NEC Article 210 Branch Circuits pt1

NEC Article 210 Branch Circuits

210.1 General Provisions

  • Article 210 provides general requirements for branch circuits.
  • Covers any circuit protected by a breaker that supplies power to other parts of a circuit.

210.3 Other Articles for Specific Purpose Branch Circuits

  • Table 210.3 lists references for specific equipment and applications (not in Chapters 5, 6, and 7) that amend or supplement the requirements in Article 210.
  • Specific circuits have their own amendments and specific requirements.
  • Examples of specific purpose branch circuits from Table 210.3:
    • Air conditioning and refrigerating equipment: Sections 440.6, 440.31, and 440.32
    • Busways: Section 368.17
    • Central heating equipment (other than fixed electric space heating equipment): Section 422.12
    • Fixed heating or fixed electric heating equipment for pipelines and vessels: Section 427.4
    • Fixed electric space heating equipment: Section 424.3
    • Fixed outdoor electrical deicing and snow melting equipment: Section 426.4
    • Infrared lamp industrial heating equipment: Sections 422.48 and 424.3
    • Motors, motor circuits, and controllers: Article 430
    • Switchboards and panel boards: Section 408.52
  • This table provides a quick reference to find information regarding installation and amendments for special purpose branch circuits.

210.4 Multi-Wire Branch Circuits

210.4(A) General

  • Branch circuits recognized by this article are permitted as multi-wire circuits.
  • Multi-wire circuits can be considered as multiple circuits.
  • All conductors of a multi-wire branch circuit must originate from the same panel board or similar distribution equipment.
  • Typical branch circuit consists of a hot (ungrounded) and a neutral (grounded) conductor, plus a grounding conductor.

Informational Note 1

  • In 3-phase 4-wire Y connected power systems supplying non-linear loads, the power system design may need to account for high harmonic currents on the neutral conductor.
  • Delta and Y type transformer configurations exist for 3-phase systems.
  • A delta transformer looks like a triangle, while a Y transformer looks like a Y, with the neutral coming from the center point.
  • Unbalanced loading in a Y configuration can cause unbalanced current on the neutral, creating harmonics or noise.
  • Circuit design should balance loads to avoid unnecessary noise on the circuitry.

Informational Note 2

  • See 300.13(B) for continuity of grounded conductors on multi-wire circuits.
  • 300.13(B) states that the continuity of a circuit should not rely on a device. The grounded circuit needs a solid mechanical connection that doesn't rely on a device.

210.4(C) Line to Neutral Loads

  • Multi-wire branch circuits should only supply line to neutral loads.
  • Exception 1: A multi-wire branch circuit can supply only one utilization equipment, such as an electric oven or clothes dryer, using two phases.
  • These appliances require extra power for heating elements.
  • Exception 2: Where all ungrounded conductors of the multi-wire branch circuit are opened simultaneously by the branch circuit overcurrent device.
  • Multiple hots can share the same neutral if a handle tie is used.
  • A handle tie is a breaker that trips or shuts off both loads mechanically at the same time.
  • If Circuit 1 and Circuit 3 share a neutral, and Circuit 1 is turned off while Circuit 3 is on, the unbalanced load on the neutral can backfeed through the neutral on Circuit 1 and shock the person servicing the equipment.
  • Breaker tie rule became an actual requirement around 2008.
  • Previously, multiple circuits sharing one neutral was called