Pilot and Overcurrent Devices
Motors are often controlled with simple stop/start buttons
A start button is a momentary make N/O contact
A stop button is a momentary break N/C contact
To add more stop buttons they must be series with each other
To add more start buttons they must be parallel with each other
Pilot devices signal a change by opening or closing a set of contacts: may be momentary or maintained
Automatic pilot devices detect a change and conver this change to the opening or closing of a set of contacts
Temperature switches are automatic pilot devices that control contacts by detecting a temperature change
Thermocouples are voltage devices that indicate a temperature by producing a change in voltage
Resistive temperature devices use resistance to indicate a change in temperature
Infrared sensors are non-contacting sensors, measures the temperature of a surface by virtue of its thermal radiation
Bimetallic devices take advantage of the expansion of metals when they are heated
Silicon diode sensors can be used over the widest variety of temperature ranges
Pressure switches is a switch with both N/O and N/C contacts connected to an actuator, some may be dual-stage and operate contacts at two predetermined pressures.
Pressure switches are drawn as if there is no pressure in the system
All switches are drawn de-energized or without any forces acting upon them
Limit switches and proximity switches have several applications:
Measuring the travel of a piece of equipment for positioning
Stopping or changing directions
Measuring the levels of solids in a container or pile
Limit switches require the actuator, level, cam, or rod to contact the object being sensed
Proximity switches can detect the object or material without contacting it
Types of proximity switches are:
Magnetic
Inductive
Capacitive
Photoelectric
Magnetic proximity switches operate by detecting the presence of an external magnetic field
Inductive proximity switches operate by creating a magnetic field and then sensing when a ferrous metal enters that field
Capacitive proximity switches operate by creating an electrostatic field and then sensing when an object enters that field
Photoelectric proximity switches operate by sensing light reflected off an object or sensing when an object interrupts a beam of light
Float switches indicate the liquid level of a vessel or tank, may be level actuated or a tethered bulb
The switching is done in the bulb itself where as level actuated is done at the termination point
Current flow creates heat and magnetism, if too much current flows, the heat generated could damage even the conductor itself, this is an overcurrent scenario
Overcurrent scenarios can be caused by either short-circuits or overloads
A short-circuit occurs in a circuit if a live ungrounded conductor contacts:
Another ungrounded conductor
A grounded conductor
Equipment that is bonded to ground
Current in a short-circuit can be extremely high because the impedance of the path is typically very low
Overload conditions is when the overcurrent is moderately higher than the normal current for that circuit, this prolonged heat can damage the circuit and conductors
An overcurrent device is any device capable of automatically opening an electric circuit under both pretermined overload and short-circuit conditions
Overcurrent devices have two ratings:
A continuous current rating: the amount of current a device will carry without exceeding a specified temperature rise
An interrupting rating: the maximum amount of current a device can safely interrupt, typically very high amounts
The two types of overcurrent devices are:
Fuses: current-senstivie device that consists of a conductor called the element, surrounded by an arc-quenching materiall called the filler
Circuit breakers: electromechanical devices that can be operated manually to de-energize a circuit and can also operate automatically in reponse to overcurrent conditions
Fuses must carry its normal load continuously without deteriorating (passive functionality) and open the circuit under overcurrent conditions (active functionality)
There are plug and cartridge fuses
Non-time delay fuses operate quickly when a circuit exceeds the current rating, they do not allow for brief overloads
The total operating time of a non-time-delay fuse can be less than one half an electrical cycle, very high short-circuit ccurrents can be cleared in less than one-quarter of an electrical cycle
Time delay fuses have a thermal cut out which responds with inverse time characteristics, higher current value less time it takes to open the circuit, vice versa. And a fuse element which opens the circuit during very high fault currents
Circuit breakers may be instantaneous trip or inverse-time
Instantaneous trip respond only to short-circuit conditions
Inverse-time circuit breakers use a bimetallic tripping element that works similar to time-delay fuses, giving the breaker inverse time characteristics
Circuit breakers have trip-free mechanisms which allows the breaker to trip even if held or locked in the on position
If fault current exceeds a device rating it may rupture causing damage to equipment
The factors affecting fault current are:
KVA kilo-volt amperes rating of the transformer
The voltage rating of the transformer secondary supplying the circuit %IZ
The percent impedence voltage of the transformer
The closer a fault is to source the less impedence there will be since the length of the fault path is shorter