Dl: Deciliter
Pumping Limits
Plant pressure- 78-86 psi
Glendale pressure- 30 psi- 56 psi (recommended pumping pressure 40 psi)
Fox point pressure- 30 psi- 65 psi (recommended pumping pressure is 60 psi)
Whitefish Bay pressure- 60 psi- 75 psi (recommended pumping pressure is 71 psi)
Chemical Limits
Alum: >4.0 ppm
Fluoride: Target dose is 0.70, acceptable range is 0.65-0.75 ppm
Chlorine: <3.00 ppm in plant tap water
Tap target dose: 2.60 ppm, acceptable range is 2.50-2.70 ppm
Current Clearwell target dose: 2.40 ppm, acceptable range is 2.25- 2.55 ppm
Tap free chlorine: <0.20 ppm
Phosphate: Target dose 3.30 ppm, acceptable range is >2.8ppm
Alkalinity: acceptable range is 105-125 dl
Hardness: acceptable range is 120-150 dl
pH: acceptable range is 7.00-8.00 for tap water
UVT: Target range is >95% (<95% and >3 from online analyzer is unacceptable)
Filters
<0.30 NTU in any filter, target range is <).10 NTU
>0.6 MGD flow per filter (0.3 MGD per side) and <3.0 MGD flow per filter (1.5 MGD per side)
Never stop filter flow, if so the filter must be taken out of service and back washed
Raw flow can not be adjusted up by greater than or equal to 0.5 MGD every 20 minutes
Turbidity
Clearwell <0.30 NTU combined filter effluent, target <0.10
Tap water <0.30 NTU, target is <0.10
Reservoir Level
6.5’-14’
Moves up and down 0.3’ per hour for every 1 MGD difference in flo9w in or out of the reservoirs between 6.5’ -12.5’
From 12.5 to 14 both reservoirs are filling or draining level changes at 0.15 per hour for every 1 MGD difference in flow
Electrical Usage
Klode: <95 Kw for higher kw run the generator
Bender plant <340 kw for higher kw run the generator