000 GPM1000\,\text{GPM}.

      • (Some engines carry an older 114 inch1\frac{1}{4}\,\text{inch} tip flowing 400 GPM400\,\text{GPM}).

  • Heavy Ground Monitor Calculations:     PDP=Nozzle Pressure+Friction Loss+Appliance Loss\text{PDP} = \text{Nozzle Pressure} + \text{Friction Loss} + \text{Appliance Loss}

    • Add 10 to 25 PSI10\text{ to }25\,\text{PSI} friction loss for the monitor appliance itself (use 25 PSI25\,\text{PSI} for high flows).

    • Add 25 PSI25\,\text{PSI} friction loss per 100 feet100\,\text{feet} of siamesed dual 212 inch2\frac{1}{2}\,\text{inch} supply lines.

  • Example: A ground monitor with a 112 inch1\frac{1}{2}\,\text{inch} tip (80 PSI80\,\text{PSI} NP) supplied by 200 feet200\,\text{feet} of dual siamesed 212 inch2\frac{1}{2}\,\text{inch} hose:     PDP=80 PSI+50 PSI(hose FL)+25 PSI(appliance)=155 PSI\text{PDP} = 80\,\text{PSI} + 50\,\text{PSI} (\text{hose FL}) + 25\,\text{PSI} (\text{appliance}) = 155\,\text{PSI}

  • Mechanical anchoring: Large ground monitors must be secured using a safety chain wrapped around the supply hose loop or pinned to a structural anchor.

  • Mini-Monitor: Equipped with a single 212 inch2\frac{1}{2}\,\text{inch} inlet flowing up to 500 GPM500\,\text{GPM} at 100 PSI100\,\text{PSI} NP. For hose lays longer than 200 feet200\,\text{feet}, use a siamese with dual 212 inch2\frac{1}{2}\,\text{inch} lines to limit line friction loss to 25 PSI25\,\text{PSI} per 100 feet100\,\text{feet}.

Detached ground monitor anchored via supply hose loop and chain
Hydrant Connection Options
  • Single 5 inch5\,\text{inch} Soft Line: Fast, standard deployment.

  • Full Hydrant Connection: Connect the 412 inch4\frac{1}{2}\,\text{inch} steamer to a 5 inch5\,\text{inch} hose, and simultaneously connect a second 5 inch5\,\text{inch} hose to a 212 inch2\frac{1}{2}\,\text{inch} side port using a Storz adapter. Increases total available flow by approximately 25%25\%.

  • Hard Suction Hydrant Hook-Up: Delivers the maximum possible volume from a hydrant. The engine must be spotted within 10 feet10\,\text{feet} of the barrel. Remove the PIV and connect a 6 inch6\,\text{inch} heavy-duty suction hose directly to the steamer inlet. Requires a crew of 2 to 3 personnel.

  • Six-Inch Soft-Intake Hose: Uses a 25 foot25\,\text{foot} flexible 6 inch6\,\text{inch} soft intake. Must be connected directly to the pump steamer without a restrictive PIV to flow over 2000 GPM2000\,\text{GPM}.

Full hydrant connection using steamer and 2.5-inch side discharge into dual 5-inch lines
Relay Pumping Operations
  • Relay pumping is required whenever an attack engine is located beyond a full bed load (1000 feet1000\,\text{feet}) of 5 inch5\,\text{inch} hose from a water source.

  • Apparatus roles:

    • Supply engine: Spots at the hydrant and pumps into the relay.

    • Relay engines: Positioned every 1000 feet1000\,\text{feet} along the supply line.

    • Attack engine: Positioned at the fire scene supplying handlines.

  • Relay hydraulic rules:     Supply Engine Initial PDP=50 PSI+10 PSI per 100 feet of 5 inch hose\text{Supply Engine Initial PDP} = 50\,\text{PSI} + 10\,\text{PSI per } 100\,\text{feet of } 5\,\text{inch hose}

    • Pumping 1400 GPM1400\,\text{GPM} produces 10 PSI10\,\text{PSI} of friction loss per 100 feet100\,\text{feet}.

    • Maintain a minimum of 50 PSI50\,\text{PSI} residual pressure at each subsequent relay engine.

    • Maximum allowable PDP in a relay is 200 PSI200\,\text{PSI}.

    • Minimum allowable intake residual pressure is 10 PSI10\,\text{PSI}.

  • Transfer valve and governor modes in relays:

    • All supply and intermediate relay engines must operate with two-stage pumps set in VOLUME and governors set in RPM mode.

    • Only the final attack engine operates in PSI mode to provide automatic pressure relief for handline crews.

Relay pumping operation showing supply engine delivering water through LDH to an attack engine
Tandem Pumping Operations (Intake-to-Intake)
  • Tandem pumping provides a secondary attack engine with water from a well-supplied initial attack engine without subjecting the second engine to high discharge pressures.

  • Setup: An LDH line is connected from an unused intake on the primary attack engine directly into the intake of the secondary attack engine.

  • The secondary engine receives water at the source hydrant's residual pressure, making line gating manageable without compounding pump pressures.

  • Both engines must monitor water usage to ensure residual pressure on both pumps remains above 10 PSI10\,\text{PSI} to prevent cavitation.

Tandem pumping diagram illustrating intake-to-intake connection
Sprinkler and Standpipe Operations
  • Spotting: Position the engine within 100 feet100\,\text{feet} of the Fire Department Connection (FDC).

  • Commercial Sprinkler Systems:

    • Maintain a continuous pump discharge pressure of 150 PSI150\,\text{PSI}.

    • Flow verification: To confirm water is flowing through the system, slowly gate down the discharge valve slightly; if the needle drops below current pressure, water is flowing through open heads. If pressure remains static, heads have not fused.

  • Standpipe Systems:     Initial PDP=100 PSI+5 PSI per floor to the fire floor\text{Initial PDP} = 100\,\text{PSI} + 5\,\text{PSI per floor to the fire floor}

    • A Remote Pump Operator (RPO) equipped with an inline gate valve and pressure gauge must manage the outlet valve on the floor below the fire floor.

    • High-Rise Relay Supply: On tall high-rise structures, position two engines in series at the FDC. The first engine pumps 100 PSI100\,\text{PSI} into the intake of the second engine, which boosts the pressure to achieve the high discharge pressure required for upper stories.

  • FDC Troubleshooting:

    • Frozen swivel: Thread a 212 inch2\frac{1}{2}\,\text{inch} double male into the swivel, followed by a double female adapter.

    • Blocked or damaged FDC: Connect a 212 inch2\frac{1}{2}\,\text{inch} line directly into a first-floor standpipe discharge outlet inside the stairwell using a double female adapter and gate valve, and open the standpipe valve fully (will not work on pressure-reducing PRV valves).

    • Wall hydrants: Wall hydrants on building exteriors are designed for system flow testing; use them to supply the system only as a last resort.

Siamese Fire Department Connection (FDC) for standpipe systemBlocked FDC workaround using a double female adapter
Drafting Operations
  • Theoretical vs. practical lift:

    • Theoretical maximum lift: 33.8 feet33.8\,\text{feet}.

    • NFPA certified pump rating: 25 feet25\,\text{feet} of lift.

    • Maximum practical fireground lift: 25 feet25\,\text{feet} (measured vertically from water surface to the center of the steamer inlet).

    • If the vertical lift exceeds 10 feet10\,\text{feet}, pump capacity is reduced.

  • Strainer placement: Submerge the strainer with at least 18 inches18\,\text{inches} of water above it to prevent whirlpool vortex formation, and maintain at least 12 inches12\,\text{inches} of clearance off the muddy bottom. Tie off the hose with rope or support it on a roof ladder.

  • Plumbing configurations:

    • Remove the PIV and connect hard suction hose directly to the steamer inlet; do not draft through a PIV due to air leaks and flow restrictions. The BIV is vacuum-certified and can remain on the intake.

    • To achieve full capacity on 1750 or 2000 GPM1750\text{ or }2000\,\text{GPM} pumps, both side steamer intakes must be connected to hard suction.

  • Drafting sequence:

    1. Connect all hard suction joints wrench-tight; secure strainer.

    2. Set two-stage pump transfer valve to VOLUME.

    3. Set governor mode to RPM; increase engine speed to 1000 to 1200 RPM1000\text{ to }1200\,\text{RPM}.

    4. Actuate the primer until steady pressure registers above 50 PSI50\,\text{PSI} on the master discharge gauge.

    5. Slowly crack the discharge line to start water moving; switch governor to PSI mode once lines are flowing steadily.

Drafting setup from an open saltwater pier
International Shore Connection
  • Marine vessels operating at the Port of Jacksonville utilize a standardized bolt-on adapter flange conforming to international maritime standards.

  • Mount the flange to the shipboard standpipe riser, bolt the halves together with the supplied gasket, connect a 212 inch2\frac{1}{2}\,\text{inch} supply line, and pump according to the ship engineer's specifications.

International Shore Connection flange assembly

Water Tanker (Shuttle) Apparatus and Rural Water Logistics

  • JFRD automatically dispatches three (3) tankers to all reported structural fires, regardless of whether hydrants are present in the district.

Tanker Apparatus Specifications
  • Chassis and pump: Pierce commercial chassis with single-stage Hale or Waterous 750 GPM750\,\text{GPM} centrifugal pumps.

  • Water tank: 2500 gallon2500\,\text{gallon} baffled and vented aluminum/poly tank.

  • Tank-to-pump valve: 4 inch4\,\text{inch} diameter slow-operating handwheel valve, allowing tankers to discharge up to their full 750 GPM750\,\text{GPM} rating directly from the tank.

  • Pump engagement: Power Take-Off (PTO) system. Shifting the transmission into DRIVE automatically disengages the PTO pump.

  • Discharge and dump hardware:

    • Rear 10 inch10\,\text{inch} square quick-dump valve with a directional swiveling chute, discharging 2500 gallons2500\,\text{gallons} in 2 to 3 minutes2\text{ to }3\,\text{minutes}.

    • Equipped with a PIV intake, LDH discharge, two pre-connected 134 inch1\frac{3}{4}\,\text{inch} lines, and a deck gun.

  • Rural equipment inventory: Portable folding water basin (2500 or 3000 gallon2500\text{ or }3000\,\text{gallon} capacity) with ground tarp, 6 inch6\,\text{inch} low-level strainer with jet siphon, and two sections of 3 inch3\,\text{inch} supply hose.

JFRD 2500-gallon water tanker apparatusInternal view of tanker water baffling and direct-fill plumbing
Tanker Shuttle Logistics and Setup
  • Initial tanker deployment:

    • Deploy the ground protective tarp adjacent to the attack engine.

    • Unfold and set up the portable tanker basin, and drop the low-level strainer.

    • Align the rear dump chute, dump the 2500 gallon2500\,\text{gallon} load into the basin, and proceed to the fill site.

  • Positioning: Position the basin and tanker to block only a single traffic lane, leaving the passing lane clear for shuttle turnaround.

  • Refill engine operations at the fill site:

    • A dedicated engine company spots at a water source (hydrant or static water draft).

    • Connect two 212 inch2\frac{1}{2}\,\text{inch} or 3 inch3\,\text{inch} supply lines to the tanker's rear direct-fill connections.

    • Refill pump pressure: Pump at an inlet pressure of 100 PSI100\,\text{PSI}; higher pressures can damage the internal baffles and tank walls. Refill time is approximately 3 minutes3\,\text{minutes}.

  • Water delivery rate calculation:     Flow Rate (GPM)=Tanker GallonsTotal Shuttle Round-Trip Time (Minutes)\text{Flow Rate (GPM)} = \frac{\text{Tanker Gallons}}{\text{Total Shuttle Round-Trip Time (Minutes)}}

    • Based on an average 10-minute round trip (5 minutes5\,\text{minutes} travel, 2.5 minutes2.5\,\text{minutes} refill, and 2.5 minutes2.5\,\text{minutes} dump), a single tanker sustains a continuous fire flow of only 250 GPM250\,\text{GPM}. Adding a second tanker increases the delivery rate to 500 GPM500\,\text{GPM}.

Dual portable tanker basins set up on scene
Multi-Basin Water Transfer (Jet Siphon)
  • When multiple basins are used, transfer water between them using a jet siphon.

  • Connect a 134 inch1\frac{3}{4}\,\text{inch} supply line from a pumper discharge to the jet siphon connection on the low-level strainer.

  • Connect a section of hard suction or lightweight hose to the strainer outlet, extending it into the primary drafting basin.

  • Pumping the jet siphon at 150 PSI150\,\text{PSI} transfers water at rates up to 540 GPM540\,\text{GPM}.

Modified Tanker Shuttle (Direct Siamese Operation)
  • When narrow roads or long driveways prevent basin deployment, use a modified direct shuttle.

  • The attack engine lays an uncharged supply line into the scene, terminating at the street in a 212 inch2\frac{1}{2}\,\text{inch} siamese.

  • Arriving tankers connect directly to the siamese and pump their tank water directly into the attack engine in an alternating relay, departing for the fill site as soon as they run dry.

Off-Road Mechanical Traction Systems
  • Tankers feature dash-mounted rocker switches controlling four-wheel drive and driver-controlled differential locks.

  • Engage differential locks before leaving paved roads to prevent getting stuck in loose sand or mud.

Dash-mounted traction switches for four-wheel drive and differential locks

Troubleshooting Fire Pump and Engine Malfunctions

Thermal Overheating
  • Fire pump overheating:

    • Caused by continuous churning of water inside the pump casing when handlines are closed.

    • Mitigation: Open the PUMP COOLER/recirculator line to return hot water to the booster tank; partially crack the TANK FILL valve; or charge the booster line and direct the nozzle into the water tank fill opening.

  • Engine motor overheating:

    • Open the ENGINE COOLER valve on the pump panel to circulate water through the internal radiator heat exchanger.

    • If engine temperature continues to rise, charge the booster line and direct a wide fog spray through the front grille directly onto the radiator fins.

    • Post-drafting wash: If raw water from a pond or river is sprayed onto the radiator, thoroughly wash the radiator, engine block, and cab undercarriage with fresh water and soap to prevent galvanic corrosion.

Pump Shift Failure and Disabled Engine "Pump-Through"
  • Manual pump shift override: If the in-cab pneumatic shift system loses air or fails, engage the pump using the manual shift handle on the pump panel (see Appendix E).

  • Pump-Through operation for a disabled engine: If an attack engine suffers a complete mechanical pump or motor failure while lines are operating inside a structure, a secondary engine can pump water through the disabled engine's discharge manifold (see Appendix H).

Manual emergency pump shift T-handle control on pump panel
Failure to Build Pressure and Loss of Prime
  • The most common cause of failure to build discharge pressure is trapped air inside the pump casing.

  • Actuate the primer until steady water discharges and the master discharge gauge shows positive pressure.

  • If the electronic governor prevents throttling up in PSI mode, switch to RPM mode and manually increase engine speed to force trapped air through the discharges.

  • If priming fails while drafting, inspect for open drain valves, loose suction hose couplings, open air bleeders, and air pockets along the hard suction hose. Check the discharge pipe on the internal intake relief valve; cap it with a 212 inch2\frac{1}{2}\,\text{inch} cap if the internal seat is leaking air.

  • Air displacement trick: To displace stubborn air while priming, open the TANK-TO-PUMP valve for a few seconds while the primer is running to flood the pump body with tank water, then close it.

Cavitation Dynamics
  • Cavitation occurs when the pump attempts to discharge more water than it receives at the intake.

  • Mechanical phenomenon: As intake pressure drops toward absolute zero, pressure at the impeller eye falls below the vapor pressure of the liquid, causing water to boil and form vapor bubbles. As these bubbles travel into the high-pressure zones of the volute, they collapse violently against the metal, eroding the bronze impellers and producing a distinct sound like rocks or gravel circulating in the pump.

  • Diagnostic indications: The earliest signs of cavitation are fluctuating discharge pressure gauges and an engine that revs without a corresponding increase in water pressure.

  • Preventive limit: Maintain at least 10 PSI10\,\text{PSI} residual intake pressure at all times.

Pitted impeller damage and fluctuating gauge during severe cavitation
Critical Velocity
  • Critical velocity is the maximum speed at which water can flow through a given diameter of fire hose before laminar flow breaks down into severe turbulence.

  • Once critical velocity is reached, increasing pump discharge pressure will not increase flow; instead, turbulence causes stream reach to degrade.

  • Corrective actions: Reduce engine RPM; step down the nozzle tip size or flow setting; or advance a larger diameter hose line (e.g., replace a 134 inch1\frac{3}{4}\,\text{inch} line with a 212 inch2\frac{1}{2}\,\text{inch} line).

Annual Service Testing Protocols for Fire Hose

  • Mandatory testing period: All fire hose must undergo annual service testing between March 15 and April 15 in accordance with NFPA standards.

  • Testing pressures and duration:

    • Large Diameter Hose (5 inch5\,\text{inch} and 6 inch6\,\text{inch}): Test at 200 PSI200\,\text{PSI} continuously for 5 minutes5\,\text{minutes}.

    • Small and Medium Diameter Hose (1 inch1\,\text{inch}, 134 inch1\frac{3}{4}\,\text{inch}, 212 inch2\frac{1}{2}\,\text{inch}, and 3 inch3\,\text{inch}): Test at 300 PSI300\,\text{PSI} continuously for 5 minutes5\,\text{minutes}.

  • Layout and testing safety:

    • Lay hose out on a dry, slight incline; connect test nozzles to the far ends to bleed air.

    • Mark the hose jacket at the back of each coupling with a pen to detect coupling slippage.

    • Fill the lines, bleed all air, and slowly raise pressure to the test level.

    • Safety gate closure: Once up to test pressure, gate the discharge valve down almost completely closed. This traps static pressure in the test layout while limiting the volume released if a hose ruptures.

    • Safety perimeter: Personnel must stay clear of the test area while hose is pressurized; never inspect couplings closely while under test pressure.

    • Post-test inspection: Inspect the line markings for coupling slippage, weeping, or jacket damage. Tag any damaged or failed sections and route them to TSF for repair or disposal.

Reference Quick Sheets, Hydraulic Theory, and Specialized Appendices

Appendix A: Diesel Motor Regeneration (DPF and SCR)
  • Diesel Particulate Filter (DPF) traps particulate soot; Selective Catalytic Reduction (SCR) treats exhaust with DEF to convert harmful NOxNO_x into nitrogen and water vapor.

  • Automatic Regeneration: Occurs automatically while driving or pumping when exhaust temperatures and conditions permit. HEST lamp illuminates when exhaust temperatures exceed 800oF800^\text{o}\text{F}.

  • Automatic regeneration during pumping requires:

    • Engine speed between 1025 and 1850 RPM1025\text{ and }1850\,\text{RPM}.

    • Virtual transmission output speed greater than 20 MPH20\,\text{MPH}.

    • Parking brake set, pump engaged, and transmission selector in DRIVE.

  • Regeneration controls and lamps:

    • REGEN INHIBIT switch: Inhibits or aborts a regeneration cycle (used when parked over dry grass or near flammables).

    • DPF REGEN switch: Manually initiates a parked regeneration cycle.

    • Flashing DPF lamp and illuminated CHECK ENGINE lamp indicate an urgent need for manual regeneration.

    • Illuminated red STOP ENGINE lamp indicates critical soot clogging; vehicle must be shut down immediately.

DPF Regeneration indicator lampHigh Exhaust System Temperature (HEST) indicator lampStop Engine red malfunction warning lampRegeneration control rocker switches and diagnostic port
Appendix B: JFRD Engine Specifications (2014 and Newer)
  • Fire pump: Midship-mounted two-stage Waterous centrifugal pump.

  • Rated capacity: 1500 or 1750 GPM1500\text{ or }1750\,\text{GPM}.

  • Water booster tank: 500 gallons500\,\text{gallons}.

  • Pressure governor: FRC Pump Boss electronic governor.

Appendix C: Engine Company Color Identification Markings
  • E-1: Red, White, Red

  • E-2: Red, White, Blue

  • SQ-4: Red

  • E-5: White

  • E-7: Silver

  • E-9: Green, White

  • E-10: Yellow, Red

  • E-11: Green

  • SQ-12: Yellow

  • E-13: Silver, Blue

  • SQ-14: White, Black

  • E-16: Yellow, Black

  • E-17: Black

  • E-18: Blue, Yellow

  • E-19: Green, Blue

  • E-20: Red, White, Red

  • E-21: Green, White, Green

  • E-22: Green, Silver

  • E-23: Green, Yellow, Green

  • E-24: White, Black, White

  • E-25: Yellow, Black, Yellow

  • E-26: White, Silver

  • E-27: Green, Blue, Green

  • E-28: Black, White, Black

  • E-29: Red, White

  • E-30: Silver, Yellow

  • E-31: Red, Silver, Red

  • E-32: Red, Blue, Red

  • E-33: Blue, Silver, Red

  • E-34: White, Blue

  • E-35: Yellow, Black, White

  • E-36: Blue, Yellow, Blue

  • SQ-37: Orange

  • ST-38: Green, Red

  • ST-39: Red, Silver

  • E-40: Green, Red, Green

  • E-41: Red, Black, Red

  • E-42: Blue, White, Blue

  • E-43: Yellow, Orange, Yellow

  • E-44: Orange, Yellow, Orange

  • E-45: Blue, Silver, Blue

  • E-46: Blue, Red

  • E-47: Black, Red

  • E-48: Green, Black

  • E-49: Green, Yellow

  • E-50: White, Green, White

  • E-51: White, Yellow, White

  • E-52: Black, Yellow, Black

  • E-53: Orange, Blue

  • E-54: Black, Silver

  • E-55: Blue, White, Blue

  • CR-56: Garnet, Gold, Garnet

  • E-57: Orange, White

  • E-58: Red, Black, Green

  • E-59: Black, Gold, Teal

  • E-60: Red, Green, Red

  • E-61: Black, Red, Black

  • E-62: Yellow, Black, Blue

  • SQ-63: Green, White, Orange

  • E-64: Teal

  • E-65: Burgundy

  • E-71: Orange, Blue, Orange

  • E-72: Blue

  • E-73: Yellow, Blue, Yellow

  • E-74: Orange, Black

  • E-75: Blue, Green, Blue

  • E-76: White, Orange, White

  • Tankers (TA): Garnet, Blue

Appendix D: Hydraulic Theory and Mathematical Formulas
  • Fluid Head and Elevation Pressures:

    • A 1 foot1\,\text{foot} column of water exerts 0.434 PSI0.434\,\text{PSI} at its base.

    • 1 PSI1\,\text{PSI} will lift a vertical water column 2.304 feet2.304\,\text{feet}.

    • Field head pressure calculation: Elevation loss equals 5 PSI5\,\text{PSI} per story (11.5 feet11.5\,\text{feet} average height), excluding the first (ground) floor.

  • Theoretical Friction Loss Coefficient Method:     FL=C×Q2×L\text{FL} = C \times Q^2 \times L

    • Where Q=GPM100Q = \frac{\text{GPM}}{100}.

    • Where L=Hose Length in Feet100L = \frac{\text{Hose Length in Feet}}{100}.

    • Hose Coefficients (CC):

      • 1 inch1\,\text{inch} Hose: C=150C = 150

      • 134 inch1\frac{3}{4}\,\text{inch} Hose: C=7.44C = 7.44

      • 212 inch2\frac{1}{2}\,\text{inch} Hose: C=1.75C = 1.75

      • 3 inch3\,\text{inch} Hose: C=0.8C = 0.8

      • 5 inch5\,\text{inch} Hose: C=0.05C = 0.05

  • Total Pump Discharge Pressure Equation:     PDP=NP+FL+BP+HA\text{PDP} = \text{NP} + \text{FL} + \text{BP} + \text{HA}

    • Where NP=Nozzle Pressure\text{NP} = \text{Nozzle Pressure}.

    • Where FL=Total Hose Friction Loss\text{FL} = \text{Total Hose Friction Loss}.

    • Where BP=Back Pressure / Elevation Loss (or Gain)\text{BP} = \text{Back Pressure / Elevation Loss (or Gain)}.

    • Where HA=Heavy Appliance Friction Loss\text{HA} = \text{Heavy Appliance Friction Loss}.

  • The Minus 10 Field Rule for 212 inch2\frac{1}{2}\,\text{inch} Hose:

    • To find friction loss in 100 feet100\,\text{feet} of 212 inch2\frac{1}{2}\,\text{inch} hose, drop the last zero from the line's GPM and subtract 10.

    • Example: For a flow of 250 GPM250\,\text{GPM}, drop the zero (2525) and subtract 10: 25−10=15 PSI25 - 10 = 15\,\text{PSI} loss per 100 feet100\,\text{feet}.

  • Smooth Bore Discharge Formula:     GPM=29.7×D2×NP\text{GPM} = 29.7 \times D^2 \times \sqrt{\text{NP}}

    • Where D=Nozzle tip diameter in inchesD = \text{Nozzle tip diameter in inches}.

    • Where NP=Nozzle pressure in PSI\text{NP} = \text{Nozzle pressure in PSI}.

Appendix E: Manual Pump Shift Evolution
  • Step 1: Shift transmission to NEUTRAL (N); set parking brake.

  • Step 2: Move the in-cab pneumatic pump shift lever to NEUTRAL (center).

  • Step 3: Go to the pump panel and pull the manual emergency pump shift T-handle firmly outward.

  • Step 4: Return to the cab and move the pneumatic shift switch to PUMP.

  • Step 5: Shift transmission to DRIVE (D); confirm lock-up (speedometer registers 15 to 20 MPH15\text{ to }20\,\text{MPH}, transmission shows 44).

  • Disengagement sequence: Shift transmission to NEUTRAL, place in-cab switch to NEUTRAL, and push the manual pump panel T-handle all the way back in.

Appendix F: Engine Company Fireground Skills Checklists
  • Skill 1: Pumping a pre-connected handline from booster tank.

  • Skill 2: Hand-laying supply line to hydrant.

  • Skill 3: Establishing engine or tanker secondary supply.

  • Skill 4: Transitioning from tank water to pressurized hydrant supply.

  • Skill 5: Pumping attack lines while simultaneously supplying water to another apparatus.

  • Skill 6: Drafting from a portable tanker basin.

  • Skill 7: Supplying elevated ladder pipes.

  • Skill 8: Deploying ground-based master stream monitors.

  • Skill 9: Relay pumping from a hydrant (hooking up).

  • Skill 10: Pumping multiple lines at variable pressures.

  • Skill 11: Placing an inline foam eductor line into operation.

Appendix G: TurboDraft Alternative Water Supply Operations
  • The TurboDraft eductor enables an engine to draft from static open water sources up to 100 feet100\,\text{feet} away and up to 20 feet20\,\text{feet} of vertical lift.

  • Operation: Connect a 212 inch2\frac{1}{2}\,\text{inch} high-pressure supply line and a 5 inch5\,\text{inch} return line to the unit; submerge the appliance; pump 180 PSI180\,\text{PSI} into the 212 inch2\frac{1}{2}\,\text{inch} line; the venturi return stream supplies water back into the engine intake.

TurboDraft deep-lift eduction appliance
Appendix H: Disabled Engine "Pump-Through" Procedure
  • If an attack engine's pump or motor fails during structural operations, a secondary pumper can pump water through the disabled engine's discharge plumbing.

  • Supply lines connected: Connect a 5 inch5\,\text{inch} hose from the second engine's LDH discharge into the disabled engine's LDH discharge port. Open both valves. Connect a second line from the disabled engine's steamer intake into the second engine's intake.

  • The second engine charges the line to an initial PDP of 150 PSI150\,\text{PSI}, pressurizing the disabled engine's discharge manifold and restoring flow to the attack lines.

Appendix I: Wildland Brush Trucks and Skid Units
  • Tank and pump hardware: 1-ton pickup chassis (Ford F350, Chevy/Ram 3500) carrying a 250 gallon250\,\text{gallon} water tank, a 10 gallon10\,\text{gallon} Class A foam cell, and an 18 to 20 HP18\text{ to }20\,\text{HP} engine-driven pump flowing 125 GPM125\,\text{GPM} at 125 PSI125\,\text{PSI}.

  • Booster reel: 200 feet200\,\text{feet} of 1 inch1\,\text{inch} hose flowing approximately 30 GPM30\,\text{GPM} at 150 PSI150\,\text{PSI} PDP.

  • Proportioning systems:

    • Hale pump with Foam-Flo proportioner (Briggs & Stratton engine).

    • CET pump with Scotty around-the-pump proportioner (Honda engine).

    • Standard proportioning rate: 0.25%0.25\% (one-quarter of one percent).

    • Field batch mixing: If the automatic proportioner is inoperative, pour one 32 ounce32\,\text{ounce} cup of Class A foam concentrate directly into the 250 gallon250\,\text{gallon} booster tank to achieve the proper 0.25%0.25\% wetting ratio.

Foam-Flo Class A proportioner placard for wildland brush truckScotty around-the-pump Class A foam proportioning dial
Appendix J: Air Brake Diagnostic Inspection Guide
  • Pre-trip pressure: Primary and secondary systems must both exceed 110 PSI110\,\text{PSI} before moving.

  • Compressor cut-out and cut-in tests: Governor cuts out the compressor at approximately 125 PSI125\,\text{PSI}, and cuts back in at approximately 100 PSI100\,\text{PSI}.

  • Low pressure warning: Warning light and audible buzzer must activate before air pressure falls below 60 PSI60\,\text{PSI}.

  • Automatic spring brake deployment: Mechanical parking brake valve pop-up must activate before pressure drops below 40 PSI40\,\text{PSI}.

  • Pressure buildup rate: Air pressure must climb from 85 to 100 PSI85\text{ to }100\,\text{PSI} within 45 seconds45\,\text{seconds} at high idle.

  • Air leakage rate limits: Pressure drop with brakes released must not exceed 2 PSI2\,\text{PSI} in 1 minute for single vehicles. Under full service brake pedal application (≥90 PSI\ge 90\,\text{PSI} applied), system loss must not exceed 3 PSI3\,\text{PSI} in 1 minute.

Appendix K: Flammable Liquids Foam Reference Matrix
  • Spill application standard: Maintain a minimum 4 inch4\,\text{inch} continuous foam blanket over the entire fuel surface.

  • Calculated application formula:     Required Fire Flow (GPM)=Surface Area (sq ft)×0.20\text{Required Fire Flow (GPM)} = \text{Surface Area (sq ft)} \times 0.20

  • Highway cargo tanker standard: Assumes a standard surface area of 500 sq ft500\,\text{sq ft}, requiring a minimum finished foam fire flow of 100 GPM100\,\text{GPM}.

  • Foam concentrate required:     Foam Concentrate=Fire Flow×0.03×Application Time in Minutes\text{Foam Concentrate} = \text{Fire Flow} \times 0.03 \times \text{Application Time in Minutes}

JFRD Engine and Tanker Class B Foam Reference Guide Table
Appendix L: The Double Drop Street Method for Water Supply Estimation
  • Application restrictions: Used only when supplied by an active municipal hydrant on a 6 inch6\,\text{inch} or larger main using 5 inch5\,\text{inch} or 6 inch6\,\text{inch} supply hose no longer than 200 feet200\,\text{feet}.

  • Assumed line flows: Calculations assume a conservative maximum flow of 200 GPM200\,\text{GPM} for an initial 134 inch1\frac{3}{4}\,\text{inch} handline, and 300 GPM300\,\text{GPM} for a 212 inch2\frac{1}{2}\,\text{inch} handline.

  • Calculation steps:

    1. Record static intake pressure.

    2. Charge the initial line; set pressure and flow.

    3. Calculate the residual pressure drop.

    4. Double the residual drop (Drop×2\text{Drop} \times 2).

    5. Divide the remaining residual pressure by this doubled value to determine remaining flow increments.

  • Example: Static pressure reads 70 PSI70\,\text{PSI}. An initial 134 inch1\frac{3}{4}\,\text{inch} line is charged, dropping residual pressure to 60 PSI60\,\text{PSI} (10 PSI10\,\text{PSI} drop).     Doubled Drop=10 PSI×2=20 PSI\text{Doubled Drop} = 10\,\text{PSI} \times 2 = 20\,\text{PSI}     Remaining Increments=60 PSI20 PSI=3\text{Remaining Increments} = \frac{60\,\text{PSI}}{20\,\text{PSI}} = 3     3×200 GPM=600 GPM remaining in the supply line3 \times 200\,\text{GPM} = 600\,\text{GPM}\text{ remaining in the supply line}

  • For any additional lines added after the first, do not double the drop; use the actual pressure drop.

Appendix M: Standard Friction Loss and Pump Discharge Pressure Guides
  • Friction Loss per 100 feet100\,\text{feet} in 134 inch1\frac{3}{4}\,\text{inch} JFRD Spec Hose (1.88 inch1.88\,\text{inch} internal diameter):

    • At 95 GPM95\,\text{GPM}: 7 PSI7\,\text{PSI}

    • At 125 GPM125\,\text{GPM}: 12 PSI12\,\text{PSI}

    • At 150 GPM150\,\text{GPM}: 17 PSI17\,\text{PSI}

    • At 180 GPM180\,\text{GPM}: 24 PSI24\,\text{PSI}

    • At 200 GPM200\,\text{GPM}: 30 PSI30\,\text{PSI}

  • Friction Loss per 100 feet100\,\text{feet} in 212 inch2\frac{1}{2}\,\text{inch} JFRD Spec Hose:

    • At 150 GPM150\,\text{GPM}: 4 PSI4\,\text{PSI}

    • At 200 GPM200\,\text{GPM}: 7 PSI7\,\text{PSI}

    • At 250 GPM250\,\text{GPM}: 11 PSI11\,\text{PSI}

    • At 300 GPM300\,\text{GPM}: 16 PSI16\,\text{PSI}

    • At 400 GPM400\,\text{GPM}: 28 PSI28\,\text{PSI}

    • At 500 GPM500\,\text{GPM}: 44 PSI44\,\text{PSI}

  • Friction Loss per 100 feet100\,\text{feet} in 5 inch5\,\text{inch} Pro-Flow Supply Hose:

    • At 600 GPM600\,\text{GPM}: 2 PSI2\,\text{PSI}

    • At 800 GPM800\,\text{GPM}: 3 PSI3\,\text{PSI}

    • At 1000 GPM1000\,\text{GPM}: 5 PSI5\,\text{PSI}

    • At 1200 GPM1200\,\text{GPM}: 7 PSI7\,\text{PSI}

    • At 1400 GPM1400\,\text{GPM}: 9 PSI9\,\text{PSI}

    • At 1600 GPM1600\,\text{GPM}: 12 PSI12\,\text{PSI}

    • At 1800 GPM1800\,\text{GPM}: 16 PSI16\,\text{PSI}

    • At 2000 GPM2000\,\text{GPM}: 19 PSI19\,\text{PSI}