unit 50

Typically, on mini-split systems the line set going to the outdoor unit carries ________ pressure, ________ temperature saturated liquid and vapor mix. The line going back to the outdoor unit carries ________ pressure superheated vapor.

 

high, high, low

 

low, high, high

Correct Answer

 

low, low, low

 

low, high, low

 

0 / 1 pts

Which of the following mini-split system indoor units requires a condensate pump because gravity condensate draining is never feasible for this type of installation?

 

Wall mount

Correct Answer

 

Ceiling suspended

 

Floor mount

 

All of these

 

0 / 1 pts

Variable refrigerant flow systems use:

 

Inverter driven systems and thermostatic expansion valves.

Correct Answer

 

Inverter driven systems and electronic expansion valves.

 

Scroll compressors and electronic expansion valves.

 

Scroll compressors and thermostatic expansion valves.

 

0 / 1 pts

Manufacturers recommend pressurizing VRF piping to ________ with nitrogen and performing a 24 hour standing leak test.

 

200 - 300 psig

 

300 - 400 psig

 

400 - 500 psig

Correct Answer

 

500 - 600 psig

 

0 / 1 pts

Standard wyes and tees are not used in VRF refrigeration networks as they introduce turbulence and do not ensure even flow to both branches.

Correct Answer

 

True

 

False

 

A type system that allows simultaneous heating and cooling to different parts of a building is the:

 

Multisplit system.

 

Heat pump variable refrigerant flow system.

Correct Answer

 

Heat recovery system.

 

All of these.

 

0 / 1 pts

Designing a heating and cooling system to accommodate load shifts:

 

Allows buildings to operate with less installed capacity and still meet the demand.

 

Improves comfort.

 

Improves efficiency.

Correct Answer

 

All of these.

 

UnansweredQuestion 8

0 / 1 pts

Some codes limit refrigerant 410A to 25 pounds per 1000 cubic feet of space. This works out to 40 cubic feet per pound of refrigerant. The limit is lower, ________ cubic feet per pound of refrigerant for 24 hour care facilities such as hospitals and nursing homes.

 

15

Correct Answer

 

20

 

30

 

50

 

UnansweredQuestion 9

0 / 1 pts

Most multisplit units require connection to:

 

All of the circuits.

 

At least four indoor units, but not all of the circuits have to be used.

 

At least three indoor units, but not all of the circuits have to be used.

Correct Answer

 

At least two indoor units, but not all of the circuits have to be used.

 

UnansweredQuestion 10

0 / 1 pts

Mechanical codes limit the amount of refrigerant a system can contain if it is located in an occupied space. Because VRF systems are connected to one large refrigerant network that would release the entire charge in case of a leak, some codes limit refrigerant 410A charge to ________ pounds per 1,000 cubic feet of space.

 

15

Correct Answer

 

25

 

30

 

50

 

UnansweredQuestion 11

0 / 1 pts

Which of the following is NOT a type of indoor unit used on mini-split systems?

 

Wall mount

 

Ceiling suspended

 

Floor mount

Correct Answer

 

Crawl space

 

UnansweredQuestion 12

0 / 1 pts

The typical number of wires connecting the outdoor unit to the indoor unit of a mini-split system is:

 

Two.

 

Three.

Correct Answer

 

Four.

 

Any of these.

 

UnansweredQuestion 13

0 / 1 pts

Flare connections are used on mini-split systems to avoid oxidation in the lines and also to avoid heating and destroying the sensitive electronic expansion valves use in the outdoor units.

Correct Answer

 

True

 

False

 

UnansweredQuestion 14

0 / 1 pts

What type of refrigerant line connections are used on multisplit systems?

 

Multiple connections on the outdoor unit

 

Single set of connections on the outdoor unit

 

A refrigeration network similar to a heat recovery system

Correct Answer

 

Both Multiple connections on the outdoor unit and Single set of connections on the outdoor unit could be used.

 

UnansweredQuestion 15

0 / 1 pts

The wiring connection between the outdoor and indoor unit typically has four wires. One wire carries power, a second wire carries low voltage communication while a third wire carries both line voltage power and low voltage communication. A fourth wire is utilized for ground.

Correct Answer

 

True

 

False

 

UnansweredQuestion 16

0 / 1 pts

Designing a heating and cooling system to accommodate load shifts can allow buildings to operate with ________ capacity to meet the demand.

 

more installed

Correct Answer

 

less installed

 

UnansweredQuestion 17

0 / 1 pts

It is possible for one multi-split indoor unit to heat while another cools.

 

True

Correct Answer

 

False

 

UnansweredQuestion 18

0 / 1 pts

Multisplit manufacturer's installation instructions will specify the maximum total installed piping length which can be supported by the charge shipped in the unit. If additional piping is installed the only correct way to charge the system is to:

 

Charge the system to the required subcooling.

 

Charge the system to the required superheat.

Correct Answer

 

Add the specified amount of refrigerant for each additional foot of refrigerant line.

 

None of these.

 

UnansweredQuestion 19

0 / 1 pts

The smallest capacity VRF outdoor units available generally equal or exceed the largest multisplit units available.

Correct Answer

 

True

 

False

 

UnansweredQuestion 20

0 / 1 pts

VRF systems are commercial systems. The outdoor units are normally designed to operate on ________ phase power and the indoor units on ________ phase power.

 

single, single

 

single, three

 

three, three

Correct Answer

 

three, single

 

UnansweredQuestion 21

0 / 1 pts

When more than one indoor unit is connected an individual branch selection box on a heat recovery system:

Correct Answer

 

Each indoor unit must operate in the same mode.

 

One indoor unit may operate in the heat mode and other(s) may operate in the cooling mode.

 

UnansweredQuestion 22

0 / 1 pts

Mini-split condensate pumps come in three basic varieties: two-piece pumps, monoblock pumps, and:

 

Multisplit pumps.

 

Peristaltic pumps.

 

Sump pumps.

Correct Answer

 

Reservoir pumps.

 

UnansweredQuestion 23

0 / 1 pts

When factory supplied branch joints are not available for VRF refrigerant piping it is permissible to use standard tees or wyes.

 

True

Correct Answer

 

False

 

UnansweredQuestion 24

0 / 1 pts

Like many multisplit units, variable refrigerant flow (VRF) systems use ________ compressors and electronic expansion valves to change the volume of refrigerant being circulated in the system.

 

scroll

 

reciprocating

 

screw

Correct Answer

 

inverter driven

 

UnansweredQuestion 25

0 / 1 pts

It is important when wiring multisplit systems that the indoor units connect to their corresponding A, B, C, or D terminal block on the outdoor unit.

Correct Answer

 

True

 

False

 

UnansweredQuestion 26

0 / 1 pts

Which system allows simultaneous heating or cooling?

 

Mini-split system

 

Multisplit system

Correct Answer

 

Heat recovery system

 

UnansweredQuestion 27

0 / 1 pts

While multisplit units are limited to a single outdoor unit, large VRF systems can combine as many as ________ outdoor units manifolded together to increase overall system capacity.

 

two

Correct Answer

 

three

 

four

 

five

 

UnansweredQuestion 28

0 / 1 pts

Power for the mini-split system is supplied:

Correct Answer

 

To the outdoor unit which powers the indoor unit.

 

To the indoor unit which powers the outdoor unit.

 

To the indoor and outdoor with their own separate dedicated wiring and circuit protection.

 

Any of these methods may be used.

 

UnansweredQuestion 29

0 / 1 pts

On heat recovery systems:

 

It is required that all indoor units be in cooling mode.

 

It is required that all indoor units be in heating mode.

Correct Answer

 

One indoor unit can be in heating mode while others are in cooling mode at the same time.

 

Both It is required that all indoor units be in cooling mode and It is required that all indoor units be in heating mode.

 

UnansweredQuestion 30

0 / 1 pts

Some multisplit systems operate all indoor units from one control while others allow individual indoor units to operate from their own controls and set points.

Correct Answer

 

True

 

False

 

UnansweredQuestion 31

0 / 1 pts

The refrigerant lines for single zone mini-split air conditioners are usually connected by:

 

SAE compression fittings.

 

Brazed connections.

Correct Answer

 

Flare fittings.

 

Reflok fittings.

 

UnansweredQuestion 32

0 / 1 pts

To avoid the creation of oxides in the refrigeration lines of mini-split systems, the lines are assembled:

 

By brazing the connections while flowing nitrogen through the lines.

 

Using Reflok fittings.

Correct Answer

 

Using heavy-walled flare fittings.

 

Using standard flare fittings.

 

UnansweredQuestion 33

0 / 1 pts

VRF systems use a refrigeration network of:

 

Wyes and tees.

Correct Answer

 

Headers and branch joints.

 

Both Wyes and tees and Headers and branch joints.

 

None of these.

 

UnansweredQuestion 34

0 / 1 pts

On mini-split systems both refrigerant lines must be insulated because they are both:

 

Low pressure and low temperature in the heating mode.

Correct Answer

 

Low pressure and low temperature in the cooling mode.

 

Low pressure and low temperature in the heating and cooling mode.

 

Low pressure and high temperature in the cooling mode.

 

UnansweredQuestion 35

0 / 1 pts

Most systems can operate with up to ________ feet of lines and a maximum of ________ feet vertical distance between the indoor and outdoor units.

Correct Answer

 

50, 10

 

75, 15

 

90, 20

 

100, 30

 

UnansweredQuestion 36

0 / 1 pts

Branch selectors are boxes in heat recovery VRF systems that allow:

Correct Answer

 

One refrigerant line to feed multiple indoor units.

 

One refrigerant line to feed a single indoor unit.

 

Multiple refrigerant lines to feed multiple indoor units.

 

Multiple refrigerant lines to feed a single indoor unit.

 

UnansweredQuestion 37

0 / 1 pts

Wiring for a four-port multisplit system runs:

 

One wire to each indoor unit.

 

Two wires to each indoor unit.

 

Three wires to each indoor unit.

Correct Answer

 

Four wires to each indoor unit.