Elevator Mechanic Exam Vocabulary Flashcards

Latching Relays and Electrical Identification

  • Definition and Usage: Latching relays are used for call registration, direction selection, or as selector relays.
  • Types: There are two primary types of latching relays:
    • Set/Reset: These are electrical latching relays.
    • Mechanical: These are mechanical latching relays.
  • Symbol Recognition: The symbol for a latching relay is a box containing a shaded triangle located in the lower right-hand corner.

Motor Speed and Electrical Formulas

  • RPM Calculation: To determine the Revolutions Per Minute (RPM), use the following procedure:
    • Step 1: Multiply the constant 60 by the Frequency (ff) in Hertz (HzHz).
    • Step 2: Divide the number of Poles (PP) by 2.
    • Step 3: Divide the result of Step 1 by the result of Step 2.
    • Formula: RPM=60×fP÷2RPM = \frac{60 \times f}{P \div 2}

Resistance and Insulation Testing

  • Megohm Meter (Megger):
    • Used to test the insulation properties of electric wiring, motor windings, and high-power antenna mounts.
    • Often referred to as "megging out" or using a "megger" to identify if equipment or wiring is shorted to ground or the frame.
    • Characteristics: It utilizes significantly higher voltages to check resistance than a standard Volt-ohm meter.
    • Minimum Resistance: The acceptable minimum resistance for insulation is 1MΩ1\,M\Omega.

Shunt and Overload Components

  • Shunt Overload Definitions:
    • (1) A parallel connection.
    • (2) A resistive element placed across armature terminals to bypass a portion of the current.
    • (3) A flexible electrical conductor designed to conduct current around mechanical joints between two conductors.
    • (4) A resistive element (usually very low resistance) used in parallel with a DC ammeter movement to bypass a calibrated portion of the total circuit current.
  • Temporary Run Box Hazards: Getting shocked while using a temporary run box is typically indicative of a bad ground.

Rigging and Hoisting Procedures

  • Bridle Hitch:
    • Consists of two, three, or four single hitches used together to hoist an object.
    • Load Stress vs. Sling Angle:
    • A sling with two legs lifting a 1,000lb1,000\,lb object at a 9090^{\circ} angle results in a load of 500lb500\,lb per leg.
    • If the angle decreases to 3030^{\circ}, the stress increases to 1,000lb1,000\,lb on each leg.
    • Safety Recommendation: Sling angles should be kept greater than 4545^{\circ}. Angles approaching 3030^{\circ} are extremely hazardous and must be avoided.
  • Lifting Materials: Hoisting materials should be checked for defects before every pick.
  • Eye Bolts: To determine the Safe Working Load (SWL), check if the eye bolt is being used for in-line loading (never use eye bolts for non-in-line hoisting).
  • Clevis Usage: When using a clevis with a screw-type pin, the pin must be tightened and inspected before each lift.

Scaffolding and Fall Protection

  • Securement: Scaffolding must be tied to the structure using #9 wire or specific tie-in devices.
  • Tie-off Requirements:
    • The first vertical tie must be at a maximum height of 4 times the narrowest base dimension.
    • Additional vertical ties must not exceed 26ft26\,ft apart.
    • Maximum horizontal distance between ties must not exceed 30ft30\,ft.
  • Load Capacity: OSHA requires scaffolds to support 4 times their maximum intended load.
  • Plank Stability: Planks used in shaftway scaffolding must have cleats to prevent movement.
  • Personal Fall Arrest System (PFAS):
    • Components: Anchorage, Lanyard, and Body Harness.
    • Lanyard length is typically 6ft6\,ft.
    • PFAS must be inspected before each use.
    • Anchorage must be independent and capable of supporting 5,000lbs5,000\,lbs per worker attached.
  • Fall Protection Threshold: OSHA requires fall protection when working on scaffolding at or above 10ft10\,ft from the ground.
  • Barricades: Safety barricades across hoistway openings should be installed after rough or finished floors are in place. Top rails should be at 42in42\,in, mid-rails at 21in21\,in, and include a 3in3\,in toe board.

Car Specifications and Counterweights

  • Counterweight Balance: Counterweights are typically hung to balance the empty car weight plus 40%40\% of the capacity load.
    • Example Calculation: If a car weighs 7,000lbs7,000\,lbs with a capacity of 3,500lbs3,500\,lbs:
    • 40% of 3,500=1,400lbs40\% \text{ of } 3,500 = 1,400\,lbs
    • Total Counterweight = 7,000+1,400=8,400lbs7,000 + 1,400 = 8,400\,lbs.
  • Modernization Weight Changes: If adding 5%5\% to a 10,000lb10,000\,lb counterweight frame:
    • 10,000×0.05=500lbs10,000 \times 0.05 = 500\,lbs
    • New weight = 10,500lbs10,500\,lbs.
  • Guide Shoes: On a traction elevator, bottom guide shoes or roller guides are fastened to the safety plank.

Wiring and Cabling

  • Wire Sizing Standards:
    • Minimum size for wires in traveling cables is #20.
    • Minimum size for wires outside of travelers is #24.
    • The largest wires are the feeders for the hoist or pump motor.
  • Spare Wires: A 10%10\% spare wire count is standard when pulling wire.
    • Calculation for 52 wires: 52×0.10=5.252 \times 0.10 = 5.2 (order 6 spares).
  • Traveling Cable Installation:
    • The loop should be at least 30 times the cable diameter.
    • Vertical suspension must be a minimum of 4ft4\,ft at both the hoistway and car hanger attachments before the loop forms.
    • If replacing a cable with a different size, the hanger must be adjusted "post-wise" to ensure the loop clears the platform edge.
  • Voltage Drop: If a controller is moved (e.g., 30ft30\,ft away), larger wire should be used to compensate for voltage drop.
  • Strain Relief: Strain supports are required in vertical raceways every 100ft100\,ft. Fastening should begin at the lowest point and work upward to adjust tension.

Specialized Elevators and Dumbwaiters

  • LULA (Limited Use/Limited Access):
    • Max Rise: 25ft25\,ft
    • Max Speed: 30ft/min30\,ft/min
    • Max Capacity: 1400lbs1400\,lbs
    • Max Platform Area: 18sq/ft18\,sq/ft
  • Residential Elevators:
    • Max Rise: 50ft50\,ft
    • Max Speed: 40ft/min40\,ft/min
    • Max Capacity: 940lbs940\,lbs
    • Max Platform Area: 19sq/ft19\,sq/ft
    • Escape Hatch: Not required unless manual operation is not provided.
  • Dumbwaiters:
    • Max Platform Area: 9sq/ft9\,sq/ft
    • Max Inside Height: 4ft4\,ft
    • Max Capacity: 500lbs500\,lbs
    • Note: No riders permitted. If working on top, the main line must be OFF and work performed only partially in.

Hydraulic Systems and Calculations

  • Mathematical Constants: π3.1416\pi \approx 3.1416; there are 231in3231\,in^3 in a Gallon.
  • Area of a Plunger: A=π×r2A = \pi \times r^2.
    • If diameter is 10in10\,in, radius (rr) is 5in5\,in.
    • A=3.1416×52=78.54in2A = 3.1416 \times 5^2 = 78.54\,in^2.
  • Volume and Oil Calculation:
    • Example: Moving a 6in6\,in jack (radius 3in3\,in) for 25ft25\,ft (300in300\,in).
    • A=3.1416×32=28.27in2A = 3.1416 \times 3^2 = 28.27\,in^2
    • V=A×H=28.27×300=8481in3V = A \times H = 28.27 \times 300 = 8481\,in^3
    • Gallons=8481÷231=36.71gallonsGallons = 8481 \div 231 = 36.71\,gallons.
  • Hydraulic Valves:
    • Relief Valve: Tested annually. Relieves pressure if car hits an obstruction, is overloaded, or hits the stop ring.
    • Check Valve: One-way valve allowing oil flow only in one direction.
    • Up Valve: Controls up start, acceleration, high speed, slowdown, leveling, and stop.
    • Down Valve: Depends on system pressure as the elevator motor does not run in the down direction.
    • Bypass and Relief: Often combined into a single unit.
  • Tests:
    • Category 1 Oil Buffer Test: Plunger must return to normal position within 90seconds90\,seconds.
    • Static Load Test: Performed on unexposed cylinders annually. Hold empty car for 15minutes15\,minutes; movement suggests an underground leak.

Electronics and Circuitry

  • Amplifiers (Op Amps):
    • Inverting: Input is supplied to the Negative terminal.
    • Non-Inverting: Input is supplied to the Positive terminal.
  • SCR (Silicon Controlled Rectifier):
    • Three-terminal device pulsing the gate with positive voltage to act as a switch.
    • Remains ON until anode/cathode voltages equalize, are reverse biased, or voltage is removed.
    • Testing: Positive lead on Anode, negative on Cathode, jumper between Anode and Gate. A good SCR shows 0.7V0.7\,V. Shorted SCRs show low resistance between anode and cathode when tested with an ohmmeter.
  • Logic Gates:
    • AND Gate: Output is High (1) ONLY when all inputs are High.
    • Exclusive OR (XOR): Output is High if any but NOT ALL inputs are High (Comparator gate).
  • Timing Circuits:
    • OFF Delay: Timing begins when current is removed. Relay picks immediately when switch closes.
    • ON Delay: Relay is delayed until capacitors are charged. Capacitors are connected in parallel.

Control Systems

  • Ward Leonard System:
    • Uses a closed loop between generator and hoist motor armatures.
    • Car speed is controlled by the amount of current in the generator shunt field.
    • Provides nearly constant speed under changing loads and regenerates power.
    • If all three contacts close in the diagram, it runs high speed.
  • Inductance in DC Brake Circuits:
    • R1: Controls the rate the magnetic field builds (time to energize/lift brake).
    • R2: Located in the discharge path; controls the time to set the brake and suppresses voltage spikes.
  • Series Brake Circuit: Uses a resistor to limit initial current. Contact E opens to insert more resistance once the brake is lifted, preventing coil saturation.

Troubleshooting and Safety Inspections

  • Noise Issues: If a hoist motor is making noise, inductors can be used on the AC input to filter "notch effect" or provide isolation. A growling/humming 3-phase motor that stalls may have a cracked/loose rotor bar.
  • Blowing Fuses: A car blowing a 3A3\,A fuse at the same point in the hoistway suggests an exposed traveling cable.
  • Phasing: A reverse phase relay detects loss of phase or phase reversal in building power.
  • Door Problems:
    • If an elevator runs with center opening doors partially open, the gate switch was likely activated but the relating device failed.
    • Mechanical safety edges bumping at center opening suggests issue with the safety edge retracting mechanism.
    • Closing force limit for passenger doors per ANSI Rule 112.3: Max 30lbs30\,lbs. (If at 50lbs50\,lbs, it is out of compliance).
  • Encoder Issues: A sawtooth waveform on an oscilloscope indicates a fault; a perfect encoder produces a square wave.
  • Escalator Errors: An escalator falling 10in10\,in short usually indicates an incorrect benchmark or column line.

Equipment and Maintenance

  • Measuring Tools:
    • Micrometer: US Mike reads in thousandths of an inch (0.001in0.001\,in); Metric reads in hundredths of a millimeter (0.01mm0.01\,mm).
    • Caliper Rule: Used to measure the outside diameter of a pipe.
    • Convert Inches: 1inch=2.54cm=25.4mm1\,inch = 2.54\,cm = 25.4\,mm.
  • Rail Data:
    • Standard rail length is 16ft16\,ft.
    • Weight Calculation: For 15 full 16lb16\,lb rails plus two 8ft8\,ft sections: (15×16)+(1×16)=16 total rails×16lbs=4096lbs(15 \times 16) + (1 \times 16) = 16 \text{ total rails} \times 16\,lbs = 4096\,lbs.
  • Oil Types: Use non-detergent, single viscosity gear oil for machines.
  • Escalator Safety:
    • Max angle of Moving Walkway: 1212^{\circ}.
    • Max angle of Escalator: 3030^{\circ}.
    • Step Level (Sag) Switch: Trips if step sags more than 1/8in1/8\,in.
    • Demarcation lights provide visual indication for entering/exiting.
    • Skirt panel clearance: No more than 3/16in3/16\,in.

Fire and Chemicals

  • NFPA Labels:
    • Red Square (4): Severe fire hazard.
    • Yellow Square (0): Not reactive.
  • Fire Classes: Class C extinguishers are for electrical equipment (motors/switches).
  • Elements of Fire: Fuel, Oxygen, Heat.
  • MSDS: Material Safety Data Sheets can be demanded from your elevator company Superintendent or Manager.

Questions & Discussion

  • Q: How many points of contact on a ladder?
    • A: 3 points of contact must be maintained. Ladders should extend 3ft3\,ft above the landing.
  • Q: What is the tripping speed for safeties?
    • A: Minimum tripping speed is not less than 115%115\% of rated speed. (e.g., 500fpm×1.15=575fpm500\,fpm \times 1.15 = 575\,fpm). All elevators above 150fpm150\,fpm require an overspeed switch.
  • Q: What to do if a coworker smells of alcohol?
    • A: Take action by informing the mechanic in charge, business representative, or supervisor.
  • Q: Which drill method for soft soil?
    • A: Rotary (Auger) drill. Use Percussion Rotary with a Button Bit for hard rock.
  • Q: Minimum clearance between facing controllers at 500V?
    • A: 36inches36\,inches.
  • Q: Total PI's for a 12-floor building with 3 cars where 3 floors don't get PI's?
    • A: (12×3)(3×3)=369=27(12 \times 3) - (3 \times 3) = 36 - 9 = 27 PI's.
  • Q: Formula for 3-phase Transformer KVA?
    • A: KVA=V×I×1.7321000KVA = \frac{V \times I \times 1.732}{1000}.