JFRD Engine Company Engineer Manual (Eighth Edition)
Historical Background and Apparatus Fleet
On January 2, 1870, Jacksonville's second volunteer fire company, The Mechanics Steam Engine Company, was formed on Adams Street between Main and Laura Streets.
The Mechanics purchased the State of Florida's first steam engine, which was rated to throw a water stream at a discharge rate of .
Training curricula and pump operations manuals developed by former Jacksonville Fire and Rescue Department (JFRD) Fire Chief Miles R. Bowers were subsequently adopted by the Florida State Fire College, remaining foundational to statewide pump operations instruction.
JFRD operates an active municipal fleet comprising more than 60 frontline engine companies citywide, alongside specialized pumping apparatus including water tankers, wildland brush trucks, airport crash trucks, and fireboats.

Preventive Maintenance Protocols
Operational apparatus readiness requires routine scheduled inspections, proactive upkeep, and immediate reporting of mechanical defects to the Tactical Support Facility (TSF).
Daily apparatus inspection results and discrepancies must be logged at the start of each shift via the JFRD Portal (located under the Tactical Support tab, within Daily Apparatus Management).
Immediate notification to the company officer and corresponding company logbook entries are required for any safety hazards, out-of-service components, or damaged, lost, or stolen tools.
Health and Safety Warning: Diesel exhaust is classified by NFPA and NIOSH as a known human carcinogen; there is no safe threshold of human exposure, mandating direct capture and active avoidance on station aprons and fire scenes.
Daily Engine and Chassis Inspection
Shift relief conference: Conduct a face-to-face debrief with the off-going engineer regarding mechanical status, handling characteristics, and recent operational history.
Fluid level verification:
Inspect motor oil, transmission fluid, radiator coolant, power steering fluid, and diesel exhaust fluid (DEF).
Rule on fluid placement: The engineer (or assigned relief operator) is the only member authorized to add fluids (DEF, diesel, unleaded, or oils) into an apparatus.
The company officer must independently verify that the correct fluid type and specification are added before pouring.
Both the engineer and company officer are held equally liable and subject to formal disciplinary action for catastrophic damage resulting from improper fluid placement.
Tank fluid verification:
Water booster tank levels and foam concentrate tank levels must be visually inspected directly inside the tank cells and compared against digital pump panel gauges.
Chassis and running gear checks:
Air brake pressure must read greater than in both front and rear split systems prior to moving.
Tires and wheels: Inspect cold inflation pressures, lug nut torque/witness marks, axle oil hub seals for weeping, and tread depth.
Minimum legal tread depth on front steer tires is (or flush with tread wear indicator bars).
Cab safety components: Confirm proper mechanical operation and positive latching of all passenger seat belts, and check windshield wiper blades/washers.
Lighting and alarms: Start the motor, run until it achieves normal operating temperature, and verify cab instrumentation, brake lights, directional signals, emergency lighting, audible sirens, and floodlighting.
Daily Fire Pump and Mechanical Inspection
Operational pump sequence:
Chock wheels, set parking brake, engage pump shift into pump gear, confirm green cab indicator lights, and place automatic transmission into drive.
Open the TANK-TO-PUMP valve and verify static pressure builds on the master discharge gauge.
Actuate the electric or air primer until water discharges freely to the pavement beneath the pump body.
Test electronic pressure governor functions in both PSI mode and RPM mode across varying engine speeds.
On two-stage pump models, actuate the electric transfer valve between VOLUME and PRESSURE to verify full mechanical gate travel.
Discharge water through at least one hoseline discharge to confirm water flow.
Cycle open and fully close both the driver-side and passenger-side intake valves (BIV or PIV); remove protective caps to drain accumulated water.
Post-pump shutdown servicing:
Disengage the fire pump, return transmission to neutral, and manually cycle all quarter-turn discharge and auxiliary valve pull-rods through their full range of motion.
Open all low-point drain valves and bleeder petcocks.
Momentarily open the main PUMP DRAIN valve to purge sediment, scale, and grit settled at the bottom of the pump casing.
Under-Cab and Underside Inspection Procedures
Prepare the cab interior: Secure or remove all loose equipment, thermal imagers, tools, and fluid bottles prior to activating the hydraulic tilt mechanism.
Cab tilt safety warning:
Personnel must never place any portion of their body beneath the cab structure while it is raising or lowering.
When fully elevated, physically verify that the mechanical cab tilt safety lock/pin is fully seated.
Never allow the lowered cab to rest unsupported upon the hydraulic lift cylinder or strut, as this introduces structural damage to the assembly.
Structural and powertrain checks under the cab:
Inspect serpentine drive belts for tension, cracking, fraying, and alignment.
Inspect the commercial battery banks for acid corrosion, loose terminal clamps, and casing cracks.
Crawl beneath the chassis to examine the engine oil pan, Allison transmission housing, midship pump transfer case, split-shaft driveline, and water piping for leaks.
Air brakes must be mechanically applied before crawling under the apparatus; never enter underneath an apparatus while the diesel motor is running.


Daily Tool and Medical Equipment Check
Automated External Defibrillator (AED): Change and charge lithium battery packs; run automated self-diagnostic circuits; verify pads, razors, and pediatric pads.
Medical Oxygen Cylinders: Cylinder pressure must register greater than ; restock bag-valve-masks, non-rebreathers, and nasal cannulas.
Emergency Medical Services (EMS) bags: Inventory advanced life support (ALS) diagnostic items, cervical immobilization collars, trauma dressings, and spine boards.
Pneumatic Air Chisel: Connect directly to a dedicated high-pressure SCBA cylinder; supply cylinder pressure must exceed .
Operating warning: Never depress the pneumatic chisel trigger unless the chisel bit is placed firmly against a sacrificial solid material to avoid cylinder piston ejection.
Self-Contained Breathing Apparatus (SCBA): Inspect packs, facepieces, regulators, and cylinder pressures in accordance with JFRD SOG 421.
Pre-connected fire hose beds: Confirm all crosslays and rear attack beds are neatly stacked, free of twists, with nozzles set to the proper GPM/pattern settings and cleared of internal debris.
Portable Chainsaws:
Inspect chain cutting teeth for sharpness and guide bar for binding.
Verify proper chain tension and direction of travel.
Top off fuel and bar lubricant reservoirs; bar lubricant on JFRD engines is standard clean motor oil.
Run the saw to verify clutch and oiler engagement.
Battery-powered hydraulic extrication tools (eDRAULIC):
Confirm battery pack charges and verify the electric pump motor function.
When returning hydraulic spreaders to vehicle brackets, store them with approximately a air gap between the tips to relieve static hydraulic pressure and prevent metal-to-metal binding.
Portable gasoline-powered motor maintenance:
Run auxiliary generators under load for approximately after checking crankcase oil and coolant.
Fuel shutdown procedure: Close the manual inline fuel petcock on all portable gas motors and run them until the carburetor runs completely dry and stalls; this purges the fuel system and avoids gumming caused by ethanol fuel additives.
Weekly Inspection and Servicing Schedules
Comprehensive weekly maintenance occurs every Monday under the direction of the station captain.
Cab and body conditioning: Deep clean interior floor mats, clean all glass/mirrors, account for map books and master gate keys, clean the thermal imaging camera (TIC), and apply automotive paste wax to exterior paint on a monthly schedule.
Roll-up compartment doors: Clean debris and aged grease from aluminum side tracks; apply dry silicone spray only. Apply light oil to door hinges, cycle multiple times, and wipe off all excess oil.
Pneumatic air reservoir draining: Locate the manual drain pull-cords or petcocks on all chassis compressed air tanks beneath the frame rails; purge accumulated condensation until the discharging air is completely dry.
Pump and plumbing servicing:
Remove all discharge caps, suction caps, elbows, and appliances. Clean male and female threads with a wire brush, check rubber swivel gaskets, and apply food-grade machinery grease.
Verify that protective zinc/metal intake mesh strainers are present inside all auxiliary pony intakes.
Cycle and lubricate all mechanical pump valve controls; note excessive friction on linkage rods.
Intake valve servicing (BIV and PIV):
Disassemble the unit from the pump steamer connection. Inspect the valve body for rust, scale, and foreign debris.
Clean and apply food-grade grease to the internal gear mechanism, external threads, and air bleeder valve.
If the large Storz swivel ring binds, wash with warm soapy water and work the swivel until it rotates freely.
Steamer intake strainers:
Inspect the metal intake strainer screens recessed inside the steamer inlets.
These screens serve a dual purpose as galvanic sacrificial anodes to protect the internal cast iron and bronze pump casing from galvanic corrosion.
Strainers naturally oxidize over time; if severe pitting or physical deterioration occurs, obtain an immediate replacement from TSF. The strainer screen must seat tightly inside the inlet barrel to function.

Pump backflushing evolution:
Connect a pressurized supply line from a city fire hydrant directly into an engine discharge port with the fire pump disengaged.
Open each discharge valve and intake valve sequentially to backflush sediment, sand, and scale out through the bottom of the pump body (crosslay plumbing does not require backflushing).
Following backflushing, immediately reconnect to the on-board tank, open the TANK-TO-PUMP valve, engage the fire pump, and activate the primer to ensure the pump body is filled with clean water and reprimed.

Tool and equipment care:
Hand tools: Wash striking surfaces with mild soap and water; dry thoroughly. Coat bare steel tool heads with light water-displacing oil. Apply raw linseed oil to natural wood handles.
Ground ladders: Wash with mild soap and water; lubricate folding roof hook spring assemblies with light oil. Inspect heat sensor labels for dark chemical change (indicating heat exposure) and check ladder compartment slides.
Fire hose nozzles: Immerse nozzle bodies in warm soapy water and cycle internal ball shutoffs, spin teeth, and gallonage selectors. Never apply petroleum-based lubricants or grease to fire hose nozzles.
Hard suction hoses: Wash threads and clean female swivel rings using warm soapy water.
Chain saws: Remove guide bar and cutting chain; blow out clutch drums and air filters using compressed air; flip the bar to balance wear; reassemble and set chain tension.
Pneumatic cutting tools: Clean bodies with soap and water; apply 5 drops of approved air tool oil directly into the tool's air inlet port prior to test operation.
Battery tools: Cycle, inspect, and complete charge cycles on all portable equipment and TICs.
Life safety ropes: Inspect structural core and sheath integrity in accordance with JFRD SOG 419.
Mechanical winches: Mount and test winch controllers at all chassis connection receiver points.
Heavy rescue hand tools: Clean high-lift jacks, wipe steel components with light oil, wash transport chains, and inspect links. Clean come-along ratchets with a dry cloth; sparingly oil gear pawls; never apply oil or lubricants to the wire rope cable; verify that the wire cable dries fully to prevent core corrosion.
Approved Lubricants and Chemical Additives
Application note: All lubricants must be used sparingly; excess grease or oil attracts abrasive road grit and particulate matter, damaging seals and bearings.
Light Oil: Liquid Wrench, WD-40, or comparable water-displacing aerosol lubricants for bare metal surfaces, tool heads, and hinge pins.
Air Tool Oil: Manufacturer-supplied low-viscosity lubricating oil applied directly to pneumatic tool inlets.
Two-Cycle Engine Oil: Premium synthetic oil blended into unleaded gasoline for two-cycle small power engines.
Silicone Spray: High-grade dry spray intended for rollup door tracks and slide-out equipment trays. Leaves no oily residue; do not apply to heavy mechanical rotating gears.
Powdered Graphite: Dry lubricant applied to mechanical pump valve control rods, linkage pivot points, and sliding shafts.
Food-Grade Machinery Grease: The only authorized grease for pump discharge threads, suction connections, and appliance swivels.
Fuel Stabilizer: Chemical additive blended into all freshly acquired unleaded small-equipment fuel cans upon delivery.
Diesel Exhaust Fluid (DEF): Aqueous urea solution conforming to ISO 22241 used in selective catalytic reduction engines to reduce exhaust emissions.
Return-to-Service Checks Following Maintenance
Following major unscheduled or scheduled maintenance at TSF, City Fleet Management, or an outside commercial truck vendor, the engine must undergo functional verification prior to re-entering service.
Extended shop service ( or spanning two shifts):
The on-duty crew must conduct a complete daily apparatus and pump check-off before loading equipment and booking in-service.
Same-day turnaround service (returned within the same shift):
Visually confirm the booster tank is full.
Engage pump and verify governor functions in PSI and RPM modes.
Check air brake system operating pressures and service stopping ability.
Verify that all loose tools, hoses, and equipment are accounted for.
Emergency Scene Positioning and Vehicle Operations
Apparatus positioning dictates operational safety, access, and handline reach at all emergency scenes, conforming to JFRD SOG 402 and SOG 406.
Emergency Medical Incidents
Single-family residential dwellings: Give initial priority positioning to the responding rescue unit (ambulance) to maintain direct access to the stretcher.
On high-speed or congested thoroughfares, angle the engine to act as a barrier to shield patient loading operations.
Multi-family apartments and institutional high-rises:
Where courtyard or driveway access is restricted, position the engine outside the main access gates or away from building canopies, preserving the closest entrance for rescue access.
Roadway and Highway Emergencies
Protect the work zone: Angle the engine across active travel lanes at a angle to physically deflect oncoming traffic away from responders and victims.
Environmental and mechanical hazards: Spot the vehicle uphill and upwind of fuel spills or chemical vapor leaks.
Account for auxiliary vehicle noise and engine exhaust: Position the diesel exhaust discharge away from triage, extrication, and patient treatment locations.
Nighttime roadway operations: Turn off forward-facing headlights when the engine is angled toward oncoming traffic to avoid blinding approaching motorists; deploy retroreflective directional lighting and traffic cones.
Structural Fire Incidents
Single-story residential structures: The first-arriving engine and first-due ladder company position along the structural front.
Spot the engine to pull attack lines from crosslays while preserving the street frontage directly in front of the structure for aerial apparatus outriggers and ladder turntable placement.
Multi-story residential and commercial structures:
Position the engine well clear of building corners.
Leaving the structural corners open enables the aerial ladder company to place its turntable where the aerial ladder can scrub two exterior building faces simultaneously.

Safety Clearances and Roadway Restrictions
Overhead hazards: Never spot an apparatus beneath active overhead electrical transmission lines.
Structural collapse: Maintain a minimum distance from burning exterior masonry walls equivalent to the height of the building.
Hose protection: Keep rubber fire hose away from the hot diesel exhaust tailpipe.
Structural weight limits: Do not drive onto private bridges, residential docks, or private residential driveways unless actively executing emergency suppression operations.
Standing water hazards: Never drive fire apparatus through standing floodwaters deeper than the structural centerline of the vehicle's wheels.
Equipment rack access: Maintain an unobstructed clear zone at the tailboard of at least on the officer's side of the engine to allow the hydraulic ladder storage rack to swing outward and lower ground ladders.

Apparatus Backing Protocols and Spotter Signals
Prior to backing any JFRD apparatus, a designated spotter must be positioned on the engineer's (driver's) side of the apparatus, positioned behind the rear tailboard.
The engineer and spotter must maintain continuous eye-to-eye contact through the driver's side exterior rearview mirror.
If the spotter disappears from the engineer's view for any reason, the vehicle must be brought to an immediate stop.
Standard backing hand signals:
Stop Signal: Both arms raised with forearms vertical and closed fists held facing forward.
Proceed Backing Signal: Both arms raised with open palms bent at the elbows, motioning in an inward beckoning sweep toward the spotter's chest.
Turn Left or Turn Right Signal: Both open hands extended together pointing in the desired direction of tailboard travel.



Fireground Water Sources and Distribution Systems
Municipal Pressurized Water Networks
The primary pressurized water supply for the City of Jacksonville is operated and maintained by JEA, consisting of artesian wells, treatment plants, elevated water towers, and an underground gridded main network.
Gridded loop networks allow pressurized water to flow toward an operating hydrant from multiple directions simultaneously, reducing localized friction loss and stabilizing static pressure.
Municipal water mains range from to in internal diameter, carrying an average static operating pressure of approximately .
Dead-end mains: Found on cul-de-sacs and dead-end roads; they receive water from only one direction, resulting in reduced available volume, elevated friction loss, and rapid residual pressure drops under fire flow conditions.
Independent municipal networks: Atlantic Beach, Neptune Beach, and the Town of Baldwin operate independent municipal water utilities that rely on localized water storage towers and variable static head pressures.

City Fire Hydrants
Standard JEA municipal hydrants are painted chrome yellow.
Thread configurations:
One large central steamer port: National Standard Thread (NST).
Two side discharge ports: National Standard Thread (NST).
Internal barrel connection to the main: intake diameter.
Average municipal static pressure: approximately .
Water main distribution sizing:
Residential distributions: to mains.
Commercial and industrial zones: to mains.
Missing or damaged steamers: If an older hydrant lacks a steamer port, or if the port threads are stripped, high volume can still be achieved by connecting supply hose to one port using an adapter, or by connecting both ports into a siamese appliance.
Private Water Distribution Systems
Private systems serve commercial complexes, industrial plants, schools, and high-density apartments, receiving water through private artesian wells or via a dedicated municipal feed equipped with an inline meter and backflow preventer.
Backflow preventers are sized to match the diameter of the underground main and include check valves that isolate the public water grid from private contamination.
Hydrant identification and colors:
Private hydrants have historically been painted red, though private systems installed or repainted since 2016 are transitioning to solid white.
Standard commercial/apartment private hydrants operate with static pressures of approximately .
High-hazard industrial private systems: Refineries, chemical plants, and port facilities often maintain dedicated private fire pumps producing static main pressures in excess of , designed to supply master streams directly without engine pressure boosting.
NFPA Hydrant Bonnet and Cap Color Classification:
Blue: or greater rated capacity.
Green: rated capacity.
Orange: rated capacity.
Red: Below rated capacity.
Reclaimed water hydrants: Finished in purple; connected to non-potable tertiary sewage/irrigation networks and intended strictly for utility flushing—never connect to purple hydrants for structural fire suppression.
Highway sound barriers: Limited-access highways feature circular access ports cut into concrete sound walls to enable crews to advance supply lines to municipal hydrants located on adjoining neighborhood streets.


Static Water Supplies and Dry Hydrants
Static sources have no head pressure; water must be drafted by lowering pump casing pressure below ambient atmospheric pressure ( at sea level).
Apparatus water booster tank:
Configured above the pump intake manifold to take advantage of positive static head pressure.
Connected via a to internal TANK-TO-PUMP valve.
Flow limitations: Internal tank baffles, piping geometry, and valve design restrict maximum gravity-fed flow from an on-board tank to across all JFRD engines.
Refill restrictions: Booster tanks must be filled solely from clean, potable municipal city fire hydrants; never refill directly from unverified private or raw static sources.
Dry hydrants:
A non-pressurized pipe assembly constructed of schedule 40/80 PVC, ductile iron, or stainless steel connecting to a deep pond, lake, or commercial retention basin, terminating in an exterior NST male connection.
Pre-operational inspection: Verify clear road access, confirm that seasonal water levels cover the submerged strainer by at least , and inspect the internal barrel for trash, dead vegetation, or cracked pipe.

Fire Pump Mechanical Theory, Design, and Components
JFRD frontline engines utilize midship-mounted Waterous centrifugal pumps installed on Pierce chassis, rated at capacities of , , or .
Structural pump assemblies consist of:
Intake manifold: Lower cast bronze/iron manifold distributing intake water directly into the impeller eyes.
Discharge manifold: Upper manifold collecting pressurized water from the volutes for routing to individual discharge valves.
Impeller and volute assembly: One or two bronze impellers mounted on a high-tensile steel shaft.
Split-shaft pump transfer case: Heavy gear casing mounted in-line along the vehicle driveshaft to transfer torque from the diesel engine (Caterpillar C12/C13 or Cummins ISL series) to the pump.

Centrifugal Pump Dynamics
Operational characteristics:
Impellers rotate continuously when engaged; water is spun through centrifugal force from the central eye radially outward across curved vanes into the volute chamber, which widens to convert velocity into static pressure.
Flow-through design: Water under external supply pressure can freely pass through an idle pump body and exit open discharge valves even when the fire pump is disengaged.
Additive incoming pressure: Positive intake pressure adds directly to the pressure generated by the rotating impellers ().
Impeller slippage: Because there is no positive displacement seal between the spinning impeller and the volute casing, discharge lines can be shut down without stalling the engine; however, the ongoing fluid shear rapidly generates friction heat within the water.
Centrifugal pumps cannot move or pump air.
Dry run warning: Centrifugal pumps cannot run dry; mechanical packing seals and bronze clearance rings will overheat and suffer catastrophic binding if operated without water for more than a few minutes.
Pneumatic Pump Shift
A pneumatic three-position toggle switch in the cab controls an air-actuated shift cylinder that slides a heavy internal ring gear within the transfer case.
ROAD: Transmission torque is directed through the rear driveshaft to the drive axle wheels.
PUMP: Driveshaft torque to the rear axle is disengaged; the internal gear engages the pump impeller transmission.
NEUTRAL: Center position; used only for mechanical failures when executing manual pump shifts.
Operating rule: When shifting between ROAD and PUMP, move the toggle smoothly without stopping in NEUTRAL, and pause several seconds before shifting the automatic transmission from neutral to drive.

Pump Testing and Certified Performance (NFPA 1911)
JFRD pumps are factory acceptance tested and certified annually by Underwriters Laboratories (UL) drafting from an open water pit under strict atmospheric conditions.
Performance ratings at draft:
rated capacity at net pump discharge pressure (PDP).
rated capacity at net pump discharge pressure (PDP).
rated capacity at net pump discharge pressure (PDP).
When fed by a positive pressure municipal hydrant or relay engine, a centrifugal pump can easily exceed its tested UL draft capacity.

Single-Stage and Two-Stage Pump Operations
Single-Stage pumps utilize one large double-suction impeller. High pressures require higher engine RPM.
Two-Stage pumps utilize two identical impellers balanced on a common shaft, operated in one of two configurations via a heavy internal transfer valve:
PRESSURE (Series) setting: The internal transfer valve directs the incoming water supply solely to the eye of the first impeller. The first impeller boosts the pressure (e.g., to ) and discharges it directly into the eye of the second impeller, which boosts the pressure again (e.g., to ). Each impeller generates approximately of the final discharge pressure. Used for high-pressure operations such as high-rise standpipes.
VOLUME (Parallel/Capacity) setting: The transfer valve splits the incoming water stream, delivering of the water volume simultaneously to each impeller eye. Both impellers discharge together in parallel into the common discharge manifold. Volume is doubled while pressure remains equal.
Operational transfer valve rules:
Standard position: Two-stage pumps must be operated in VOLUME during normal structural operations, relay pumping, and whenever discharge requirements exceed of the pump's rated capacity.
Attempting to deliver high volume while locked in PRESSURE will choke the pump and restrict total GPM.
The transfer valve is operated by an electric-over-hydraulic actuator with no intermediate positions.
Manual override: If the electrical switch fails, manually turn the mechanical shaft using a socket and ratchet wrench.
Pressure spike warning: To prevent water hammer, reduce engine RPM to idle before changing the transfer valve position; do not drop pressure rapidly if handline crews are inside a fire building.


Intake and Discharge Plumbing, Valves, and Gauges
Intake configuration: All incoming ports connect into an open intake manifold, which is monitored by a single Master Intake Gauge.
Standard layout: Two steamer intakes (one per side), two auxiliary pony intakes, and, on selected engines, a electric front intake.
Hazardous materials engines (E-7 and E-21): Equipped with an additional direct tank fill intake inside the tailboard compartment to route external hydrant or tanker water directly into the tank for inline foam proportioning.
Intake valves:
Ball Intake Valve (BIV): Less restrictive, flows in excess of , and is vacuum-certified for drafting.
Piston Intake Valve (PIV): Flow-restrictive internal piston mechanism; not rated for drafting operations.
Pressure relief valves: Both BIV and PIV contain internal adjustable spring-loaded relief valves preset to open at to vent excess line surges out through bottom dump ports. The pump body also contains an internal intake relief valve factory set at .
Valve handles and slow-close requirements:
Standard handline discharges utilize manual quarter-turn ball valves with mechanical pull handles; when opened, handles can be locked in place by twisting .
Large-diameter valves ( or larger) must utilize slow-operating gear wheels or electric actuators requiring to cycle between fully open and fully closed to mitigate destructive water hammer.
Master compound gauges:
Master Intake Gauge: Registers positive pressure () and vacuum (, inches of mercury).
Master Discharge Gauge: Displays total discharge manifold pressure ().
Individual Line Gauges: Display individual line discharge pressure ().



Auxiliary Priming Systems
The primer is an electrically driven positive displacement rotary pump that evacuates trapped air from the centrifugal pump body, creating a partial vacuum so atmospheric pressure pushes water upward through the hard suction hose.
Standard priming time: to prime through a single steamer hose; up to when drafting through dual steamer connections.
Engines with front intakes have two independent priming pumps that must be actuated simultaneously when utilizing the front intake to draft.
Optimal engine speed for priming is .
Alternative air bleed methods: If the primer fails, partially open the overhead deck gun discharge valve (the highest physical point on the pump plumbing) or slightly open the TANK FILL valve to vent trapped air into the booster tank.

Thermal Auxiliary Cooling Controls
Pump Cooler / Re-circulating Line: Directs a continuous low-volume stream of water () from the pump discharge manifold back into the booster tank. Keeps static water in the pump cool when handlines are closed.
Warning: If operating from a pressurized hydrant or relay supply line, leaving this valve open will eventually overfill and vent water through the booster tank roof vent.
Engine Cooler / Auxiliary Cooler: An internal closed-circuit heat exchanger; cool discharge water is circulated through a closed metal coil within the motor's engine radiator. Prevents engine overheating during stationary pumping operations under heavy loads. Pump water and motor coolant never mix.


Diesel Engine Operating Parameters
Oil Pressure:
Idle speed: minimum of .
Operating pumping speed: .
Coolant Temperature: Fully warmed normal range is .
Electrical System Voltage: .
Transmission Temperature: Normal operating limit is under .
Pressure Control Systems and Electronic Governors
JFRD utilizes microprocessor-based electronic pressure governors—the FRC Pump Boss 200 and Pump Boss Max—integrating throttle control and line pressure relief into a single unit.
The governor controls engine RPM by monitoring signals from a high-speed piezoelectric pressure transducer tapped directly into the pump discharge manifold.


PSI Mode (Pressure Governing)
When set in PSI mode, the governor maintains a constant pump discharge pressure (PDP) regardless of fluctuations in incoming hydrant pressure or changes in flow from opening or closing handline nozzles.
The governor functions like an automotive cruise control, automatically increasing or decreasing engine RPM to maintain the set discharge pressure.
Mandatory PSI mode operations:
Advancing and operating interior attack handlines.
Supplying elevated ladder pipes or portable master monitors.
Supplying commercial automatic sprinkler or standpipe systems.
Automatic cutoff: If discharge pressure requirements exceed , the internal software disables the pressure sensor, requiring the operator to switch to RPM mode.
RPM Mode (Throttle Control)
In RPM mode, the pressure sensor feedback loop is bypassed. The unit functions as a manual electronic throttle, holding engine speed steady at the selected RPM regardless of changes in discharge pressure.
No automatic pressure relief is provided in RPM mode; pressure surges pass directly into hoselines.
Mandatory RPM mode operations:
Initial drafting evolutions from a static water source.
Supplying or operating as an intermediate engine in a relay pumping operation.
Initial charging of large diameter supply hose (LDH).
Operation during an electronic pressure transducer failure or PSI mode malfunction.
Pumping operations where discharge pressures exceed .
Operational Steps for Pressure Governors
The operator must execute four steps in order:
Engage the pump.
Open the TANK TO PUMP valve.
Open the selected discharge valve.
Operate the governor.
Diagnostic error alerts: The pressure sensor must detect positive discharge pressure before the governor will throttle up in PSI mode. If air is trapped in the pump body, the unit locks engine speed at idle and flashes
LO SUPPLYorLO PRESSURE.Factory Presets:
Engine PSI preset: .
Tanker PSI preset: .
RPM preset (both engines and tankers): .
Cavitation safety return: If discharge pressure drops below while running in PSI mode (indicating complete loss of water supply), the governor automatically drops engine speed to idle to protect the pump from cavitation damage.
Low residual alert: If incoming intake residual pressure drops below , the governor may drop engine speed to idle; to maintain flow under tight water supply conditions, shift into RPM mode.
Fire Hose Inventories, Nozzle Dynamics, and Appliances
Minimum Engine Company Hose Inventory
Large Diameter Hose (): (loaded flat, with Storz couplings).
Medium Diameter Hose (): (loaded flat, male coupling forward/on top).
Pre-connected Attack Lines ( or ): Two crosslays.
High-Rise Hose Pack: of true high-rise hose (three sections).
Apartment Hose Pack: of hose with wye and nozzle.
Booster Hose: of rubber-jacketed line on reel.
Wildland Forestry Hose: of woven jacket hose.
Hard Suction Hose: Two sections of suction hose (one heavy-duty, one lightweight drafting).
Soft Intake Hose: One section of flexible soft supply hose.

Large Diameter Hose () Technical Parameters
Couplings: Sexless, quarter-turn Storz locking connections.
Loading guidelines: Hose must be packed flat with couplings staggered across the bed; couplings must never flip over during layout.
Layout rules:
When securing to an intake valve, ensure there is no right-hand twist in the hose body, which can unlock the Storz coupling upon pressurization.
If using a mechanical hose clamp, apply it on the supply side close to a coupling, positioned at least behind the engine tailboard to accommodate line stretch.
Supply lines connected to hydrants on working incidents must be or larger.
Vehicular crossing warnings:
Crossing charged hose is strictly prohibited except in absolute emergencies.
Any emergency crossing must be made at an angle across the hose, never perpendicular, and permitted only for high-clearance vehicles.
Apparatus must never run over a aluminum Storz coupling.
Hydraulic capacity and friction limits:
Flowing creates approximately friction loss per of hose.
The practical maximum flow limit of single supply hose is .
Operating safety boundaries: Never exceed working discharge pressure; maintain a minimum of residual pressure.
Storz Adapters and Pump Fittings
Storz to male adapter: Vacuum-certified adapter utilizing an internal compression gasket; allows connecting hard suction or soft intake hose directly to a Ball Intake Valve (BIV).
female to Storz: Threaded adapter mounted permanently to the pump's Large Diameter Discharge (LDH) port.
female to Storz: Primary municipal hydrant adapter, attached to the exposed end of hose in the hose bed.
female to Storz: Enables connection of supply line to the side discharge ports of a fire hydrant.

Hose, Appliances, and Nozzles
Loading: Packed with the male coupling facing out on top to allow fast deployments.
Smooth Bore Handline Tips ( Nozzle Pressure):
tip: flows .
tip: flows .
tip: flows .
Friction Loss allowance: Add a baseline of friction loss per of hose at a standard flow.
Maximum safe handline flow: represents the maximum safe limit for manual handline handling.
Akron Turbojet Fog Nozzle:
Rated for nozzle pressure.
Selectable gallonage settings: .
Break-apart design: Features an integrated ball-valve playpipe with unscrewable nozzle tip, allowing connection of a line to extend reach.
Warning: Rotating the front protective bumper fully clockwise shuts off water flow regardless of handle bale position.

Attack Hoselines and Nozzles
Akron Turbojet Adjustable Gallonage Nozzle:
Five selectable positions: .
JFRD tactical interior standard: All pre-connected attack lines must be set to either the or position prior to advancing into a structure.
Elevation allowance: Add PDP per building floor above ground level.
Variant operating pressures:
Model (Standard engine issuance):
Pumping requires an initial PDP of .
Pumping requires an initial PDP of .
Kink notice: nozzles are more prone to hose kinking; if lines kink, the engineer can increase PDP by .
Model (HazMat team and specialized engines):
Pumping requires an initial PDP of .
Pumping requires an initial PDP of .

Booster Hose, Hard Suction, and Specialized Packs
Booster reel hose: of rubber hose equipped with a Akron Turbojet nozzle ( at NP). Used for overhaul and small exterior fires. Avoid sustained high-pressure, low-flow pumping to prevent pump overheating.
Hard suction hose: Two sections with connections.
Heavy-duty suction hose: High vacuum/pressure rating; used for drafting or hooking up to a pressurized hydrant.
Lightweight drafting hose: Flexible corrugated hose used strictly for drafting; cannot withstand positive hydrant pressure.
Low-level strainer: Carried on tankers and select engines; painted red with female threads. Features a jet siphon port to draft water down to within a few inches of a portable basin floor.
Soft intake hose: in length, painted red, diameter; capable of flowing in excess of when connected directly to a steamer port.
High-Rise Pack:
Three shoulder bundles containing each ( total) of lightweight hose.
Equipped with a lightweight shutoff bale, mini-stream shaper, and short stack tips ( and a low-flow tip that discharges at NP).
High-Rise accessory bag contents: Inline pressure gauge, gate valve, lightweight elbow, increaser, fog nozzle, two spanners, marking chalk, 6 wooden door wedges, 6 latch straps, 6 glow sticks, pipe wrench, flat and Phillips screwdrivers, Allen wrench set, and an adjustable crescent wrench.
Apartment Pack: Two sections ( total) of hose, a gated wye, and an adjustable nozzle.
Specialized distributor nozzles:
Attic distributor nozzles: Supplied via or pipe lengths from the floor below; discharges an umbrella spray pattern up to in diameter ( for at ; for at ).
Cellar nozzle: Drops through floor openings to flow at with a circular coverage area.


Foam Systems, Agents, and Incident Proportioning
Chemical Foam Agents
Class A Foam: A synthetic hydrocarbon surfactant that reduces the surface tension of water, improving fuel penetration on Class A materials (brush, rubbish, structural overhaul). Educted at , , or . Never use on Class B fires.
Class B Foam: National Foam Universal Green 3% (Alcohol-Resistant Synthetic Foam). Used on both non-polar hydrocarbon fuels (gasoline, diesel) and polar solvents (alcohols, ketones). Educted at an invariant setting across all fuels.
Ethanol warning: Because commercial gasoline contains up to ethanol, Universal Green 3% combined with physical aeration is mandatory to achieve extinguishing expansion ratios.
Dedicated On-Board Apparatus Foam Tanks:
Engines 7 and 21: Equipped with an onboard automatic foam proportioning system and a Universal Green foam tank.
Foam 37: Industrial tanker carrying of Universal Green concentrate.
Crash Trucks at Stations 16 and 56: Carry Mil-Spec AFFF formulated for non-polar aviation fuels.
Chemical incompatibility warning: Mil-Spec AFFF and Universal Green are chemically incompatible and will gel if mixed in tanks or plumbing; however, they may be applied onto the same fire simultaneously through separate delivery devices.
Minimum On-Board Station Inventory Requirements:
Engines: Minimum of three 5-gallon pails () of Class B foam, and one 5-gallon pail () of Class A foam.
Tankers: Minimum of fifteen 5-gallon pails () of Class B foam, and five 5-gallon pails () of Class A foam.
Foam Proportioning Hardware and Hydraulics
Akron Inline Foam Eductor:
Rated for a fixed flow of .
Metering dial adjustable from to .
Hydraulic inlet pressure requirement: Must receive an inlet pressure of exactly to function properly.
If inlet pressure is below , venturi suction draws excess concentrate (yielding an overly rich mix and draining foam supplies prematurely), while line flow drops below .
Nozzle matching and aeration attachments:
The attack nozzle must be set to match the eductor rating: precisely .
The nozzle bale must be opened fully; partially closing the bale creates backpressure that shuts down the venturi draft.
The Akron Foam Aeration Tube must be snapped onto the Turbojet nozzle when discharging Universal Green 3% to achieve mechanical air aspiration and foam blanket expansion.
Distance limits from eductor to nozzle:
When using a fog nozzle: maximum distance of of hose.
When using a fog nozzle: maximum distance of of hose.
High-Capacity Eductors: Engines 7, 21, and select regional pumpers carry the Akron eductor and aerator tube. Handline requirements: hose, an Akron nozzle flowing , with up to of hose and an inlet pressure of .


Application Tactics and Foam Management
Application rule: Foam blankets must remain static to extinguish flammable liquid fires; dike, dam, and divert running liquid pools before application.
Three-dimensional pressurized fuel fires: Foam alone will not suppress gravity-fed or pressurized fuel sprays; combine with dry chemical agent (Purple K) for a dual-agent attack.
Blanket thickness: Apply foam using gentle bounce-off, roll-on, or rain-down methods until a uniform foam blanket covers the entire fuel surface.
Verify vapor suppression: Check perimeter air with a photoionization or combustible gas indicator (LEL meter).
Reapplication: Reapply foam every .
Twenty-five percent drain time: The duration required for of the water to drain from the foam matrix is using seawater, and using fresh municipal water.
Extrication Tools, Ground Ladders, and Portable Extinguishers
Engine Company Ground Ladders
Extension Ladder: Reaches first-story residential roofs, second-story window sills, and second-story residential balconies.
Roof Ladder: Provides roof access on single-story structures, high-ceiling interior reach, and operates on pitched roofs with folding roof hooks deployed.
Folding Attic Ladder: Accesses residential scuttle holes, narrow interior attic openings, and small elevated openings.

Vehicle Extrication Complement
Mechanical tools: High-lift mechanical jack with vehicle lifting attachments; three lengths of alloy rescue chain (, , and ); one J-hook with shackle; one mechanical cable come-along winch; three wooden step chocks; one box of ladder wedge cribbing; and dimensional hardwood cribbing.
Pneumatic air chisel: Provided with three specialized cutting bits: long flat chisel, short flat chisel, and a panel cutter.
Powered hydraulic rescue tools (spreaders, cutters, and telescopic rams): Conventional hydraulic pump models or self-contained battery-powered eDRAULIC units.

Portable Fire Extinguishers
Pressurized Water: capacity; range of ; UL rating .
Carbon Dioxide (): capacity; range of ; UL rating .
Purple K Dry Chemical (PKP - Potassium Bicarbonate):
Standard model: cylinder; range of for ; UL rating .
High-flow model (distinguished by a red handle): cylinder; range of discharged in ; UL rating .
Class D dry powder extinguishers (MET-L-X and LITH-X): Used on combustible metals (magnesium, titanium, lithium); deployed via an external cartridge discharge nozzle.

Advanced Fireground Pumping Operations
Water Supply Estimation and Residual Pressure Drop Methods
Estimating available supply: Record static intake pressure before opening any discharge. Once water is flowing, observe the residual intake pressure. The drop from static to residual determines available line capacity:
Residual drop less than : Can supply three (3) additional lines of equal flow.
Residual drop between and : Can supply two (2) additional lines of equal flow.
Residual drop between and : Can supply one (1) additional line of equal flow.
Residual drop greater than : Water supply is nearly exhausted; only a lower-volume line can be added.
Example: Static pressure reads . A deck gun is charged flowing , dropping residual pressure to . The drop is . Because the drop falls between and , the main can support two additional lines of equal volume ( additional capacity).
Booster tank transition: When switching from tank water directly to a hydrant while lines are flowing, static pressure is bypassed; assume a standard baseline static pressure of .
Pumping Multiple Lines and Pressure Gating
Throttle management: Throttle the fire pump to supply the line requiring the highest pressure.
Pressure gating: Manually gate down the discharge valves supplying lines that require lower pressure, observing the individual line pressure gauge (not the master discharge gauge).
Water flow requirement: Water must be flowing through a line to accurately set and gate discharge pressure; static lines cannot be gated down.
Locking handles: Once dialed in, rotate the mechanical pull handle to lock the internal ball valve in place.
Elevated Master Streams and Ladder Pipes
Supply guidelines:
Position the engine within of the ladder truck turntable.
Initial pump discharge pressure: for all nozzle configurations.
Supply via hose connected directly to the ladder truck's side or rear waterway intake.
Mid-ship aerials have side intakes; rear-mount aerials have a single rear intake.
Flow limits: Standard JFRD ladder truck waterways are limited to flows between (tower ladders excluded). Never exceed supply pressure.

Engine Deck Guns and Ground-Based Master Monitors
Apparatus deck gun: When discharged from the engine carriage, elevate the barrel assembly. If detached and mounted to the portable ground stinger base, never elevate the barrel into an upper extension.
Deck Gun Master Stream Nozzle Hydraulics:
Fog Master Nozzle: nozzle pressure; selectable flows of .
Smooth Bore Master Stream Tips ( nozzle pressure):
: flows .
: flows .
: flows .
: flows .
(Some engines carry an older tip flowing ).
Heavy Ground Monitor Calculations:
Add friction loss for the monitor appliance itself (use for high flows).
Add friction loss per of siamesed dual supply lines.
Example: A ground monitor with a tip ( NP) supplied by of dual siamesed hose:
Mechanical anchoring: Large ground monitors must be secured using a safety chain wrapped around the supply hose loop or pinned to a structural anchor.
Mini-Monitor: Equipped with a single inlet flowing up to at NP. For hose lays longer than , use a siamese with dual lines to limit line friction loss to per .

Hydrant Connection Options
Single Soft Line: Fast, standard deployment.
Full Hydrant Connection: Connect the steamer to a hose, and simultaneously connect a second hose to a side port using a Storz adapter. Increases total available flow by approximately .
Hard Suction Hydrant Hook-Up: Delivers the maximum possible volume from a hydrant. The engine must be spotted within of the barrel. Remove the PIV and connect a heavy-duty suction hose directly to the steamer inlet. Requires a crew of 2 to 3 personnel.
Six-Inch Soft-Intake Hose: Uses a flexible soft intake. Must be connected directly to the pump steamer without a restrictive PIV to flow over .

Relay Pumping Operations
Relay pumping is required whenever an attack engine is located beyond a full bed load () of hose from a water source.
Apparatus roles:
Supply engine: Spots at the hydrant and pumps into the relay.
Relay engines: Positioned every along the supply line.
Attack engine: Positioned at the fire scene supplying handlines.
Relay hydraulic rules:
Pumping produces of friction loss per .
Maintain a minimum of residual pressure at each subsequent relay engine.
Maximum allowable PDP in a relay is .
Minimum allowable intake residual pressure is .
Transfer valve and governor modes in relays:
All supply and intermediate relay engines must operate with two-stage pumps set in VOLUME and governors set in RPM mode.
Only the final attack engine operates in PSI mode to provide automatic pressure relief for handline crews.

Tandem Pumping Operations (Intake-to-Intake)
Tandem pumping provides a secondary attack engine with water from a well-supplied initial attack engine without subjecting the second engine to high discharge pressures.
Setup: An LDH line is connected from an unused intake on the primary attack engine directly into the intake of the secondary attack engine.
The secondary engine receives water at the source hydrant's residual pressure, making line gating manageable without compounding pump pressures.
Both engines must monitor water usage to ensure residual pressure on both pumps remains above to prevent cavitation.

Sprinkler and Standpipe Operations
Spotting: Position the engine within of the Fire Department Connection (FDC).
Commercial Sprinkler Systems:
Maintain a continuous pump discharge pressure of .
Flow verification: To confirm water is flowing through the system, slowly gate down the discharge valve slightly; if the needle drops below current pressure, water is flowing through open heads. If pressure remains static, heads have not fused.
Standpipe Systems:
A Remote Pump Operator (RPO) equipped with an inline gate valve and pressure gauge must manage the outlet valve on the floor below the fire floor.
High-Rise Relay Supply: On tall high-rise structures, position two engines in series at the FDC. The first engine pumps into the intake of the second engine, which boosts the pressure to achieve the high discharge pressure required for upper stories.
FDC Troubleshooting:
Frozen swivel: Thread a double male into the swivel, followed by a double female adapter.
Blocked or damaged FDC: Connect a line directly into a first-floor standpipe discharge outlet inside the stairwell using a double female adapter and gate valve, and open the standpipe valve fully (will not work on pressure-reducing PRV valves).
Wall hydrants: Wall hydrants on building exteriors are designed for system flow testing; use them to supply the system only as a last resort.


Drafting Operations
Theoretical vs. practical lift:
Theoretical maximum lift: .
NFPA certified pump rating: of lift.
Maximum practical fireground lift: (measured vertically from water surface to the center of the steamer inlet).
If the vertical lift exceeds , pump capacity is reduced.
Strainer placement: Submerge the strainer with at least of water above it to prevent whirlpool vortex formation, and maintain at least of clearance off the muddy bottom. Tie off the hose with rope or support it on a roof ladder.
Plumbing configurations:
Remove the PIV and connect hard suction hose directly to the steamer inlet; do not draft through a PIV due to air leaks and flow restrictions. The BIV is vacuum-certified and can remain on the intake.
To achieve full capacity on pumps, both side steamer intakes must be connected to hard suction.
Drafting sequence:
Connect all hard suction joints wrench-tight; secure strainer.
Set two-stage pump transfer valve to VOLUME.
Set governor mode to RPM; increase engine speed to .
Actuate the primer until steady pressure registers above on the master discharge gauge.
Slowly crack the discharge line to start water moving; switch governor to PSI mode once lines are flowing steadily.

International Shore Connection
Marine vessels operating at the Port of Jacksonville utilize a standardized bolt-on adapter flange conforming to international maritime standards.
Mount the flange to the shipboard standpipe riser, bolt the halves together with the supplied gasket, connect a supply line, and pump according to the ship engineer's specifications.

Water Tanker (Shuttle) Apparatus and Rural Water Logistics
JFRD automatically dispatches three (3) tankers to all reported structural fires, regardless of whether hydrants are present in the district.
Tanker Apparatus Specifications
Chassis and pump: Pierce commercial chassis with single-stage Hale or Waterous centrifugal pumps.
Water tank: baffled and vented aluminum/poly tank.
Tank-to-pump valve: diameter slow-operating handwheel valve, allowing tankers to discharge up to their full rating directly from the tank.
Pump engagement: Power Take-Off (PTO) system. Shifting the transmission into DRIVE automatically disengages the PTO pump.
Discharge and dump hardware:
Rear square quick-dump valve with a directional swiveling chute, discharging in .
Equipped with a PIV intake, LDH discharge, two pre-connected lines, and a deck gun.
Rural equipment inventory: Portable folding water basin ( capacity) with ground tarp, low-level strainer with jet siphon, and two sections of supply hose.


Tanker Shuttle Logistics and Setup
Initial tanker deployment:
Deploy the ground protective tarp adjacent to the attack engine.
Unfold and set up the portable tanker basin, and drop the low-level strainer.
Align the rear dump chute, dump the load into the basin, and proceed to the fill site.
Positioning: Position the basin and tanker to block only a single traffic lane, leaving the passing lane clear for shuttle turnaround.
Refill engine operations at the fill site:
A dedicated engine company spots at a water source (hydrant or static water draft).
Connect two or supply lines to the tanker's rear direct-fill connections.
Refill pump pressure: Pump at an inlet pressure of ; higher pressures can damage the internal baffles and tank walls. Refill time is approximately .
Water delivery rate calculation:
Based on an average 10-minute round trip ( travel, refill, and dump), a single tanker sustains a continuous fire flow of only . Adding a second tanker increases the delivery rate to .

Multi-Basin Water Transfer (Jet Siphon)
When multiple basins are used, transfer water between them using a jet siphon.
Connect a supply line from a pumper discharge to the jet siphon connection on the low-level strainer.
Connect a section of hard suction or lightweight hose to the strainer outlet, extending it into the primary drafting basin.
Pumping the jet siphon at transfers water at rates up to .
Modified Tanker Shuttle (Direct Siamese Operation)
When narrow roads or long driveways prevent basin deployment, use a modified direct shuttle.
The attack engine lays an uncharged supply line into the scene, terminating at the street in a siamese.
Arriving tankers connect directly to the siamese and pump their tank water directly into the attack engine in an alternating relay, departing for the fill site as soon as they run dry.
Off-Road Mechanical Traction Systems
Tankers feature dash-mounted rocker switches controlling four-wheel drive and driver-controlled differential locks.
Engage differential locks before leaving paved roads to prevent getting stuck in loose sand or mud.

Troubleshooting Fire Pump and Engine Malfunctions
Thermal Overheating
Fire pump overheating:
Caused by continuous churning of water inside the pump casing when handlines are closed.
Mitigation: Open the PUMP COOLER/recirculator line to return hot water to the booster tank; partially crack the TANK FILL valve; or charge the booster line and direct the nozzle into the water tank fill opening.
Engine motor overheating:
Open the ENGINE COOLER valve on the pump panel to circulate water through the internal radiator heat exchanger.
If engine temperature continues to rise, charge the booster line and direct a wide fog spray through the front grille directly onto the radiator fins.
Post-drafting wash: If raw water from a pond or river is sprayed onto the radiator, thoroughly wash the radiator, engine block, and cab undercarriage with fresh water and soap to prevent galvanic corrosion.
Pump Shift Failure and Disabled Engine "Pump-Through"
Manual pump shift override: If the in-cab pneumatic shift system loses air or fails, engage the pump using the manual shift handle on the pump panel (see Appendix E).
Pump-Through operation for a disabled engine: If an attack engine suffers a complete mechanical pump or motor failure while lines are operating inside a structure, a secondary engine can pump water through the disabled engine's discharge manifold (see Appendix H).

Failure to Build Pressure and Loss of Prime
The most common cause of failure to build discharge pressure is trapped air inside the pump casing.
Actuate the primer until steady water discharges and the master discharge gauge shows positive pressure.
If the electronic governor prevents throttling up in PSI mode, switch to RPM mode and manually increase engine speed to force trapped air through the discharges.
If priming fails while drafting, inspect for open drain valves, loose suction hose couplings, open air bleeders, and air pockets along the hard suction hose. Check the discharge pipe on the internal intake relief valve; cap it with a cap if the internal seat is leaking air.
Air displacement trick: To displace stubborn air while priming, open the TANK-TO-PUMP valve for a few seconds while the primer is running to flood the pump body with tank water, then close it.
Cavitation Dynamics
Cavitation occurs when the pump attempts to discharge more water than it receives at the intake.
Mechanical phenomenon: As intake pressure drops toward absolute zero, pressure at the impeller eye falls below the vapor pressure of the liquid, causing water to boil and form vapor bubbles. As these bubbles travel into the high-pressure zones of the volute, they collapse violently against the metal, eroding the bronze impellers and producing a distinct sound like rocks or gravel circulating in the pump.
Diagnostic indications: The earliest signs of cavitation are fluctuating discharge pressure gauges and an engine that revs without a corresponding increase in water pressure.
Preventive limit: Maintain at least residual intake pressure at all times.

Critical Velocity
Critical velocity is the maximum speed at which water can flow through a given diameter of fire hose before laminar flow breaks down into severe turbulence.
Once critical velocity is reached, increasing pump discharge pressure will not increase flow; instead, turbulence causes stream reach to degrade.
Corrective actions: Reduce engine RPM; step down the nozzle tip size or flow setting; or advance a larger diameter hose line (e.g., replace a line with a line).
Annual Service Testing Protocols for Fire Hose
Mandatory testing period: All fire hose must undergo annual service testing between March 15 and April 15 in accordance with NFPA standards.
Testing pressures and duration:
Large Diameter Hose ( and ): Test at continuously for .
Small and Medium Diameter Hose (, , , and ): Test at continuously for .
Layout and testing safety:
Lay hose out on a dry, slight incline; connect test nozzles to the far ends to bleed air.
Mark the hose jacket at the back of each coupling with a pen to detect coupling slippage.
Fill the lines, bleed all air, and slowly raise pressure to the test level.
Safety gate closure: Once up to test pressure, gate the discharge valve down almost completely closed. This traps static pressure in the test layout while limiting the volume released if a hose ruptures.
Safety perimeter: Personnel must stay clear of the test area while hose is pressurized; never inspect couplings closely while under test pressure.
Post-test inspection: Inspect the line markings for coupling slippage, weeping, or jacket damage. Tag any damaged or failed sections and route them to TSF for repair or disposal.
Reference Quick Sheets, Hydraulic Theory, and Specialized Appendices
Appendix A: Diesel Motor Regeneration (DPF and SCR)
Diesel Particulate Filter (DPF) traps particulate soot; Selective Catalytic Reduction (SCR) treats exhaust with DEF to convert harmful into nitrogen and water vapor.
Automatic Regeneration: Occurs automatically while driving or pumping when exhaust temperatures and conditions permit. HEST lamp illuminates when exhaust temperatures exceed .
Automatic regeneration during pumping requires:
Engine speed between .
Virtual transmission output speed greater than .
Parking brake set, pump engaged, and transmission selector in DRIVE.
Regeneration controls and lamps:
REGEN INHIBIT switch: Inhibits or aborts a regeneration cycle (used when parked over dry grass or near flammables).
DPF REGEN switch: Manually initiates a parked regeneration cycle.
Flashing DPF lamp and illuminated CHECK ENGINE lamp indicate an urgent need for manual regeneration.
Illuminated red STOP ENGINE lamp indicates critical soot clogging; vehicle must be shut down immediately.




Appendix B: JFRD Engine Specifications (2014 and Newer)
Fire pump: Midship-mounted two-stage Waterous centrifugal pump.
Rated capacity: .
Water booster tank: .
Pressure governor: FRC Pump Boss electronic governor.
Appendix C: Engine Company Color Identification Markings
E-1: Red, White, Red
E-2: Red, White, Blue
SQ-4: Red
E-5: White
E-7: Silver
E-9: Green, White
E-10: Yellow, Red
E-11: Green
SQ-12: Yellow
E-13: Silver, Blue
SQ-14: White, Black
E-16: Yellow, Black
E-17: Black
E-18: Blue, Yellow
E-19: Green, Blue
E-20: Red, White, Red
E-21: Green, White, Green
E-22: Green, Silver
E-23: Green, Yellow, Green
E-24: White, Black, White
E-25: Yellow, Black, Yellow
E-26: White, Silver
E-27: Green, Blue, Green
E-28: Black, White, Black
E-29: Red, White
E-30: Silver, Yellow
E-31: Red, Silver, Red
E-32: Red, Blue, Red
E-33: Blue, Silver, Red
E-34: White, Blue
E-35: Yellow, Black, White
E-36: Blue, Yellow, Blue
SQ-37: Orange
ST-38: Green, Red
ST-39: Red, Silver
E-40: Green, Red, Green
E-41: Red, Black, Red
E-42: Blue, White, Blue
E-43: Yellow, Orange, Yellow
E-44: Orange, Yellow, Orange
E-45: Blue, Silver, Blue
E-46: Blue, Red
E-47: Black, Red
E-48: Green, Black
E-49: Green, Yellow
E-50: White, Green, White
E-51: White, Yellow, White
E-52: Black, Yellow, Black
E-53: Orange, Blue
E-54: Black, Silver
E-55: Blue, White, Blue
CR-56: Garnet, Gold, Garnet
E-57: Orange, White
E-58: Red, Black, Green
E-59: Black, Gold, Teal
E-60: Red, Green, Red
E-61: Black, Red, Black
E-62: Yellow, Black, Blue
SQ-63: Green, White, Orange
E-64: Teal
E-65: Burgundy
E-71: Orange, Blue, Orange
E-72: Blue
E-73: Yellow, Blue, Yellow
E-74: Orange, Black
E-75: Blue, Green, Blue
E-76: White, Orange, White
Tankers (TA): Garnet, Blue
Appendix D: Hydraulic Theory and Mathematical Formulas
Fluid Head and Elevation Pressures:
A column of water exerts at its base.
will lift a vertical water column .
Field head pressure calculation: Elevation loss equals per story ( average height), excluding the first (ground) floor.
Theoretical Friction Loss Coefficient Method:
Where .
Where .
Hose Coefficients ():
Hose:
Hose:
Hose:
Hose:
Hose:
Total Pump Discharge Pressure Equation:
Where .
Where .
Where .
Where .
The Minus 10 Field Rule for Hose:
To find friction loss in of hose, drop the last zero from the line's GPM and subtract 10.
Example: For a flow of , drop the zero () and subtract 10: loss per .
Smooth Bore Discharge Formula:
Where .
Where .
Appendix E: Manual Pump Shift Evolution
Step 1: Shift transmission to NEUTRAL (N); set parking brake.
Step 2: Move the in-cab pneumatic pump shift lever to NEUTRAL (center).
Step 3: Go to the pump panel and pull the manual emergency pump shift T-handle firmly outward.
Step 4: Return to the cab and move the pneumatic shift switch to PUMP.
Step 5: Shift transmission to DRIVE (D); confirm lock-up (speedometer registers , transmission shows 44).
Disengagement sequence: Shift transmission to NEUTRAL, place in-cab switch to NEUTRAL, and push the manual pump panel T-handle all the way back in.
Appendix F: Engine Company Fireground Skills Checklists
Skill 1: Pumping a pre-connected handline from booster tank.
Skill 2: Hand-laying supply line to hydrant.
Skill 3: Establishing engine or tanker secondary supply.
Skill 4: Transitioning from tank water to pressurized hydrant supply.
Skill 5: Pumping attack lines while simultaneously supplying water to another apparatus.
Skill 6: Drafting from a portable tanker basin.
Skill 7: Supplying elevated ladder pipes.
Skill 8: Deploying ground-based master stream monitors.
Skill 9: Relay pumping from a hydrant (hooking up).
Skill 10: Pumping multiple lines at variable pressures.
Skill 11: Placing an inline foam eductor line into operation.
Appendix G: TurboDraft Alternative Water Supply Operations
The TurboDraft eductor enables an engine to draft from static open water sources up to away and up to of vertical lift.
Operation: Connect a high-pressure supply line and a return line to the unit; submerge the appliance; pump into the line; the venturi return stream supplies water back into the engine intake.

Appendix H: Disabled Engine "Pump-Through" Procedure
If an attack engine's pump or motor fails during structural operations, a secondary pumper can pump water through the disabled engine's discharge plumbing.
Supply lines connected: Connect a hose from the second engine's LDH discharge into the disabled engine's LDH discharge port. Open both valves. Connect a second line from the disabled engine's steamer intake into the second engine's intake.
The second engine charges the line to an initial PDP of , pressurizing the disabled engine's discharge manifold and restoring flow to the attack lines.
Appendix I: Wildland Brush Trucks and Skid Units
Tank and pump hardware: 1-ton pickup chassis (Ford F350, Chevy/Ram 3500) carrying a water tank, a Class A foam cell, and an engine-driven pump flowing at .
Booster reel: of hose flowing approximately at PDP.
Proportioning systems:
Hale pump with Foam-Flo proportioner (Briggs & Stratton engine).
CET pump with Scotty around-the-pump proportioner (Honda engine).
Standard proportioning rate: (one-quarter of one percent).
Field batch mixing: If the automatic proportioner is inoperative, pour one cup of Class A foam concentrate directly into the booster tank to achieve the proper wetting ratio.


Appendix J: Air Brake Diagnostic Inspection Guide
Pre-trip pressure: Primary and secondary systems must both exceed before moving.
Compressor cut-out and cut-in tests: Governor cuts out the compressor at approximately , and cuts back in at approximately .
Low pressure warning: Warning light and audible buzzer must activate before air pressure falls below .
Automatic spring brake deployment: Mechanical parking brake valve pop-up must activate before pressure drops below .
Pressure buildup rate: Air pressure must climb from within at high idle.
Air leakage rate limits: Pressure drop with brakes released must not exceed in 1 minute for single vehicles. Under full service brake pedal application ( applied), system loss must not exceed in 1 minute.
Appendix K: Flammable Liquids Foam Reference Matrix
Spill application standard: Maintain a minimum continuous foam blanket over the entire fuel surface.
Calculated application formula:
Highway cargo tanker standard: Assumes a standard surface area of , requiring a minimum finished foam fire flow of .
Foam concentrate required:

Appendix L: The Double Drop Street Method for Water Supply Estimation
Application restrictions: Used only when supplied by an active municipal hydrant on a or larger main using or supply hose no longer than .
Assumed line flows: Calculations assume a conservative maximum flow of for an initial handline, and for a handline.
Calculation steps:
Record static intake pressure.
Charge the initial line; set pressure and flow.
Calculate the residual pressure drop.
Double the residual drop ().
Divide the remaining residual pressure by this doubled value to determine remaining flow increments.
Example: Static pressure reads . An initial line is charged, dropping residual pressure to ( drop).
For any additional lines added after the first, do not double the drop; use the actual pressure drop.
Appendix M: Standard Friction Loss and Pump Discharge Pressure Guides
Friction Loss per in JFRD Spec Hose ( internal diameter):
At :
At :
At :
At :
At :
Friction Loss per in JFRD Spec Hose:
At :
At :
At :
At :
At :
At :
Friction Loss per in Pro-Flow Supply Hose:
At :
At :
At :
At :
At :
At :
At :
At :