Safety Instrumented Systems - Part B
Safety Instrumented Systems - Part B Notes
Rationale
- Safety instrumented systems (SIS) are crucial for reducing the risk of accidents and their consequences in industrial settings.
- Understanding the special requirements of SIS is essential for proper maintenance, troubleshooting, and configuration.
Outcome
- Upon completion of this module, you will be able to describe the principles and applications of safety instrumented systems.
Prerequisites
- Prior completion of the module "310401hA Safety Instrumented Systems - Part A" is required.
Objectives
- Select, configure, and verify an SIS system for a specific Safety Integrity Level (SIL) rating.
Introduction
- This module focuses on how to verify a safety system to ensure it performs as designed.
Objective One: Verification
- Goal: Select, configure, and verify an SIS system for a specific SIL rating.
Verification
- Control functions performed by an SIS are called Safety Instrumented Functions (SIF).
- SIFs are designed to prevent or mitigate specific hazards and are assigned a Safety Integrity Level (SIL).
- SIL rating verification requires calculating the SIF's average Probability of Failure on Demand (PFDavg).
- Hardware Fault Tolerance (HFT) of the SIF architecture must comply with its SIL rating.
- Spurious Trip Rate (STR) must meet company policy.
Methods for Calculating PFDavg (Table 1)
| Method | System Modeled | Quantification Technique | Handles Different Repair Times | Handles Diverse Technology | Handles Sequence Dependent Failures |
|---|---|---|---|---|---|
| Simplified Equations | Simple SIF equation | Simple math | No | No | No |
| Fault Tree Analysis | SIF with complex relationships | Simple math or Boolean algebra | Yes | Yes | Yes |
| Markov Analysis | SIF with complex relationships, time dependant requirements or PE logic solvers | Matrix algebra | Yes | Yes | Yes |
- Simplified Equations: Only method presented in this module.
- Fault Tree Analysis: Uses top-down diagrams representing the logical relationship between subsystem and component failures.
- Markov Analysis: Uses circles representing system states, connected by transitions (arrows) indicating paths between states.
Simplified Equations for PFD (Table 2)
Equations for Probability of Failure On Demand
| Configuration | Equation |
|---|---|
| 1oo1 | |
| 1oo1D | |
| 1oo2 | |
| 1oo2D | |
| 2oo2 | |
| 2oo3 |
Assumptions for Correct Application:
- Failure rates are constant over the functional test period.
- Failure rates for redundant components within a sensor voting group are identical.
- Full functional tests are 100% effective.
- Final control elements fail in the safe state (e.g., ESD valve fails closed).
- Automatically diagnosed failures cause the SIF to take automatic action or degrade to a mode where the SIF can take safety action automatically.
- Mean Time To Repair (MTTR) is the time to repair any detected failure.
SIL Rating Based on PFDavg (Table 3)
| Safety Integrity Level (SIL) | PFDavg | Risk Reduction Factor (RRF) |
|---|---|---|
| SIL 4 | 0.00001 to 0.0001 | 10,000 to 100,000 |
| SIL 3 | 0.0001 to 0.001 | 1,000 to 10,000 |
| SIL 2 | 0.001 to 0.01 | 100 to 1,000 |
| SIL 1 | 0.01 to 0.1 | 10 to 100 |
Simplified Equations for Spurious Trip Rate (STR) (Table 4)
| Configuration | Equation |
|---|---|
| 1oo1 | |
| 1oo2 | |
| 2oo2 | |
| 2oo3 |
Assumptions for Correct Application:
- Failure rates are constant over the functional test period.
- Failure rates for redundant components within a sensor voting group are identical.
- Final control elements fail in the safe state.
- Diagnosed dangerous failure puts the SIF in a safe state via automatic or human intervention.
Limitations of Simplified Equations
- They do not account for partial proof test calculations, varying degrees of diagnostic coverage, or other factors.
- More complex formulas are required for these calculations.
SIL Rating for Components (Table 5)
- Determined by component type (A or B), architecture, and Safety Failure Fraction (SFF) rating.
- The lowest rating of any component dictates the overall allowed SIL.
Type A Components
- Simple devices with well-known failure modes and a solid history of operation.
| SFF | HFT of 0 | HFT of 1 | HFT of 2 |
|---|---|---|---|
| < 60% | SIL 1 | SIL 2 | SIL 3 |
| 60% to <90% | SIL 2 | SIL 3 | SIL 4 |
| 90% to <99% | SIL 3 | SIL 4 | SIL 4 |
| >99% | SIL 3 | SIL 4 | SIL 4 |
Type B Components
- Complex components with potentially unknown failure modes.
| SFF | HFT of 0 | HFT of 1 | HFT of 2 |
|---|---|---|---|
| < 60% | Not allowed | SIL 1 | SIL 2 |
| 60% to <90% | SIL 1 | SIL 2 | SIL 3 |
| 90% to <99% | SIL 2 | SIL 3 | SIL 4 |
| >99% | SIL 3 | SIL 4 | SIL 4 |
Distillation Fired Heater Reboiler Example
- A refinery is installing a new processing unit with a distillation column heated by a gas-fired heater reboiler (Figure 1).
Scenario
- The amount of vapor generated is sensitive to the vapor/liquid temperature in the column.
- Malfunctions leading to excessive heat input can generate excessive vapor amounts.
- Cooling systems may lack the capacity to control pressure during excess heat input.
- Vapor release from a column rupture can cause an explosion when contacting the fired heater.
Task
- Select, configure, and verify a column pressure SIS.
Steps
- Risk assessment
- Conceptual design verification
- Redesign verification
- SRS specifications
Risk Assessment
Identified Risks
- Column rupture likelihood: Occasional.
- Explosion severity to personnel: Severe (two fatalities).
- Explosion severity to the environment: Minor (minor on-site release).
- Explosion severity to commercial aspects: Severe (equipment damage > 20 million).
Risk Matrix Assignment
- Medium risk, requiring a SIL 2 SIS installation.
Layer of Protection Analysis (LOPA)
- Acceptable risk level for an explosion: 10^{-4} occurrences per year.
- Initiating event: Overheating due to fuel control valve failure.
- Process risk level for fuel valve failure: Once every two years.
- Mechanical pressure relief valve risk reduction: 10 (credit of 0.1).
- Alarms and operator response risk reduction: 10 (credit of 0.1).
- BPCS risk reduction: None (failure of its control valve is the initiating event).
Required Risk Reduction
- The risk reduction that the SIS system requires is 200 times or a PFD of 0.005, which you calculate as follows.
- PFD = (10^{-4} / yr) / ((2 / yr)(0.1)(0.1)) = 0.005
- A PFD of 0.005 requires an SIL 2 SIS installation.
Nuisance Trips and Shutdowns
- Nuisance trips should occur less than once every three years (STR < 0.33 failures/yr).
- Planned shutdowns occur once every three years.
Conceptual Design Verification
Initial SIF Design (Figure 2)
- Pressure SIS transmitter (PZT-8) to measure column pressure.
- Fail-closed (FC) pressure SIS valve (PZV-8) to shut off fuel supply.
- Safety PLC logic solver:
- Alarm (PZAH-8) to BPCS for high column pressure.
- Automatic closure of ESD fuel valve (PZV-8) at trip point.
Equipment Failure Rates (Table 6)
- Failure rates are given in failures per billion hours (FIT).
| Instrument | λSU (FIT) | λSD (FIT) | λDD (FIT) | λDU (FIT) |
|---|---|---|---|---|
| Pressure transmitter | 0 | 250 | 750 | 120 |
| Solenoid de-energize to trip | 0 | 6690 | 0 | 2900 |
| Ball valve, tight shut-off | 0 | 2153 | 0 | 2378 |
| Safety PLC | 990 | 0 | 509 | 7 |
Reliability Block Diagram (RBD) (Figure 3)
- Calculates PFDavg, STRSIS, and overall allowed SIL rating.
Design Information
- Simplex architecture (1oo1) for pressure transmitter, safety PLC, solenoid, and ESD valve.
- Common Cause Factor (CCF) beta (β) factor of 0% due to no redundancy.
- Proof test interval (TI) of one year (8760 hours) for sensors and final elements.
- Proof TI of three years (26,280 hours) for the logic solver.
Initial Design Limitations
- Insufficient risk reduction.
- PFDavg of 2.37 E-02 (0.0237) exceeds the required 0.005.
- Inadequate nuisance trip reduction.
- STRSIS of 1.05 failures/yr, exceeds the required 0.33 failures/yr.
- Overall allowed SIL 1 rating, lower than the required SIL 2.
PFD Calculation
- PFDavg is the sum of PFD calculations for each component (Table 2 formulas).
Example: ESD Ball Valve (1oo1 Architecture)
PFD = 2 * λDU * TI
λDU = 2378 E-09 failures/hr, TI = 8760 hr
PFD = (2 * 2378 E-09) * 8760 = 1.04 E-02
STR Calculation
- STRSIS is the sum of STR calculations for each component (Table 4 formulas).
Example: Pressure Transmitter (1oo1 Architecture)
- STR = λS + λDD
- λDD = 750 E-09 failures/hr, λS = 250 E-09 failures/hr
- STR = (750 E-09 + 250 E-09) = 1.00 E-06
SIL Rating Determination
- Using Table 5, based on component type, architecture, and SFF rating. The lowest SIL rating component counts.
Example: Safety PLC
Type B component, 1oo1 architecture (HFT of 0).
SFF = 1 - (λDU / λ)
λDU = 7 E-09 failures/hr
λ = λDD + λDU + λS = (509 E-09) + (7 E-09) + (990 E-09) = 1.51 E-06
SFF = 1 - (7E-09 / 1.51E-06) = 1 - 0.005 = 0.995 PFD = [(1-β) × (λDU ×TI)^2] / 3 + (β×λDU × TI) / 2
B = 0.05
λDU =5800 E-09 failures/hr
TI = 8760 hr
PFD = [(1-0.05)x((5800 E-09)x(8760))^2] / 3 + (0.05x(5800 E-09)x(8760)) / 2= 2.08 E-03
STR Calculation
STR for the solenoid valves is calculated as such:
λDD = 0 failures/hr
λs = 6690 E-09 failures/hr
MTTR is 72 hours.
B=0.05
STR = (2x(6690 E-09) ((6690 E-09)+(0))x (72))+(0.05) x ((6690 E-09)+(0)) = 3.4 E-07
The STR rate is now doubled because of the 2001 architecture; therefore, the STR equals 6.8 E-7 for the solenoid valves.
SIL Rating
- The overall SIL rating is equal to the lowest SIL rating of any component (Table 5).
- For example, calculate the SIL allowed for the ESD Valve. In this example, the ESD valve is a type A component and the ESD valve has 1oo2 architecture that provides an HFT of one (1).
λDU =2378 E-09 failures/hr
λ = λDD + λDU +λs = (0) + (2378 E-09)+(2153 E-09) = 4531 E-06
SFF = 1- (λDU / λ) = 1- (2378 E-09) / (4531 E-09) =1-0.525 = 0.475 PFD = [(1-β) × (λDU ×TI)^2] / 3 + (β×λDU × TI) / 2
β= 0.03
λDU = 20500 E-09 failures/hr
TI = 8760 hr
The STR for lool architecture is as follows:
STR = (λS + λDD)
λDD is 131 E-09 failures/hr
λ is 118 E-09 failures/hr
The switch's 2oo3 architecture provides an HFT of one (1).
λDU =24 E-09 failures/hr
λ = λDD + λDU +λs = (131 E-09)+(24 E-09)+(118 E-09) = 273 E-09
SFF = 1- (λDU / λ) = 1- (24 E-09) / (273 E-09) =1-0.088 = 0.91$$ or 91%
An SFF of 90 to 99% and a HFT of one for a type A component allows for a SIL rating of four (4).
- a) PFDavg = 2.18E-03, SIL 2
b) STRSIS 0.171 failures per year
c) SIL 2