NEC Article 210 Branch Circuits pt1
NEC Article 210 Branch Circuits
210.1 General Provisions
- Article 210 provides general requirements for branch circuits.
- Covers any circuit protected by a breaker that supplies power to other parts of a circuit.
210.3 Other Articles for Specific Purpose Branch Circuits
- Table 210.3 lists references for specific equipment and applications (not in Chapters 5, 6, and 7) that amend or supplement the requirements in Article 210.
- Specific circuits have their own amendments and specific requirements.
- Examples of specific purpose branch circuits from Table 210.3:
- Air conditioning and refrigerating equipment: Sections 440.6, 440.31, and 440.32
- Busways: Section 368.17
- Central heating equipment (other than fixed electric space heating equipment): Section 422.12
- Fixed heating or fixed electric heating equipment for pipelines and vessels: Section 427.4
- Fixed electric space heating equipment: Section 424.3
- Fixed outdoor electrical deicing and snow melting equipment: Section 426.4
- Infrared lamp industrial heating equipment: Sections 422.48 and 424.3
- Motors, motor circuits, and controllers: Article 430
- Switchboards and panel boards: Section 408.52
- This table provides a quick reference to find information regarding installation and amendments for special purpose branch circuits.
210.4 Multi-Wire Branch Circuits
210.4(A) General
- Branch circuits recognized by this article are permitted as multi-wire circuits.
- Multi-wire circuits can be considered as multiple circuits.
- All conductors of a multi-wire branch circuit must originate from the same panel board or similar distribution equipment.
- Typical branch circuit consists of a hot (ungrounded) and a neutral (grounded) conductor, plus a grounding conductor.
- In 3-phase 4-wire Y connected power systems supplying non-linear loads, the power system design may need to account for high harmonic currents on the neutral conductor.
- Delta and Y type transformer configurations exist for 3-phase systems.
- A delta transformer looks like a triangle, while a Y transformer looks like a Y, with the neutral coming from the center point.
- Unbalanced loading in a Y configuration can cause unbalanced current on the neutral, creating harmonics or noise.
- Circuit design should balance loads to avoid unnecessary noise on the circuitry.
- See 300.13(B) for continuity of grounded conductors on multi-wire circuits.
- 300.13(B) states that the continuity of a circuit should not rely on a device. The grounded circuit needs a solid mechanical connection that doesn't rely on a device.
210.4(C) Line to Neutral Loads
- Multi-wire branch circuits should only supply line to neutral loads.
- Exception 1: A multi-wire branch circuit can supply only one utilization equipment, such as an electric oven or clothes dryer, using two phases.
- These appliances require extra power for heating elements.
- Exception 2: Where all ungrounded conductors of the multi-wire branch circuit are opened simultaneously by the branch circuit overcurrent device.
- Multiple hots can share the same neutral if a handle tie is used.
- A handle tie is a breaker that trips or shuts off both loads mechanically at the same time.
- If Circuit 1 and Circuit 3 share a neutral, and Circuit 1 is turned off while Circuit 3 is on, the unbalanced load on the neutral can backfeed through the neutral on Circuit 1 and shock the person servicing the equipment.
- Breaker tie rule became an actual requirement around 2008.
- Previously, multiple circuits sharing one neutral was called