Pneumatic Technology Package TP101 Study Notes
Overview of the TP101 Pneumatic Technology Package
The Collection of Transparencies is designed for the basic material of the TP100 Pneumatic Technology Package, which forms part of the Learning System for Automation from Festo Didactic GmbH & Co.
The transparency materials are developed from both didactical and methodological perspectives to support technical instruction.
The accompanying syllabus covers the following educational objectives:
Physical fundamentals of pneumatics.
Function and application of various pneumatic components.
Designation and drawing of standardized pneumatic symbols.
Drawing of pneumatic circuit diagrams in accordance with international standards.
Representation of motion sequences and different operating statuses.
Implementation of direct and indirect stroke-dependent controls.
Utilization of / logic functions for input signals.
Design of time-dependent control systems using time-delay valves.
Design of pressure-dependent control systems using pressure sequence valves.
Troubleshooting procedures for simple pneumatic control systems.
Electronic presentation materials are provided on CD-ROM, including "Pneumatics_transparencies.pdf" and "Pneumatics_text.pdf". The software required for these files is Adobe Acrobat Reader (specifically version for Windows provided as "rs405eng.exe").
The Structure of Pneumatic Systems
Pneumatic systems are structured hierarchically, typically read and analyzed from the bottom to the top.
S P A Principle: Sensor, Processor, Actuator.
I P A Principle: Input, Processing, Output.
The flow of energy and signals follows a specific control chain:
Energy Supply Elements: This base level includes the compressor, pneumatic reservoir, pressure regulating valve, and service unit.
Signal Input (Input Elements): These components initiate signals and include push-button directional control valves, roller lever valves, proximity switches, and air barriers.
Signal Processing (Processing Elements): These components handle logic and include directional control valves, shuttle valves, dual-pressure valves ( logic), pressure sequence valves, and sequencers.
Command Execution / Signal Output (Working Elements): This top level performs the actual work and includes components such as cylinders, motors, and optical indicators.
Control Elements: These are directional control valves that interface directly between the processing stage and the working elements.
System Circuit Diagram and Component Identification
Circuit diagrams follow a standardized identification code for components to ensure clarity and organization.
Numbering Logic:
System Number: Begins with ; this is only used if the entire circuit consists of more than one system.
Circuit Number: Begins with . All accessories associated with the circuit are identified with .
Component Identification: Designated by a letter (e.g., for actuator, for valve, for sensor/switch, for energy supply).
Component Number: Begins with .
Hierarchical Layout (Top to Bottom):
Working Element: Identified as ; may have a marking line for input elements like .
Control Element: Identified as .
Processing Element: Identified as .
Input Elements: Identified as , , and .
Energy Supply Elements: Identified as and .
Direct Actuation of Cylinders
Single-acting Cylinders:
Perform work in only one direction.
Return to the initial position via an integrated mechanical spring.
Feature one air supply port and one vent hole.
Controlled by a -way valve (specifically a valve with working ports and switching positions).
Typically manually actuated with a spring return.
Double-acting Cylinders:
Perform work in both directions (advance and retract).
Feature air supply ports (no return spring).
Controlled by a -way valve (specifically a valve with working ports and switching positions).
Typically manually actuated with a spring return.
Operational States:
Rear End Position: Retract.
Front End Position: Advance.
Symbols for the Power Supply Section (DIN ISO 1219)
Symbols follow DIN ISO : "Fluid Technique – Graphical Symbols and Circuit Diagrams."
The flow direction is indicated by a triangle. Pneumatic and hydraulic symbols generally follow the same logic.
Key Energy Supply Symbols:
Compressor: Constant displacement volume.
Pneumatic Reservoir.
Pressure Source.
Maintenance Symbols:
Filter.
Water Separator: Available with manual actuation or automatic condensate drain.
Lubricator.
Pressure Regulating Valve: Includes a relief port and is adjustable.
Combined Symbols:
Air Service Unit: Represents a combination of a compressed air filter, pressure regulating valve, pressure gauge, and lubricator.
Simplified Service Unit: A single box symbol representing the maintenance components.
Simplified Service Unit (no lubricator): A single box symbol excluding the lubrication function.
Directional Control Valves: Ports and Switching Positions
Directional control valves serve as control, processing, or input elements.
Naming Convention:
The designation is pronounced as "X-slash-Y way valve" (e.g., -way valve is "Two-slash-two way valve").
The first digit () represents the number of ports.
The second digit () represents the number of switching positions.
Standard Variations:
2/2-Way Valve: Normally open position.
3/2-Way Valve: Available in normally closed or normally open positions.
4/2-Way Valve: Flow from and from .
5/2-Way Valve: Flow from and from .
5/3-Way Valve: Features a mid-position where ports are closed.
Port Identification: Numbers are used exclusively for port identification.
Port Designations (DIN ISO 5599-3)
Port numbering follows DIN ISO : "Fluid Technology – Pneumatics, 5-Way Valves."
Power Ports:
1: Supply port.
2, 4: Working ports.
3, 5: Exhaust ports.
Pilot Ports (Signal Ports):
10: A signal applied at this port blocks flow from to .
12: A signal applied at this port opens flow from to .
14: A signal applied at this port opens flow from to .
81, 91: Designations for auxiliary pilot air.