Electrical Conductors
Conductor Materials
- Copper and Aluminum are most commonly used for wiring.
Copper
- Pros:
- Low resistance, more current/area, smaller wire sizes.
- Cons:
- More expensive, price volatility.
Aluminum
- Pros:
- Less expensive, lighter, more flexible, easier to install.
- Cons:
- Greater thermal expansion/contraction, less current/area, larger wire sizes required.
- Not for under 100A due to device ratings and arcing.
Conductor Types
- Solid: Used for smaller wire sizes (#10 and smaller).
- Stranded: Used for #8 and larger.
Conductor Insulation
- Table 310.4(1) lists insulation types for conductors rated 600V.
- Common types:
- TW: Dry and wet locations, 60°C.
- THW: Moisture and heat resistant, dry and wet locations, 75°C (special applications 90°C).
- THHN: High heat resistant, dry and damp locations, nylon jacket, 90°C.
- THWN: Moisture and heat resistant, dry and wet locations, nylon jacket, 75°C.
- THWN-2: Moisture and heat resistant, dry and wet locations, nylon jacket, 90°C.
- XHHW: Moisture resistant, dry and damp locations 90°C, wet locations 75°C.
- Key:
- T = Thermal resistant
- W = Wet location
- N = Nylon
- X = Cross-linked polyethylene insulation
Conductor Ampacities
- Function of Material (Copper vs Aluminum) and Type of insulation.
- Function of:
- Physical size (AWG or kcmil)
- Total length of conductor (total Z of the circuit)
- Location
- Table 310.16 shows sizes and ampacities.
NEC 110.14(C) Temperature Limitations
- Conductors connected to devices <= 100A: limited to 60°C.
- Conductors connected to devices > 100A: limited to 75°C.
- 90°C column may only be used for ampacity adjustments and corrections.
Guidelines
- Copper:
- Loads <= 100A: use 60°C column.
- Loads > 100A: use 75°C column.
- Minimum #12, Maximum 600kcmil
- Aluminum:
- Loads >= 100A only
- Max 750kcmil
Multiple Sets
- Large loads require multiple sets of conductors.
- All conductors must be equal size.
Ambient Temperature Correction Factor
- If ambient temperature > 30°C (86°F), use correction factor from Table 310.15 (B)(1)(1).
- Rooftop: Add 33°C or 60°F to outdoor ambient temperature if conduit is < ¾-inches above the roof.
- If more than 3 current carrying conductors are in one conduit, use Table 310.15(C)(1) to adjust ampacity.
- Exclude neutral and grounding conductors in a 3-phase system.
Sizing the Equipment Grounding Conductor (EGC)
- NEC Table 250.122: EGC is sized based on the OCPD protecting the feeder/branch circuit.
Identification - Industry Standards for Conductor Colors
- 208Y/120V:
- φA – Black, φB – Red, φC – Blue, Neutral – White, Equipment Ground – Green (or Bare)
- 480Y/277V:
- φA – Brown, φB – Orange, φC – Yellow, Neutral – White or Gray, Equipment Ground – Green (or Bare)
Conductor Types (Cables)
- NEC Article 334: NM (Non-metallic sheathed cable) - "Romex", typically in residential.
- NEC Article 340: UF (Underground feeder and branch-circuit cable) - Underground version of NM cable.
- NEC Article 330: MC (Metal clad cable) - Wires in a metal casing from the factory. Casing acts as the conduit.