Raceway and Conduit Notes
Raceway/Conduit
- Purpose
- Protect conductors
- Support conductors
- Provide access to conductors
- Reduce risk of fire
- Metal raceway can be used as grounding conductor (but we won’t do that)
- EMT (Electrical Metal Tubing) – NEC 358
- Also called “thin wall conduit”
- Tubing not threaded, joined by compression or set screw fittings
- IMC (Intermediate Metal Conduit) – NEC 342
- More protection from physical damage
- Threaded fittings
- RMC (Rigid Metal Conduit) – NEC 344
- Threaded fittings
- Maximum protection from physical damage
- FMC (Flexible Metal Conduit) – NEC 348
- Commonly called “Greenfield”
- Generally for final connections, specifically those subject to movable devices (lights), or vibration (motors)
- Limit length to less than 6 feet.
- LFMC (Liquid-tight Flexible Metal Conduit) – NEC 350
- PVC jacketed to allow for outdoor use
- ENT (Electrical Non-metallic Tubing) - NEC 362
- Most often blue or orange flexible tubing
- “Smurf tube” or “Smurf pipe”
- Can’t be used in return air plenums
- PVC (Rigid polyvinyl Chloride Conduit) - NEC 352
- Comes in Schedule 40 and Schedule 80
- Lightweight, inexpensive
- Typically used for below grade installations
- Not allowed in return air plenums
Raceway Sizing
- Generally the smallest allowed by code/common practice is 1/2”
- Smallest conduit underground is typically 1”
- NEC Chapter 9
- Table 1- Limits us to 40% fill
- Start with Table 5 to determine total area for conductors
- Then use Table 4 to select appropriate conduit size based on conduit type
- Annex C-Explanatory material (not code)
- Based on Tables 1, 4, 5 and 5A in Chapter 9
- Must use the table that corresponds to the conduit being used