Power Plant Systems Notes (Fuel, Water, and Emissions)

Fuel Oils: essential concepts

  • Fuel oils: lighter oils for diesel engines/turbines; heavier oils heated for boilers. Derived from crude oil; residua after distillation/cracking. Distillation separates into distillates; cracking increases light hydrocarbons yields.

  • Key properties to know: specific gravity, heating value, viscosity, flash point, fire point, pour point, sulfur content. API gravity relates to specific gravity as:
    Degrees API=141.5SG15/15−131.5\text{Degrees API} = \frac{141.5}{\text{SG}_{15/15}}-131.5

  • Heating value (kJ/kg) relates to SG; for a representative formula used in the course:
    Heat of combustion (kJ/kg)=2.326[(22,320−3,780)×SG15∘/15∘]\text{Heat of combustion (kJ/kg)} = 2.326\left[(22{,}320-3{,}780)\times \text{SG}_{15^\circ/15^\circ}\right]

  • Grade range (ASTM fuel oils No. 1–No. 6): No. 1 and 2 are distillates; No. 4–6 are heavier distillate/residual blends. Sulfur content generally increases from No. 1 to No. 6 (approx. 0.01%–3.5%).

  • Viscosity is temperature dependent; standard viscometers include Saybolt (Universal/Furol), Saybolt at specified temp; specify both scale and temperature when reporting viscosity.

  • Impurities: water/sediment (non-economical to remove completely; keep impurities low, e.g., <2%), ash (abrasive), and sulphur influence corrosion and SOx emissions.


Fuel Oil Supply Systems: design and operation ( sketch-based )

  • Storage tanks: carbon steel, vented to atmosphere; flame arrestor on vent; steam smothering line to blanket tank; dual-suction pumps (low suction for normal use; high suction for sludge/water removal).

  • Sludge management: water/sludge can settle; switch pumps to high suction when water/sludge reach suction; return to low suction after cleanup.

  • Suction strainers (duplex): two filters; one in service, one standby; switch without pressure loss; differential filter switch at ~10–15 kPa.

  • Fuel oil pumps: usually positive-displacement gear/rotary screw pumps; include discharge pressure relief valves back to storage tank; a downstream PSV prevents downstream overpressure; two pumps: electric for start-up, steam-driven for in-service operation; provide required burner pressure: mechanical atomization needs ~345–1725 kPa; steam atomization needs ~15–860 kPa.

  • Oil heaters: shell-and-tube exchangers; heat oil to ~85–104°C depending on atomization method; heaters and pumps may be separate or skid-mounted.

  • Oil handling and discharge strainers: duplex suction strainers and duplex discharge strainers; mesh sizes depend on fuel oil grade (e.g., 100-mesh for No. 2; 10-mesh for No. 6).

  • Automatic regulation: automatic control valves regulate oil to burners; proportional to combustion air for stable firing; excess oil returned via constant-flow-cycle valve when pumps deliver more than required.

  • Burners: can be dual-fuel (oil/gas); oil gun/atomizer; gas header with inner/outer spuds; pilot lighter for any fuel; steam or mechanical atomization differences drive heater temp targets: steam-atomized oil ~104°C; mechanical ~85–104°C depending on system.

  • Steam-atomizing burner: steam flows through center in oil gun to atomize; nozzle tip photo shown; the steam path surrounds the fuel path.

  • Safety/controls: discharge regulators, flow proportioning between burners; open/close valves to individual burners via remote shut-off stations.


Fuel Gas Supply Systems: design and operation ( sketch-based )

  • Gas composition: methane is main combustible; natural gas may contain H2S (sour gas) and mercaptans; sweetening removes H2S/CO2/mercaptans; water content in gas is normalized; odorants added for safety.

  • Transmission/conditioning: remove water, liquids, H2S; remove dirt; add odorant; ensure gas reaches customer nearly pure fuel.

  • Plant entry and pressure reduction: plant inlet valve; downstream twin pressure reducing stations reduce to plant design pressure (e.g., from ~700 kPa to ~280 kPa). A downstream shut-off isolates the regulator in case of major leaks.

  • Pilot and main burner lines: pilot off-take reduces 280 kPa to ~20 kPa for pilots; remote shut-off for pilots arranged with two shut-off valves and vent valve; main burner control valve varies gas flow from ~7–70 kPa depending on boiler load.

  • Piping considerations: slope ~2.5 cm per 15 m; drip legs; expansion bends; branch connections on top/sides; external shutoffs near buildings; lockable valves above 35 kPa; ensure valves accessible for emergency.

  • Safety interlocks: manual shut-offs; automatic shut-off stations; pilot take-off; burner control valve; furnace venting.


Solid Fuels: design and operation ( sketch-based )

  • Types: coal (several grades), biomass (wood, bark, chips, sawdust), refuse-derived fuel (RDF), waste incineration with heat recovery.

  • Biomass specifics: lower NOx/SO2 emissions than fossil fuels; grating systems for feeding biomass: travelling gratings, pinhole furnaces, vibrating grate systems; fluidized bed biomass boiler shown; two- to multi-fuel feeders.

  • Coal properties: carbon, hydrogen, oxygen, sulfur, nitrogen, moisture, ash; coal is categorized by fixed carbon/volatile matter content and heating value (Anthracite, Semi-anthracite, Bituminous, Sub-bituminous, Lignite).

  • Pulverized fuel systems: coal is pulverized to fine powder for burners; coal is transported from storage via unloaders to breakers, conveyors, weigh belts, and into bunkers; coal feeders feed pulverizers; pulverizers include ball-race mills and ring-roll (bowl) mills; air supplies the pulverized coal to burners; classifiers control fineness (80% through 200 mesh, 95–99% through 50 mesh is common).

  • Ash handling: two ash streams – bottom ash (coarse) and flyash (fine). Bottom ash collected in hoppers; fly ash removed by baghouse or electrostatic precipitator (ESP). Wet bottom ash systems use water quenching; dry bottom ash uses mechanical handling.

  • Dust collection: baghouses (fabric filters) provide high efficiency; cleaning methods include reverse air, shaker, and pulse-jet; bag life 3–5 years; moisture/acid dewpoint considerations.

  • Electrostatic precipitators (ESP): charged discharge electrodes; plates collect flyash; high voltage DC (30–75 kV); periodic rapping to loosen ash; back corona and resistivity issues addressed by design; maintenance of hoppers and ash conveying.


Coal and Fuel Handling Components (core flow)

  • Coal storage → unloading (ships/trains) → reclaiming → breakers (to reduce lump size) → magnetic separators to remove tramp metal → belt weighing → bunkers/hoppers → coal feeders → pulverizers → burners.

  • Pulverizers: types include tube mills, ball-and-race mills, impact mills, hammer mills, bowl mills; primary air for drying/transport; classifiers to meet fineness; sometimes supported by external exhauster or forced-draft fans.

  • Flow control: feeders (gravimetric or volumetric); belt feeders or overshot roll feeders; load control linked to boiler demand.


Power Plant Water and Steam Systems: design and operation (sketch-based)

  • Overall water cycle: makeup water → feedwater heating → boiler economizer/steam drum → steam distribution to process heaters/turbines → condensate return to deaerator; condensate polishing for high-purity feedwater.

  • Feedwater systems:

    • Condensate is purified makeup water; preheated in multiple stages: LP heaters, HP heaters; deaerator removes O2/CO2; open (deaerator) heater is common; HP heaters are downstream of boiler feedwater pumps.

    • Boiler cycles: utility plant with six or eight stages of feedwater heating; bleed steam heats feedwater; condensate drains cascade through heaters; deaerator storage serves as suction for feedwater pump.

    • Closed feedwater heaters: U-tube design; shell-side heated by low-pressure steam; bypass valve to protect shell in leaks; trip gear to avoid overpressure.

  • Steam distribution: high-pressure superheated steam from boiler to topping turbine; process heating and utility steam use; pressure reductions via stations; steam traps and condensate return; LP/MP/HP headers; return condensate to deaerator.

  • Condensate systems: condensate return tank; flash losses; amines added to control pH; condensate polishing to recover as feedwater.

  • Cooling water systems:

    • Open circulating (wet) system: cooling water from tower to heat exchangers, then back to tower; two cooling modes: evaporative cooling and air contact; typical outlet temps ~40–45°C; inlet ~20°C.

    • Closed recirculating system: chiller or cooling tower alternative; reduced makeup and blowdown; lower chemical load when closed.

    • Makeup water quality and blowdown: conductivity control to maintain cycle concentration; softened makeup reduces blowdown.

  • Wastewater handling: plant wastewater flows to treatment (oil/water separation tank, primary sludge), stabilization lagoon with aeration, activated sludge, clarifier, polishing tank; discharge with QA parameters (pH 6.5–8.5; BOD/COD; temperature; suspended solids).


Measurement, Control & Instrumentation (highlights)

  • Pressure measurement: transducers (electrical/ electronic) convert mechanical pressure (Bourdon, diaphragm, bellows) to electrical signal; transducers include voltage divider, variable resistance, inductance, reluctance (magnetic pickup), capacitance, strain gauges, and piezoelectric transducers. Commonly used in boiler control loops.

  • Temperature measurement: RTD (platinum, nickel, copper; 3- or 4-wire), thermocouples (types B,E,J,K,R,S,T), thermistors; radiation pyrometers for non-contact temp; thermowell protection; RTD three-wire/ four-wire compensation.

  • Level measurement devices: ball-float, displacement-type, hydrostatic head, capacitance, multi-probe conductivity columns, nucleonic gauges, ultrasonic, remote water-level indicators; open/closed-loop level control in deaerator, boiler drums.

  • Flow measurement: differential-pressure meters (Venturi, orifice plate, flow nozzle, Dall tube, Gentile flow tube, Pitot tubes); Q = A v relationships; need straight-pipe runs; importance of proper tapping locations to avoid disturbances.

  • Liquid level and flow-indicating devices: manometers (U-tube, mercury-filled, bell-type, spring-balanced), square-root vs linear scale (square-root compensation for DP meters); ring balance; force balance transmitters; electric flow indication (electro-mechanical and mag meters).

  • Valve actuation options: solenoid, pneumatic-diaphragm, power cylinder, electric motor; positioners to provide high-gain control; open-loop vs closed-loop control of final control elements.


Automatic Control Theory for Boilers (summary)

  • On/Off (two-position): simple, uses cut-in/cut-out pressure setpoints; poor for stable control; used where load changes are small.

  • Proportional (P) control: output proportional to error; reduces offset but cannot eliminate it; risk of oscillation if gain is too high.

  • Proportional-Integral (P+I) control: adds integral (reset) action to eliminate offset; improves steady-state accuracy.

  • Proportional-Integral-Derivative (P+I+D): adds derivative (rate) action to improve transient response.

  • Single-element vs multi-element feedwater control:

    • Single-element: drum level control only; adequate for small boilers with limited load changes.

    • Two-element: adds steam flow as a feedforward signal to anticipate drum level changes (reduces swell/shrinkage).

    • Three-element: adds feedwater flow measurement; maintains best drum level under wide loading by comparing steam and feedwater flow plus drum level.

  • Turbine-following vs boiler-following vs integrated control: coordination between boiler firing and turbine load with megawatt signals; integrated control provides flexible performance.

  • Distributed Control Systems (DCS): centralized computer-based control with operator interfaces, alarms, and data history; network protocols (Fieldbus, HART, Ethernet/TCP-IP); advantages include better trend analysis, alarm management, and remote operation; disadvantages include vendor lock-in and higher cost; modern systems use glass displays and historian data.

  • Programmable Logic Controllers (PLC): modular, field-programmable control with I/O racks; simple logic with timers and counters; PLCs used for sequencing startups and safety interlocks.


Combustion, Emissions & Environmental Control (brief)

  • Combustion chemistry: complete vs incomplete combustion; formation of CO2, CO, H2O, SO2, NOx; elemental balances (C, H, O, S) govern emissions and energy yield.

  • NOx control: multiple approaches—flue-gas recirculation (FGR/IFGR), air staging, fuel staging, burner out-of-service (BOOS), low-NOx burners, and, where appropriate, SNCR/SCR (catalytic/ non-catalytic reduction of NOx).

  • Flue Gas Desulfurization (FGD): wet scrubbers (lime/limestone slurries) and dry/wet combinations to remove SO2; gypsum byproduct; lime/lime-slurry regeneration considerations; acid dew point management; corrosion control.

  • SCR: catalytic reduction of NOx using ammonia, NOx converted to N2 and H2O; concerns: ammonia slip, catalyst life, space requirements; alternatives include SNCR (ammonia/urea without catalyst).

  • Mercury control & other pollutants: measurement and control as part of CEMS; use of baghouses and ESPs for particulates; chemical conditioning of flue gas to improve collection efficiency; ozone/or other methods for NOx and CO2 reductions where applicable.


Water, Wastewater & Environmental Monitoring (highlights)

  • Wastewater treatment in plants: oil/water separation, primary/secondary treatment, aeration, clarifier, polishing, disinfection (chlorine/chlorine dioxide) before reuse or release.

  • Cooling water chemistry: corrosion inhibitors, scale inhibitors, anti-foaming agents; blowdown to control conductivity; makeup water quality; water treatment strategies for open and closed systems.

  • CEMS: Continuous Emission Monitoring Systems for stack emissions; components: sampling system, gas analyzers, data acquisition; extractive vs in-situ analyzers; data handling and QA requirements; monitoring of opacity (PM) and various gas species (SO2, NOx, Hg, O2, CO2, hydrocarbons).

  • Environmental data usage: real-time adjustments, trend analysis, regulatory reporting, and QA; uptime/availability targets (often 90–95% monthly) and backfill data strategies if data is invalid.

  • Fuels and combustion planning to minimize emissions: selection of fuels, ash fusion temperature management, and slag control to avoid deposition on heat transfer surfaces.


Quick reference equations and concepts

  • API gravity relation to SG:
    API=141.5SG−131.5\text{API} = \frac{141.5}{\text{SG}} - 131.5

  • Fuel oil heating value (example from course):
    Heat of combustion (kJ/kg)=2.326[(22,320−3,780)×SG15∘/15∘]\text{Heat of combustion (kJ/kg)} = 2.326\left[(22{,}320-3{,}780)\times \text{SG}_{15^\circ/15^\circ}\right]

  • Air for combustion (typical coal example):

  • Theoretical air for complete combustion is composition dependent (typical coal ~9.2 kg air per kg coal).

  • Gas to plant entry pressure and reduction: gas entry ~700 kPa; downstream regulators to ~280 kPa; pilot gas to ~20 kPa.

  • Basic differential pressure flow principle: flow meter output is proportional to sqrt of differential pressure (for DP meters).

  • Open vs closed cooling water: open uses evaporation; closed uses chillers; blowdown concentrates dissolved solids.


Exam-ready tips

  • Be able to sketch fuel oil, fuel gas, and solid fuel supply systems and label major components (tanks, strainers, pumps, heaters, burners).

  • Memorize grade ranges and key properties: viscosity ranges, flash points, sulfur content, and typical heating values.

  • Understand boiler feedwater heating sequence (LP/HP heaters, deaerator, economizer) and the role of bleed steam.

  • Distinguish open vs closed cooling systems; know why condensate polishing matters for high-pressure feedwater.

  • Recognize major control strategies: On/Off, P, PI, PID; single/2/3-element feedwater control; turbine-following, boiler-following, integrated control.

  • Know primary NOx and SO2 control methods (FGR, staging, SCR/SNCR, FGD, dry scrubbers) and the concept of ammonia slip.

  • Understand basic waste management: bottom vs fly ash, baghouses vs ESPs, and why cleaning cycles matter.

  • Be able to identify key instrumentation types and where they’re used (pressure, temperature, flow, level, and corresponding transducers).

  • Know the purpose and basic arrangement of a Packaged Boiler Control System startup sequence (purge, pilot, main flame proving, firing rate control).