Heat of Rejection = Evaporator Heat + Compressor Heat

he coaxial (counterflow) design means that

refrigerant and water flow in opposite

directions which increases heat exchange

efficiency. The warmest refrigerant is in

contact with the warmest water which

maintains a more constant temperature

difference.

Water Outlet

To

Ground Loop

90F

Refrigerant

Inlet from

Compressor

HP/HT/SC

Typical closed loop water source heat pumps require 3.0 GPM/To

Since open loop systems are fed with cooler water, they require only 1.5

GPM/Ton.

Water is heated about 10°F from the inlet to the outlet or the water coil

BTU = GPM x 500 x ΔT

Recovered heat is the heat of

rejection put to useful work.

The water tubes must be cleaned

annually which requires a system

shutdown and refrigerant recovery

Evaporative condensers are used to

condense the refrigerant in a chiller system

by evaporating a small amount of water on

the warm refrigerant pipes

970 BTU/lb. of heat is removed for every

pound of water that evaporates

Dampers and fan can control are used for

low ambient control.

Although water source systems are very efficient, they also require more

maintenance.

all water

source systems require some sort of cleaning and descaling annually

Higher than normal condensing temperatures are an indication of poor

heat exchange because of poor water flow or scaled/fouled condensers.

The first check should always be condenser water flow!

80% of the

heat is rejected through refrigerant condensation

while the refrigerant is saturated.

At normal peak load conditions, the temperature of

the refrigerant in modern high efficiency air source

condensers is 15°−20°F higher than the ambient

temperature. Standard efficiency equipment has a

30°F temperature split.

Airflow across this condenser can be natural-draft,

forced-draft, or induced draft

Induced-draft condensers use a fan to pull air

across the condenser. They are the most

common type of air-cooled condenser design.

Properly charged systems with dirty condensers can

be identified by high condensing pressures and head

pressures.

ir-cooled Coil Construction

Three coil constructions shown from top to bottom: copper

tube and aluminum fin coil, spine-fin aluminum coil, and a

microchannel aluminum coil.

Tube and Fin

(most common)

Spiny Fin (Trane)

Microchannel

(High Efficiency

High-Efficiency Condensers

The common methods to increase

efficiency is to increase the coil size

Remote condensers on ice machines

and refrigerators solve this problem by

moving the heat from the water to

outside the kitchen.

FAN- CYCLING

• FAN SPEED CONTROL

• DAMPER CONTROL

• CONDENSER FLOODING

The typical residential TEV can keep an air conditioner working properly with

ambient temperatures down to 55°F.

Fixed metering devices cannot adapt to pressure changes, so they are only rated

down to 65°F outdoors.

This only works well when multiple fans are used because

with only one fan the pressure would rise too quickly and

fall too quickly creating a pressure rollercoaster

This control will vary the speed of a single-phase fan

motor to keep the head pressure from dropping below

its set point.

Flooding controls artificially raise the head

pressure by backing the liquid refrigerant

up into the condenser. A receiver is

required