Study Notes on High Voltage and Current Measurement Techniques
Measurement of High Voltages and Currents
Importance of High Voltage and Current Measurement
- Essential in industrial testing and research laboratories.
- Accuracy in measurement ensures safety for personnel and equipment.
- Protection against overvoltages and induced voltages due to stray coupling is necessary.
- Device location and layout are crucial for effective measurement.
Classification of High Voltage Measurement Devices
High voltage measuring devices differ significantly from low voltage devices due to:
- Calibration needs for high voltage devices (device ranges must not be extrapolated linearly).
- Need to minimize electromagnetic interference in impulse voltage and current measurements.
Types of High Voltage Measurement Devices
Table 7.1 - High Voltage Measurement Techniques
- (a) d.c. voltages
- (i) Series resistance microammeter.
- (ii) Resistance potential divider.
- (iii) Generating voltmeters.
- (iv) Sphere and other spark gaps.
- (b) a.c. voltages (power frequency)
- (i) Series impedance ammeters.
- (ii) Potential dividers (resistance or capacitance type).
- (iii) Potential transformers (electromagnetic or capacitance voltage transformer).
- (iv) Electrostatic voltmeters.
- (v) Sphere gaps.
- (c) High frequency a.c., impulse voltages, and rapidly changing voltages
- (i) Potential dividers with a cathode ray oscillograph.
- (ii) Peak voltmeters.
- (iii) Sphere gaps.
Measurement of High Direct Current (d.c.) Voltages
Techniques Used
General method involves extending meter range with a large series resistance.
Typical net current through the meter is limited to one to ten microamperes for full-scale deflection.
Challenges with High d.c. Voltages
At very high voltages (1000 kV or more), challenges arise due to:
- Large power dissipation.
- Leakage currents.
- Limitations on voltage stress per unit length.
- Resistance changes due to temperature variations.
Solution Techniques
Resistance Potential Divider with Electrostatic Voltmeter
- Provides better performance for high precision needs, but still suffers drawbacks of power dissipation and current drain.
- Spark gaps, such as sphere gaps, can be used for peak voltage measurement, affected by atmospheric conditions.
Measurement Technique Details
7.1.1 High Ohmic Series Resistance with Microammeter
High voltage measured by connecting a high resistance (hundreds of megaohms) in series with a microammeter.
Voltage calculated via , where:
- V is the voltage of the source.
- I is the current through the calibrated resistance R.Protective device used across meter (e.g., paper gap, neon glow tube) ensures protection against high voltages.
Protective Resistance Setup
Value of series resistance R designed to allow a current of 1-10 microamperes for full-scale deflection.
Constructed from multiple wire wound resistors in series to avoid ground flashovers.
Corona-free terminations prevent discharge issues, using materials with low temperature coefficients.
Limitations of Series Resistance Design
Significant challenges include:
- Power dissipation and source loading.
- Temperature effects and long-term stability.
- Voltage dependence of resistive elements.
- Sensitivity to mechanical stresses.
7.1.2 Resistance Potential Dividers for d.c. Voltages
High accuracy with designs eliminating temperature and voltage influences.
Voltage measured using the formula:
where V2 is the voltage across the lower arm R2.
Protecting Against Transient Voltages
Voltage controlling capacitors connected across elements mitigate transient issues that may arise during voltage fluctuations.
Additional Measurement Techniques
7.1.3 Generating Voltmeters
Operate under principles that isolate source loading, especially with generators.
Principle of Operation
Charge stored in capacitor: , where C is capacitance, V is voltage.
Varying capacitance results in current: .
The current for varying capacitance described as sinusoidal yields RMS value:
.
Practical Implementations
Design of generating voltmeters incorporates rotating mechanisms driven by synchronous motors; can measure a.c. voltages under specific speed conditions.
Measurement of High a.c. and Impulse Voltages
Techniques Used
Commonly utilize potential dividers, transformers, and electrostatic voltmeters, with designs tailored for insulation and source loading.
Key Instruments in High a.c. Measurement
Peak Voltmeters and Sphere Gaps
- Specifically utilized for capturing peak values and reference during calibration.
Series Impedance Voltmeters
Employ resistive or reactive impedance for power frequency a.c. measurements, with capacitance preferred to minimize losses.
Series Capacitance Voltmeters
Designed to substitute for resistors to negate thermal variations and boost accuracy in high a.c. measurements.
Capacitance Potential Dividers
High accuracy employed in measurement while addressing harmonics through additional capacitors for linearization.
Capacitive Voltage Transformers (CVTs)
Used in power systems; configured to measure various voltages while providing isolation between high and low voltage terminals.
Potentials and Capacitive Devices
Potential Transformers (PT)
- Old devices offering simplified construction, but can experience ratio and phase angle errors, suffering from harmonic and transient limitations.
Electrostatic Voltmeters
Operate within electrostatic fields, leveraging the attractive forces between electrodes, useful for accurate measurement of high voltage parameters.
Spark Gaps for Measurement of High Voltages
Construction and Functionality
Uniform field spark gaps provide reliable measurements of peak voltage based upon known sparkover voltage parameters.
Sphere Gaps
Spheres are generally made from conductive materials (copper, aluminum) with engineered dimensions.
Peak values recorded are dependent on spacing and surrounding conditions.
Operational Considerations
Precise arrangement of spheres can affect results; configurations can either be vertical or horizontal to enhance measurement reliability.
Sparkover Voltage Calibration
Measurements involve finding average sparkover values across multiple trials, recommending preliminary measurements before critical ones.
Capacitance and Environment Effects
The sphere gap measurements involve accounting for nearby earthed objects, temperature, humidity, and the effects of irradiation on voltage readings.
Worked Examples
Example 7.1: Generating Voltmeter Design
Capacitance calculated based on designed range from 20 kV to 200 kV while ensuring operational stability under specified current readings.
Conclusion of Calculations
Generated capacitance for the voltmeter deduced to meet operational parameters effectively, suggesting an ideal capacitor configuration.
Example 7.2: Peak Reading Voltmeter Configuration
Design criteria established based on specific voltage requirements, employing potential divider ratios to ascertain meter specifics for usability up to specified peak voltages.