Gas Piping System Notes
Gas Piping Systems
Sizing
- Sizing is based on Chapter 4 of the 2015 International Fuel Gas Code.
- Methods include Longest Length Method (402.4.1), Branch Length Method (402.4.2), and Hybrid pressure.
- Maximum indoor pressure is 5 psi (402.6), with exceptions for:
- Welded Fittings
- Ventilated Chase
- Industrial/Agricultural applications
- Temporary construction
- LP gas up to 20 psi
- Common indoor gas piping systems:
- 7” WC
- 2 psi (requires gas utility permission)
- 5 psi (requires gas utility permission)
- Longest Length Method: All pipe sections are sized using the 80-foot column.
Pipe Materials (403…)
- Acceptable Materials:
- Wrought Iron
- Steel (Black Steel)
- Copper
- Aluminum
- Corrugated Stainless Steel Tubing (CSST)
- Plastic (Polyethylene)
- Unacceptable Materials:
Fittings (403.9…)
- Steel:
- Threaded joints with joint compound, Flanges, Welded
- Copper:
- Threaded joints with joint compound, Flanges, Welded, Press Fittings
- Aluminum:
- Brazed, Flared, Press Fittings
- CSST:
- Plastic (Polyethylene):
Installation (404…)
- General:
- Do not run gas piping through ducts, chimneys, elevator shafts, etc.
- Concealed piping inside solid walls/partitions is prohibited unless in a chase or casing.
- Concealed locations require threaded, brazed, welded, or listed fittings.
- Underground piping requires a minimum 12” bury.
- Underground piping to outside appliances requires an 8” bury if not susceptible to damage.
- Do not run gas piping under a building; if necessary, use a sleeve open to the outdoors.
- Underground penetrations of foundations are prohibited.
- CSST:
- Must be protected from damage (Shield Plates 404.7.3).
- Must be bonded to the electrical grounding system.
- Plastic Pipe (Polyethylene, PE) – 404.17:
- Outdoors underground only.
- Not within or under any building or slab.
- Maximum 100 psi.
- Must have a yellow 18ga tracer wire.
- Sediment Trap (408.4):
- Installed downstream of the appliance shutoff valve, close to the appliance inlet.
- Use a tee fitting with a capped nipple in the bottommost opening.
- Exceptions: Illuminating appliances, ranges, clothes dryers, decorative vented appliances, gas fireplaces, outdoor grills.
- Gas Appliance Connection:
- Maximum 6 ft connector in the same room.
- Gas Train Components:
- Dirt Leg, Regulator, Electric Gas Valve, Pipe Union, Manual Gas Valve, Low-pressure gas switch, High-pressure gas switch, PRV vent tubing
- Medium Pressure Regulators (MP Regulators) – 410.1:
- Must be accessible.
- Protected from physical damage.
- If indoors, must be vented outdoors OR equipped with a leak-limiting device.
Testing (406…)
- Pressure:
- 1-1/2 x the design pressure, or
- Minimum 3 psi test
- Test Medium:
- Air, nitrogen, carbon dioxide, or inert gas (406.2).
- Duration:
- 1/2 hour per 500 cubic feet of pipe volume, or
- 10 minutes minimum
- Leakage:
- Any pressure loss indicates a leak; correct and re-test.
Combustion Air and Exhaust Flues
- Fuel-burning equipment needs supply air for combustion and ventilation.
- Key for equipment operation and occupant safety (prevents oxygen depletion and gas buildup).
- Supply air sources:
- Outdoor Air
- Indoor Air
- Mechanical Supply
- Combustion Air Methods:
- Two Openings Method
- Sized and located per Sections 304.6, 304.6.1
- Single High Opening Method
- Sized and located per Sections 304.6, 304.6.2
- Indoor Air Standard Method
- Sections 304.5, 304.5.1
- Calculate required volume: 50 ft² per 1000 Btu
- Combination Indoor/Outdoor Air
- Determine indoor volume ratio and outdoor opening size per Section 304.7
- Engineered System
- Approval required per Section 304.8
- Known Air Infiltration Rate Method
- Sections 304.5, 304.5.2
- Calculate required volume for fan-assisted appliances using Equation 3.2, otherwise Equation 3.1
- Mechanical Supply
- Air flow rate and system design per Sections 304.9 through 304.9.3
- Indoor Air
- 50 cubic feet per 1,000 Btu/h input needed.
- High/low openings within 12 inches of ceiling/floor.
- Opening area of 1 sq. in. per 1,000 Btu/h each.
- Outdoor Air
- High/low openings within 12 inches of ceiling/floor.
- Opening area of 1 sq. in. per 2,000 Btu/h each if vertical.
- Opening area of 1 sq. in. per 4,000 Btu/h each if horizontal.
- Mechanical Supply
- Direct-vent application
- Combustion air duct size per manufacturer’s requirements, based on Btu/h input and length of duct.
- Similar for exhaust flues.
- Minimum separation distances and distances from grade outlined.