Elevator Mechanic Exam Vocabulary Flashcards
Latching Relays and Electrical Identification
- Definition and Usage: Latching relays are used for call registration, direction selection, or as selector relays.
- Types: There are two primary types of latching relays:
- Set/Reset: These are electrical latching relays.
- Mechanical: These are mechanical latching relays.
- Symbol Recognition: The symbol for a latching relay is a box containing a shaded triangle located in the lower right-hand corner.
- RPM Calculation: To determine the Revolutions Per Minute (RPM), use the following procedure:
- Step 1: Multiply the constant 60 by the Frequency (f) in Hertz (Hz).
- Step 2: Divide the number of Poles (P) by 2.
- Step 3: Divide the result of Step 1 by the result of Step 2.
- Formula: RPM=P÷260×f
Resistance and Insulation Testing
- Megohm Meter (Megger):
- Used to test the insulation properties of electric wiring, motor windings, and high-power antenna mounts.
- Often referred to as "megging out" or using a "megger" to identify if equipment or wiring is shorted to ground or the frame.
- Characteristics: It utilizes significantly higher voltages to check resistance than a standard Volt-ohm meter.
- Minimum Resistance: The acceptable minimum resistance for insulation is 1MΩ.
Shunt and Overload Components
- Shunt Overload Definitions:
- (1) A parallel connection.
- (2) A resistive element placed across armature terminals to bypass a portion of the current.
- (3) A flexible electrical conductor designed to conduct current around mechanical joints between two conductors.
- (4) A resistive element (usually very low resistance) used in parallel with a DC ammeter movement to bypass a calibrated portion of the total circuit current.
- Temporary Run Box Hazards: Getting shocked while using a temporary run box is typically indicative of a bad ground.
Rigging and Hoisting Procedures
- Bridle Hitch:
- Consists of two, three, or four single hitches used together to hoist an object.
- Load Stress vs. Sling Angle:
- A sling with two legs lifting a 1,000lb object at a 90∘ angle results in a load of 500lb per leg.
- If the angle decreases to 30∘, the stress increases to 1,000lb on each leg.
- Safety Recommendation: Sling angles should be kept greater than 45∘. Angles approaching 30∘ are extremely hazardous and must be avoided.
- Lifting Materials: Hoisting materials should be checked for defects before every pick.
- Eye Bolts: To determine the Safe Working Load (SWL), check if the eye bolt is being used for in-line loading (never use eye bolts for non-in-line hoisting).
- Clevis Usage: When using a clevis with a screw-type pin, the pin must be tightened and inspected before each lift.
Scaffolding and Fall Protection
- Securement: Scaffolding must be tied to the structure using #9 wire or specific tie-in devices.
- Tie-off Requirements:
- The first vertical tie must be at a maximum height of 4 times the narrowest base dimension.
- Additional vertical ties must not exceed 26ft apart.
- Maximum horizontal distance between ties must not exceed 30ft.
- Load Capacity: OSHA requires scaffolds to support 4 times their maximum intended load.
- Plank Stability: Planks used in shaftway scaffolding must have cleats to prevent movement.
- Personal Fall Arrest System (PFAS):
- Components: Anchorage, Lanyard, and Body Harness.
- Lanyard length is typically 6ft.
- PFAS must be inspected before each use.
- Anchorage must be independent and capable of supporting 5,000lbs per worker attached.
- Fall Protection Threshold: OSHA requires fall protection when working on scaffolding at or above 10ft from the ground.
- Barricades: Safety barricades across hoistway openings should be installed after rough or finished floors are in place. Top rails should be at 42in, mid-rails at 21in, and include a 3in toe board.
Car Specifications and Counterweights
- Counterweight Balance: Counterweights are typically hung to balance the empty car weight plus 40% of the capacity load.
- Example Calculation: If a car weighs 7,000lbs with a capacity of 3,500lbs:
- 40% of 3,500=1,400lbs
- Total Counterweight = 7,000+1,400=8,400lbs.
- Modernization Weight Changes: If adding 5% to a 10,000lb counterweight frame:
- 10,000×0.05=500lbs
- New weight = 10,500lbs.
- Guide Shoes: On a traction elevator, bottom guide shoes or roller guides are fastened to the safety plank.
Wiring and Cabling
- Wire Sizing Standards:
- Minimum size for wires in traveling cables is #20.
- Minimum size for wires outside of travelers is #24.
- The largest wires are the feeders for the hoist or pump motor.
- Spare Wires: A 10% spare wire count is standard when pulling wire.
- Calculation for 52 wires: 52×0.10=5.2 (order 6 spares).
- Traveling Cable Installation:
- The loop should be at least 30 times the cable diameter.
- Vertical suspension must be a minimum of 4ft at both the hoistway and car hanger attachments before the loop forms.
- If replacing a cable with a different size, the hanger must be adjusted "post-wise" to ensure the loop clears the platform edge.
- Voltage Drop: If a controller is moved (e.g., 30ft away), larger wire should be used to compensate for voltage drop.
- Strain Relief: Strain supports are required in vertical raceways every 100ft. Fastening should begin at the lowest point and work upward to adjust tension.
Specialized Elevators and Dumbwaiters
- LULA (Limited Use/Limited Access):
- Max Rise: 25ft
- Max Speed: 30ft/min
- Max Capacity: 1400lbs
- Max Platform Area: 18sq/ft
- Residential Elevators:
- Max Rise: 50ft
- Max Speed: 40ft/min
- Max Capacity: 940lbs
- Max Platform Area: 19sq/ft
- Escape Hatch: Not required unless manual operation is not provided.
- Dumbwaiters:
- Max Platform Area: 9sq/ft
- Max Inside Height: 4ft
- Max Capacity: 500lbs
- Note: No riders permitted. If working on top, the main line must be OFF and work performed only partially in.
Hydraulic Systems and Calculations
- Mathematical Constants: π≈3.1416; there are 231in3 in a Gallon.
- Area of a Plunger: A=π×r2.
- If diameter is 10in, radius (r) is 5in.
- A=3.1416×52=78.54in2.
- Volume and Oil Calculation:
- Example: Moving a 6in jack (radius 3in) for 25ft (300in).
- A=3.1416×32=28.27in2
- V=A×H=28.27×300=8481in3
- Gallons=8481÷231=36.71gallons.
- Hydraulic Valves:
- Relief Valve: Tested annually. Relieves pressure if car hits an obstruction, is overloaded, or hits the stop ring.
- Check Valve: One-way valve allowing oil flow only in one direction.
- Up Valve: Controls up start, acceleration, high speed, slowdown, leveling, and stop.
- Down Valve: Depends on system pressure as the elevator motor does not run in the down direction.
- Bypass and Relief: Often combined into a single unit.
- Tests:
- Category 1 Oil Buffer Test: Plunger must return to normal position within 90seconds.
- Static Load Test: Performed on unexposed cylinders annually. Hold empty car for 15minutes; movement suggests an underground leak.
Electronics and Circuitry
- Amplifiers (Op Amps):
- Inverting: Input is supplied to the Negative terminal.
- Non-Inverting: Input is supplied to the Positive terminal.
- SCR (Silicon Controlled Rectifier):
- Three-terminal device pulsing the gate with positive voltage to act as a switch.
- Remains ON until anode/cathode voltages equalize, are reverse biased, or voltage is removed.
- Testing: Positive lead on Anode, negative on Cathode, jumper between Anode and Gate. A good SCR shows 0.7V. Shorted SCRs show low resistance between anode and cathode when tested with an ohmmeter.
- Logic Gates:
- AND Gate: Output is High (1) ONLY when all inputs are High.
- Exclusive OR (XOR): Output is High if any but NOT ALL inputs are High (Comparator gate).
- Timing Circuits:
- OFF Delay: Timing begins when current is removed. Relay picks immediately when switch closes.
- ON Delay: Relay is delayed until capacitors are charged. Capacitors are connected in parallel.
Control Systems
- Ward Leonard System:
- Uses a closed loop between generator and hoist motor armatures.
- Car speed is controlled by the amount of current in the generator shunt field.
- Provides nearly constant speed under changing loads and regenerates power.
- If all three contacts close in the diagram, it runs high speed.
- Inductance in DC Brake Circuits:
- R1: Controls the rate the magnetic field builds (time to energize/lift brake).
- R2: Located in the discharge path; controls the time to set the brake and suppresses voltage spikes.
- Series Brake Circuit: Uses a resistor to limit initial current. Contact E opens to insert more resistance once the brake is lifted, preventing coil saturation.
Troubleshooting and Safety Inspections
- Noise Issues: If a hoist motor is making noise, inductors can be used on the AC input to filter "notch effect" or provide isolation. A growling/humming 3-phase motor that stalls may have a cracked/loose rotor bar.
- Blowing Fuses: A car blowing a 3A fuse at the same point in the hoistway suggests an exposed traveling cable.
- Phasing: A reverse phase relay detects loss of phase or phase reversal in building power.
- Door Problems:
- If an elevator runs with center opening doors partially open, the gate switch was likely activated but the relating device failed.
- Mechanical safety edges bumping at center opening suggests issue with the safety edge retracting mechanism.
- Closing force limit for passenger doors per ANSI Rule 112.3: Max 30lbs. (If at 50lbs, it is out of compliance).
- Encoder Issues: A sawtooth waveform on an oscilloscope indicates a fault; a perfect encoder produces a square wave.
- Escalator Errors: An escalator falling 10in short usually indicates an incorrect benchmark or column line.
Equipment and Maintenance
- Measuring Tools:
- Micrometer: US Mike reads in thousandths of an inch (0.001in); Metric reads in hundredths of a millimeter (0.01mm).
- Caliper Rule: Used to measure the outside diameter of a pipe.
- Convert Inches: 1inch=2.54cm=25.4mm.
- Rail Data:
- Standard rail length is 16ft.
- Weight Calculation: For 15 full 16lb rails plus two 8ft sections: (15×16)+(1×16)=16 total rails×16lbs=4096lbs.
- Oil Types: Use non-detergent, single viscosity gear oil for machines.
- Escalator Safety:
- Max angle of Moving Walkway: 12∘.
- Max angle of Escalator: 30∘.
- Step Level (Sag) Switch: Trips if step sags more than 1/8in.
- Demarcation lights provide visual indication for entering/exiting.
- Skirt panel clearance: No more than 3/16in.
Fire and Chemicals
- NFPA Labels:
- Red Square (4): Severe fire hazard.
- Yellow Square (0): Not reactive.
- Fire Classes: Class C extinguishers are for electrical equipment (motors/switches).
- Elements of Fire: Fuel, Oxygen, Heat.
- MSDS: Material Safety Data Sheets can be demanded from your elevator company Superintendent or Manager.
Questions & Discussion
- Q: How many points of contact on a ladder?
- A: 3 points of contact must be maintained. Ladders should extend 3ft above the landing.
- Q: What is the tripping speed for safeties?
- A: Minimum tripping speed is not less than 115% of rated speed. (e.g., 500fpm×1.15=575fpm). All elevators above 150fpm require an overspeed switch.
- Q: What to do if a coworker smells of alcohol?
- A: Take action by informing the mechanic in charge, business representative, or supervisor.
- Q: Which drill method for soft soil?
- A: Rotary (Auger) drill. Use Percussion Rotary with a Button Bit for hard rock.
- Q: Minimum clearance between facing controllers at 500V?
- A: 36inches.
- Q: Total PI's for a 12-floor building with 3 cars where 3 floors don't get PI's?
- A: (12×3)−(3×3)=36−9=27 PI's.
- Q: Formula for 3-phase Transformer KVA?
- A: KVA=1000V×I×1.732.