Governed by BS 7671.
Principle: A circuit must automatically disconnect if current exceeds its design limit (over-current) to reduce:
BS 7671 stipulates maximum disconnection times that protective devices must achieve.
Earthing System | Circuit Rating | Maximum Disconnection Time |
---|---|---|
TN (earthing via conductor in supply cable) | \le 63\ \text{A} | 0.4\ \text{s} |
TT (earthing via local earth electrode) | \le 63\ \text{A} | 0.2\ \text{s} |
Distribution / >63 A – TN | — | \le 5\ \text{s} |
Distribution / >63 A – TT | — | \le 1\ \text{s} |
Protective devices used: