Timers and Smart Relays
Timers provide basic automatic control of a system
There are three types of timing devices:
Spring-wound interval timers
Mechanical and electronic time switches
Timing relays
Spring-wound interval timers are designed to be used as wall switches and provide a timed-on interval. Not very accurate.
Mechanical and electronic time switches use small electrically driven clock motors that controls adjustable trip mechanism or cams to change the state of electrical contacts. Electronic time switches use an electric clock to control contacts.
Timing relays timing relays have their timed operation controlled pneumatically, by a fluid filled dashpot, or by electronic circuits.
Timed relays have N/O, N/C, or I/C (instantaneous non-timed contacts)
There are five basic timing functions:
Time delay on energization
Time delay on de-energization
Interval timing
One-shot timing
Repeat cycle timing
TDOE contacts change state after a specified time, when the coil is de-energized the contacts revert their state immediately.
TDOD contacts change state instantly when a relay coil is energized. Their state only revert after a specified time, after the coil is de-energized.
A maintained E-stop is required when TDOD contacts are in a circuit
Interval timing contacts change state instantly when the coil is energized, but revert to their normal state after a specified time measured from the instant the coil is energized, even if the coil remains energized for a longer period.
One-shot timing requires an extra set of terminals to receive a start signal. The coil is energized continuously, but the contacts only change state when the start terminals receive a signal.
Repeat cycle timing provides regular on-off for timed contacts. May be started through a start signal or energizing the coil. May provide an alternate sequence. Starts cycling upon energization until de-energization of the coil.
Multi-function timing relays can provide several different timing functions.
Smart relays have numerous inputs and outputs along with some memory to store a program.
Smart relays are programmable relays often compared to PLCs
The programming languages for smart relays are ladder logic and function block diagrams
Symmetrical timing is same on-off times, non-symmetrical is different - a function of smart relays