Panelboard & Switchboard Notes
Panelboard Selection
- Amperage:
- OCPD must be greater than the calculated load.
- Typically load to 80% capacity.
- Allow for future capacity.
- Standard Amp Ratings: 100, 150, 200, 225, 250, 400, 600
MLO or MCB
- Considerations:
- Where will OCPD be located?
- Is a main circuit breaker needed or sensible?
Number of Poles
- Typical options: 12, 18, 24, 30, or 42 poles.
Feeder Size
- Feeder must be sized to match the selected OCPD.
Distribution Panels
- Range: 400A - 1200A.
- Mounting: Wall mounted (surface or recessed).
- Protection: Fuses or CBs, but not both.
- Configuration: MLO or MCB.
- Siemens panels: P4 & P5.
- Physical size depends on breakers.
Enclosure Dimensions
- Type 1 and Type 3R/12 enclosures are common.
- Dimensions vary based on amperage (400-800A).
Branch Breaker Selection
- Key factors:
- Maximum Interruption Rating (KAIC).
- Voltage (AC).
- Trip Type (Thermal, Magnetic, Electronic).
- Amperage.
- Unit Space Requirements.
Switchboards/Switchgear
- Amperage: 1200A - 6000A (MCB limited to 5000A).
- Common Range: 1200A - 4000A.
- Mounting: Floor mounted.
- Configuration: MLO or MCB.
- Standards:
- UL891 - Switchboards (requires front access).
- UL1558 - Switchgear (requires access on all sides).
- Compartment barriers limit to 4 devices in a vertical section.
Sizing Considerations
- Continuous load: 125%.
- Spare capacity: 10% minimum.
- Order of Work:
- Calculate sizing load in amps.
- Select appropriate OCPD (local or remote?).
- Select appropriate panel.
- Select feeder size.
Load Calculations
- Example:
- Lighting: 6233<br/>vert1.25=7791.25
- Receptacles (<10KVA): 10000<br/>vert1.00=10000
- Receptacles (>10KVA): 16100<br/>vert0.50=8050
- Largest Motor: 44064<br/>vert1.00=44064
- Misc: 5200<br/>vert1.00=5200