HVAC Load Estimating - Detailed Notes

CHAPTER THREE: HVAC Load Estimating

3.1 Introduction to HVAC Load Calculations

  • HVAC systems are designed to meet heating and cooling loads based on temperature and humidity.

  • Statistical data from worldwide locations is utilized by HVAC designers.

  • Outside temperature criteria for design load calculations depend upon the nature of the building.

    • If it is crucial for the system to meet demand, designers may assume the coldest recorded temperature.

    • Most buildings are not designed based on this criterion but rather a median of extremes.

3.2 Temperature Criteria for Load Calculations

  • Design temperature criteria include:

    • Heating DB (Dry Bulb)

    • Cooling DB & MCWB (Mean Coincident Wet Bulb)

  • Table 3.1 presents climatic conditions for HVAC design for St. Louis, MO, indicating various DB and MCWB values at different percentiles.

Table 3.1: Climatic Conditions for HVAC Design
  • 99.6%: 7.5°F DB

  • 99%: 12.7°F DB

  • 0.4%: 96.2°F DB, 76.7°F MCWB

  • 1%: 93.5°F DB, 76.1°F MCWB

  • 2%: 91.1°F DB, 75.0°F MCWB

  • 0.4%: 79.5°F WB, 90.9°F MCDB

Heating Load Calculation:
  • For heating systems, use mean of the coldest recorded temperatures.

  • Median value balances annual extremes above and below. Recommended for critical systems (e.g., hospitals).

  • General office environments can operate with less stringent criteria; typically using a "percent" concept based on historical frequency.

% criteria for Heating Load Calculations:
  • 99.6% value (e.g., 6°F)—statistically 0.4% of the year (35 hours) experiences temperatures below this value.

  • 99.0% value (e.g., 10°F)—statistically 1.0% of the year experiences temperature below this value (88 hours).

3.3 Designing HVAC Systems by Calculating Loads

3.3.1 Conducted Loads
  • Heat losses include conducted loads through building envelope elements (walls, roofs, windows) and outside air loads (leakage/infiltration and ventilation air).

  • Heating load calculations for conduction:

    • Heat transfer is proportional to the temperature difference between warm and cold sides of building envelope elements.

    • Basic formula:
      Q=A×TDRQ = \frac{A \times TD}{R}

    • Where:

      • QQ = heat transfer (Btuh)

      • AA = area of assembly (ft²)

      • TDTD = temperature difference (°F)

      • RR = resistance (hr-ft²-°F/Btu)

U-Factor Calculation
  • The U-factor (or U) is the tendency of an assembly to conduct heat and is the reciprocal of R.

  • Using U in heat transfer equations:
    Q=U×A×TDQ = U \times A \times TD

3.3.2 Estimating U-Factors for Building Assemblies
  • Total resistance of building assemblies can be determined by calculating the resistances of individual layers within the assembly.

  • Example: Concrete has a resistance of 0.10 hr-ft²°F per inch, leading to 8 in. of concrete providing a resistance of 0.80. Table 3.2 lists thermal resistances for representative materials.

  • The effect of air spaces and surfaces within wall assemblies is significant in estimating thermal resistance.

3.3.3 Infiltration and Ventilation Loads
  • Infiltration due to air leakage through windows and doors needs to be included in load calculations:
    Q=1.1×CFM×TDQ = 1.1 \times CFM \times TD

  • Humidification load can be calculated as follows, depending on desired and actual humidity ratios:

    • Q=4840×CFM×(W<em>roomW</em>oa)Q = 4840 \times CFM \times (W<em>{room} - W</em>{oa})

    • Where W<em>roomW<em>{room} = desired room humidity ratio, W</em>oaW</em>{oa} = outside air humidity ratio.

3.3.4 Miscellaneous Loads
  • Other losses to consider include:

    • Losses through walls below grade.

    • Through slabs on grade.

  • Analysis of exhaust systems and fresh air requirements is critical.

3.3.5 Heating Load Example (Sample Problem 3.1)
  • Problem 3.1 demonstrates methods for calculating heating and humidification loads for a small office building.

  • Given building dimensions and standard U-factors for walls, roof, windows.

Total Heat Loss = 91,700 Btuh
Total Humidification of Outside Air = 21,200 Btuh
3.4 Calculating Cooling Loads
  • Heat gains include conduction, solar effects through glazing, outside air loads, internal heat gains, etc.

3.4.1 Conducted and Solar Heat through Glazing
  • Total heat gain is represented by the equation:
    Q=U×A×TD+SC×A×SHGFQ = U \times A \times TD + SC \times A \times SHGF

  • Important terms include:

    • SHGF: Solar Heat Gain Factor (Btuh/ft²)

    • SC: Shading Coefficient (dimensionless)

3.4.2 Cooling Load Calculation for Walls and Roofs
  • The TETD must also incorporate solar heating effects:
    Q=U×A×TETDQ = U \times A \times TETD

3.4.3 Internal Heat Gains
  • Internal heat from lights, appliances, and occupants should also be included in calculations:

    • General assumptions: 250 Btuh sensible and 250 Btuh latent heat per occupant (ASHRAE standards).

3.4.6 Sample Cooling Loads Calculation (Sample Problems 3.2 and 3.3)
  • Shows heat loads in a small office building with variables in lighting, appliance loads, and U-factors.

  • Overall air-conditioning load remains largely consistent regardless of design variations.

Conclusion
  • HVAC load estimates blending calculations of heating, cooling, humidification, infiltration, and various building properties are paramount to design efficiency and comfort.