Elements of Boiler Systems Study Notes
Combustion Theory and Chemistry
- Combustion Definition: The rapid oxidation of a fuel producing heat energy, light, and gaseous products (Fuel+Oxygen→Products of Combustion+Energy.
- Combustible Elements: Carbon (C), hydrogen (H2), and sulfur (S).
- Fuel Constituents (NOCASH): Nitrogen (N), oxygen (O), carbon (C), ash (A), sulfur (S), and hydrogen (H).
- Moisture and ash are non-combustible residues.
- Fuel-bound oxygen reduces the theoretical combustion air calculation by indicating hydrogen already bonded as water.
- The Three Ts of Combustion: Complete combustion requires sufficient air plus adequate:
- Time: Adequate furnace volume for complete reaction prior to cooling.
- Temperature: Sufficient heat to maintain ignition.
- Turbulence: Thorough mixing of fuel particles and combustion air.
- Complete Combustion Equations:
- C+O2→CO2+Heat
- 2H2+O2→2H2O+Heat
- S+O2→SO2+Heat
- Incomplete Combustion Equations:
- 2C+O2→2CO+Heat
- 2CO+O2→2CO2+Heat
- 3H2+O2→2H2O+H2+Heat
- 2S+O2→SO2+S+Heat
- Air Composition and Quantities:
- Volumetric ratio: 21% O2 and 79% N2.
- Mass ratio: 23% O2 and 77% N2.
- Theoretical air: The exact minimum air needed for complete chemical oxidation.
- Excess air: Air supplied over theoretical air to ensure complete combustion (Combustion Air=Theoretical Air+Excess Air).
- Typical excess air requirements: Stoker coal (25–35%), pulverized coal (15–20%), fuel oil (10–15%), gaseous fuels (3–10%).
- Nitrogen Oxides (NOX): Formed from fuel-based nitrogen (FBN) and high furnace temperatures (>1000∘C. Reduced by lowering peak flame temperatures, staging air (tertiary air), or chemical flue gas treatment.
Fuel Characteristics and Refractory Materials
- Solid Fuels:
- Proximate analysis: Determines moisture, volatile combustible matter (VCM), fixed carbon, and ash.
- Ultimate analysis: Determines mass percentages of elements (C, H, O, N, S) and ash.
- Hog fuel and biomass: Wood waste, bark, pellets, and bagasse. Carbon-neutral alternative fuel.
- Municipal Solid Waste (MSW): Fired via mass burning (unprocessed) or Refuse Derived Fuel (RDF, shredded and separated). RDF regulations mandate minimum combustion temperature of 1000∘C, retention time >1s, and flue gas CO<50ppm.
- Liquid Fuels (Fuel Oils):
- Classified by Relative Density (specific gravity), Viscosity (SSU), and Flash Point.
- Grades 1 and 2: Light furnace oils; low viscosity; do not require preheating.
- Grades 4, 5, and 6: Heavy industrial oils; require preheating in storage and heating to ≈95∘C for atomization.
- Storage safety: Aboveground tanks require containment berms sized for at least 110% of single tank capacity.
- Gaseous Fuels:
- Natural gas: Methane (80–90%) and ethane (10–20%); relative density ≈0.676; odorized with mercaptan for leak detection.
- Liquefied Petroleum Gases (LPG): Propane (boiling point −42∘C) and butane (boiling point 0∘C); liquid form occupies 1/120th of gas volume; heavier than air.
- Biogas: Composed primarily of CH4 and CO2 derived from anaerobic digestion.
- Refractory Materials:
- High-temperature ceramics (fireclay, alumina, silica, zirconia) in bricks, castable, gunnable, plastic, and blanket forms.
- Applied to burner throats, inspection doors, and baffles; subject to spalling, slagging, and thermal cracking from direct flame impingement.
Solid Fuel Delivery and Firing Equipment
- Fuel Handling:
- Coal handling: Crushers reduce coal to <5cm; hammer mills extract tramp metal; belt scales meter input to bunkers (3–12h capacity).
- Biomass handling: Drag chain conveyors, disc screens, and magnetic separators remove tramp iron.
- Mechanical Stokers:
- Spreader stoker: Throws fuel onto grates; fines burn in suspension, larger lumps burn on moving or vibrating beds.
- Crossfeed (chain/travelling grate) stoker: Gravity-fed bed moves from front to rear; fuel depth set by gate.
- Underfeed stoker: Rams force green coal upward through retorts into incandescent bed; air supplied through tuyeres.
- Pulverized Fuel Systems:
- Ball and race pulverizers grind coal into fine dust; primary air carries dust to burner throats; burns entirely in suspension.
- Cyclone Furnaces:
- Tangential high-velocity combustion in water-cooled horizontal cylinders exceeding 1650∘C; ash liquefies and drains as molten slag.
- Fluidized Bed Combustion (FBC):
- Solid fuel burns in suspension within an inert granular bed (sand, limestone) kept fluid by upward airflow.
- Bubbling bed (AFBC): Fluidizing velocity 2–3m/s; distinct freeboard boundary; utilizes in-bed steam tubes.
- Circulating bed (CFBC): Fluidizing velocity 6–10m/s; bed material circulates through cyclones and returns to the furnace.
- Environmental advantage: Low combustion temperature (800–900∘C) limits thermal NOX; limestone converts to CaO and captures SO2 as gypsum (CaSO4).


Gaseous and Liquid Fuel Burners
- Gas Burners:
- Premix (atmospheric): Primary air (30–40%) entrained in venturi before reaching drilled ports or ribbons; blue, non-luminous flame.
- After-mix: Mechanical draft introduces combustion air; fuel and air mix at burner throat (e.g., ring burners, multi-spud burners).
- Pilots: Continuous (standing), intermittent (fires during main burner on-cycle), and interrupted (de-energizes 10s after main flame established).
- Automatic Safety Shut-Off Valves (SSOV): Normally closed, slow opening (4–5s), instantaneous closing (<1s); diaphragm valves, solenoid valves, or electro-hydraulic motorized valves (Hydramotor® / Fluid Power Gas Valve®).
- Liquid Fuel Burners:
- Air atomizing: Compressed air (100–250kPa) shears fuel mist; turndown ratio up to 8:1.
- Steam atomizing: Dry steam supplied at 100–200kPa above oil pressure (1035–1380kPa); turndown ratio up to 6:1.
- Mechanical atomizing: Oil forced under pressure (700–1400kPa fixed; 2050–2750kPa modulating) through slotted sprayer plate.
- Rotary cup: Oil spun off a cup at 3000–8000r/min into high-velocity air; turndown up to 10:1.
- Oil Fuel Auxiliaries:
- Fuel oil pumps: Single-stage (<2.4m lift); two-stage (<4.9m lift per CSA B139).
- Relief valve returns excess oil to tank; cutoff valve prevents fuel admission below minimum atomization pressure.
- Time-delay oil valve holds closed for 5–15s after igniter spark to permit a 10–15s air pre-purge.
Flue Gas Analysis and Combustion Efficiency
- Flue Gas Components: Primary indicators are CO2, O2, CO, SO2, and NOX.
- Combustion Efficiency Indicators:
- Maximum CO2 indicates stoichiometric combustion.
- Declining CO2 with high O2 signifies excessive combustion air.
- Declining CO2 with presence of CO and unburned carbon (soot) signifies incomplete combustion.
- Electronic Instrumentation: Continuous Emissions Monitoring Systems (CEMS) utilize electrochemical or infrared (IR) sensors, equipped with thermoelectric Peltier coolers to remove moisture.
- Net Stack Temperature: Measured stack temperature minus ambient combustion air temperature. Boiler efficiency declines with higher net stack temperatures and excess air.
Draft Systems and Airflow Regulation
- Draft Definition: A differential pressure that produces a continuous flow of air and combustion gases through a boiler.
- Natural Draft: Density difference between hot gases in a vertical stack and equal-height column of cooler outdoor air.
- Increases with chimney height, higher flue gas temperature, and lower ambient temperature.
- Mechanical Draft Systems:
- Induced Draft (ID): Fan at boiler outlet maintains negative furnace pressure; handles hot, expanded flue gas.
- Forced Draft (FD): Fan supplies ambient air to windbox under positive pressure.
- Balanced Draft: Combines FD fan (supplies combustion air) and ID fan (maintains slightly negative furnace pressure set point).
- Airflow Control Methods: Inlet vane dampers (VIV), fan outlet dampers, burner registers/louvres, or variable fan speed (steam turbine governors, VFDs, or variable speed couplings).
- Draft Measurement: Low pressures measured in millimeters of water (1mmH2O=9.81Pa) via U-tube manometers, inclined manometers, or diaphragm gauges.
- Ventilation Regulations: Dedicated outside air supply openings required by CSA B149.1 (gas) and CSA B139 (oil); doors/operable windows prohibited as certified air openings.

Boiler Feedwater and Piping Systems
- System Components: Make-up water treatment, condensate returns, deaerator, boiler feed pumps, and control valves.
- Deaerator Functions:
- Operates as ASME BPVC Section VIII vessel at 70–400kPa.
- Removes dissolved O2 and CO2 to prevent waterside corrosion.
- Preheats feedwater to reduce thermal shock.
- Stores 20min reserve feedwater volume elevated above pumps to provide Net Positive Suction Head (NPSH).
- Piping Codes and Valves:
- ASME B31.1 (122.1.7) mandates a check valve and stop valve (gate valve) on power boiler feedwater connections.
- Globe valves must receive flow under the disc.
- Feedwater design pressure must exceed boiler MAWP by 25% or 1550kPa, whichever is less (ASME B31.1 122.1.3).
- Automatic Recirculation Control (ARC) valves or minimum flow orifices prevent feed pump overheating during throttled flow.

Feedwater Control Strategies and Low Water Cut-Offs
- Control Methodologies:
- Single-element: Regulates feed valve based strictly on drum water level; suitable for steady loads and large water volumes.
- Two-element: Regulates based on drum level and steam flow; mitigates swell and shrinkage.
- Three-element: Regulates based on drum level, steam flow, and feedwater flow; achieves strict mass-flow balance on high-capacity units.
- Swell and Shrinkage:
- Swell: Sudden steam load increase causes drum pressure drop; steam bubbles expand, producing a false water level rise.
- Shrinkage: Sudden steam load decrease raises drum pressure; steam bubbles collapse, producing a false water level drop.
- Low Water Fuel Cut-Offs (LWCO):
- CSA B51 (6.3.2) requires at least two independent cut-offs for boilers without continuous certified supervision.
- ASME CSD-1: Requires two cut-offs set at different levels, activating above the Lowest Permissible Water Level (LPWL) and visible in the gauge glass; the lower control mandates manual lockout reset.
- Steam heating return loops (Hartford loops) prevent gravity return systems from siphoning boiler water below the safe line.
Blowoff and Blowdown Systems
- Blowoff vs. Blowdown:
- Bottom blowoff: Intermittent discharge of sludge and suspended mud from lowest points (drums, headers) performed under light load once per 24h (ASME Section VII).
- Surface blowoff: Skims oily or suspended matter ≈15cm below water level to prevent foaming and priming.
- Continuous blowdown (CBD): Continuously extracts concentrated water to maintain Total Dissolved Solids (TDS) and specific conductance within ASME guidelines.
- Shock Service and Valve Requirements:
- Bottom blowoff piping requires shock service design (ASME B31.1): Schedule 80 steel for >690kPa; Class 2000# fittings minimum; diameters 25–65mm (20–50mm for Section IV).
- Quick-opening and slow-opening valve combination sequence:
- Opening: Open inside quick-opening guard valve first, then open outside slow-opening valve slowly.
- Closing: Close outside slow-opening valve first, then close inside quick-opening guard valve last.
- Two seatless valves: Open outside valve first and close outside valve last to prevent hydraulic lock and casing fracture.
- Blowoff vessel: Depressurizes flash steam to atmosphere and quenches effluent to maximum 65∘C (CSA B51) prior to sewer entry.

Boiler Fireside Cleaning Systems
- Fireside Fouling: Ash, soot, and slag insulate tubes, lowering thermal efficiency, increasing net stack temperature, reducing steaming rate, and increasing gas pass draft loss.
- Soot Blowing Mediums: High-pressure dry superheated steam (prevents tube erosion), compressed air, or water wash; boiler must operate at minimum 50% load with negative furnace draft (ASME Section VII).
- Soot Blower Varieties:
- Short retractable wall blowers: Installed in radiant waterwall zones; penetrate 25–50mm and rotate 360∘ to clean a 1.5m radius.
- Long retractable soot blowers: Traverses between tube banks in radiant superheaters/reheaters; opposed nozzles discharge in a helical path; lance requires continuous steam flow while inserted to prevent thermal sagging.
- Stationary soot blowers: Multi-nozzle elements rotating permanently in lower temperature convection passes (generating bank, economizer).
- Non-Lance Cleaning Methods: Acoustic (sonic) horns, mechanical/pneumatic rapping, falling shot (6mm steel pellets), and controlled explosives for stubborn slag.
Questions & Discussion
- Combustion Air Calculation (Powder River Basin Coal):
- Theoretical air: 7.5kg air per 1kg coal.
- Total air required for 25kg coal at 20% excess air: 25×7.5×1.20=225kg.
- Theoretical and Combustion Air for Liquid Fuel:
- Composition: 75.4% C, 12.6% H2, 0.25% S, balance ash.
- Calculated theoretical air requirement: 10.0m3/kg.
- Combustion air required at 15% excess air: 10.0×1.15=11.5m3/kg.
- Flue Gas Analysis and Fuel Interdependence:
- Flue gas reading of 14.2% CO2 corresponds to 7.5% excess air when firing light fuel oil, but corresponds to 30.9% excess air when firing bituminous coal.
- Continuous Blowdown Rate Determination:
- Boiler generates 6700kg/h steam with a feedwater supply of 6920L/h (6920kg/h).
- Blowdown flow rate: 6920−6700=220kg/h.
- Blowdown percentage: 6920220×100%=3.2%.
- Safety Case Studies:
- Isolation of Shared Blowoff Piping: Boilers connected to a shared blowoff tank must have blowoff lines disconnected and blanked before workers enter drums, preventing accidental scalding from adjacent active units.
- Piping Material Compatibility: Forged brass ball valves (ASTM B283 C37700) are explicitly prohibited for boiler external piping by ASME B31.1 due to catastrophic body separation hazards under thermal shock.