Domestic Water System Sizing Notes
Domestic Water System Sizing
- Domestic water piping is sized based on:
- Flow rate (quantity) in gallons per minute (gpm).
- Water pressure in pounds per square inch (psi).
Definitions
- Fixture Supply: Water supply pipe connected to an individual fixture.
- Branch: Piping system part, excluding riser/main/stack; combines two or more fixture supply pipes.
- Main: Principal pipe artery to which branches connect.
Fixture Supply
- Minimum flow rate/pressure for fixtures in Table 604.3.
- Maximum flow rate for fixture types in Table 604.4.
- Minimum supply pipe sizes for fixtures in Table 604.5.
Sizing of Water Piping System
- Code lacks specific domestic water system sizing method.
- Appendix E offers two methods; this class covers the uniform friction loss method.
Estimate Water Supply Demand
- Determine water supply fixture units (WSFU) for each plumbing fixture from Table E103.3(2); fixture supply pipe does not need assigned a WSFU value for sizing.
- Add WSFU’s for each branch, main, and service pipe segment toward building service.
- HOT + COLD \neq TOTAL
- Convert WSFU's to GPM using Table E103.3(3), interpolating if needed.
- Use flush valves if they account for 10% or more of total fixtures.
- Some engineers only use flush tank column for sizing hot water pipes.
- Minimum water service size = ¾”.
Water Pressure
- Plumbing fixtures need minimum water pressure to operate (psi).
- 1 FT of water (feet of head) = 0.433 psig = pressure (psig) = height (feet).
Pressure Analysis
- Water pressure changes from public main to building points due to:
- Elevation change (static head).
- Pressure loss through fittings/valves/components.
- Friction loss from pipe flow (diameter, length, GPM).
Ensuring Adequate Pressure
- Determine WSFU and GPM for each pipe segment.
- Available water pressure in municipal main (contact supplier, hydrant flow test).
- Account for pressure fluctuations; use low pressure for design.
Pressure at Worst Case Fixture
- Identify fixture needing greatest pressure (Table 604.3).
Pressure Change Due to Elevation
- Measure height from pressure source to highest fixture outlet (static head loss).
- Subtract pressure if outlet is higher.
- Add pressure if outlet is lower
- Example: 52’ x 0.433 = 22.5 psi
Pressure Loss at Tap to Main
- IPC TABLE E103.3(4).
- Based on size and flow through tap.
Pressure Loss Through Components
- Meters: Loss based on size and flow.
- Backflow Preventers: Check cut sheets for pressure loss curves.
Pipe Friction Loss
- Pressure loss per 100’ of piping, based on:
- Type, diameter, and length of pipe.
- Flow (GPM).
Maximum Velocity
- High velocity can damage piping and cause noise.
- Hot water: 11fps, Cold water:
Equivalent Length of Pipe
- Fittings/valves cause pressure loss; accounted for by equivalent pipe length, found in Table E103.3(6).
- Multiplier (1.2 to 1.5) often used for fittings/valves.
- Measure pipe length to furthest fixture.
- Determine max pressure drop allowed by pipe friction loss.
- Determine equivalent pipe length from pressure point to remote fixture (Measured length x 1.2).
- Determine max pressure drop allowed per 100’ of pipe.
- Add “do not exceed” lines to pipe pressure loss chart (velocity, max psi/100’).
- Follow GPM line until hitting a “do not exceed” line, then use pipe size to the left.
Water Pressure Concerns
- Maximum water pressure within building is 80 psi.
- Pressure reducing valve (PRV) needed if service entry pressure is higher.
- Exception: PRV not required if pressure reduces by the time water reaches fixture outlet.
- If available water pressure is too low, a booster pump may be required.