Heat of Rejection = Evaporator Heat + Compressor Heat
he coaxial (counterflow) design means that
refrigerant and water flow in opposite
directions which increases heat exchange
efficiency. The warmest refrigerant is in
contact with the warmest water which
maintains a more constant temperature
difference.
Water Outlet
To
Ground Loop
90F
Refrigerant
Inlet from
Compressor
HP/HT/SC
Typical closed loop water source heat pumps require 3.0 GPM/To
Since open loop systems are fed with cooler water, they require only 1.5
GPM/Ton.
Water is heated about 10°F from the inlet to the outlet or the water coil
BTU = GPM x 500 x ΔT
Recovered heat is the heat of
rejection put to useful work.
The water tubes must be cleaned
annually which requires a system
shutdown and refrigerant recovery
Evaporative condensers are used to
condense the refrigerant in a chiller system
by evaporating a small amount of water on
the warm refrigerant pipes
970 BTU/lb. of heat is removed for every
pound of water that evaporates
Dampers and fan can control are used for
low ambient control.
Although water source systems are very efficient, they also require more
maintenance.
all water
source systems require some sort of cleaning and descaling annually
Higher than normal condensing temperatures are an indication of poor
heat exchange because of poor water flow or scaled/fouled condensers.
The first check should always be condenser water flow!
80% of the
heat is rejected through refrigerant condensation
while the refrigerant is saturated.
At normal peak load conditions, the temperature of
the refrigerant in modern high efficiency air source
condensers is 15°−20°F higher than the ambient
temperature. Standard efficiency equipment has a
30°F temperature split.
Airflow across this condenser can be natural-draft,
forced-draft, or induced draft
Induced-draft condensers use a fan to pull air
across the condenser. They are the most
common type of air-cooled condenser design.
Properly charged systems with dirty condensers can
be identified by high condensing pressures and head
pressures.
ir-cooled Coil Construction
Three coil constructions shown from top to bottom: copper
tube and aluminum fin coil, spine-fin aluminum coil, and a
microchannel aluminum coil.
Tube and Fin
(most common)
Spiny Fin (Trane)
Microchannel
(High Efficiency
High-Efficiency Condensers
The common methods to increase
efficiency is to increase the coil size
Remote condensers on ice machines
and refrigerators solve this problem by
moving the heat from the water to
outside the kitchen.
FAN- CYCLING
• FAN SPEED CONTROL
• DAMPER CONTROL
• CONDENSER FLOODING
The typical residential TEV can keep an air conditioner working properly with
ambient temperatures down to 55°F.
Fixed metering devices cannot adapt to pressure changes, so they are only rated
down to 65°F outdoors.
This only works well when multiple fans are used because
with only one fan the pressure would rise too quickly and
fall too quickly creating a pressure rollercoaster
This control will vary the speed of a single-phase fan
motor to keep the head pressure from dropping below
its set point.
Flooding controls artificially raise the head
pressure by backing the liquid refrigerant
up into the condenser. A receiver is
required