Module 5: Power System Components

Circuit Breakers

  • A switch with the capability of interrupting high current, even under fault conditions.
  • Can interrupt normal load current and fault current to protect the system.
  • Can be programmed to disconnect when current flow is too high for a specific period.
    • This feature prevents disconnection due to transient currents (e.g., inrush currents or oscillations).
    • Example settings: disconnect at 1000A in 0.1s, 500A in 0.5s, or 200A in 1s.
  • Interrupts current with high values, even short-circuit currents.

Reclosers

  • A type of circuit breaker with automatic closing capability.

  • A regular circuit breaker opens and remains open until manually closed by an operator after fault clearance.

  • Reclosers are programmed for a certain number of reclosures (e.g., four times).

  • When a fault is detected:

    • The recloser opens for a specific period.
    • It recloses automatically.
    • If the current returns to normal, it remains closed.
    • If the fault persists (high current), it reopens.
    • This open and reclose process repeats for the programmed number of cycles.
    • If the fault is not cleared after all cycles, it remains open.
  • Useful for restoring system operation with temporary faults.

    • Example: a tree branch touching a transmission line causes a temporary fault that might clear on its own or burn away.
  • Can be used with sectionalizers to clear permanent faults.

Sectionalizers

  • Used to isolate sections of a network with faults.

  • Cannot interrupt fault current; it cannot open while high current is flowing.

  • Used in conjunction with reclosers to isolate fault areas.

  • Operation:

    • The sectionalizer detects fault current but does not open immediately.
    • It waits for the recloser to open first.
    • When the sectionalizer detects the current go to zero, it opens, isolating the fault area without interrupting high current.
  • Programmable to wait for a certain number of recloser operations before opening.
    *Example

    *Grid connected to a transformer, then to a recloser (programmed to close three times).
    *Recloser output connected to a distribution network divided into two sections (Section 1 and Section 2).
    *Each section is connected through a sectionalizer.
    *Normal Operation:
    *Normal current flows from transformer through the recloser to each sectionalizer.
    *Fault in Section 1:
    *High current flows from the grid to the recloser to Section 1.
    *Sectionalizer 1 and recloser detect high current (first count).
    *Recloser opens and interrupts the current.
    *Current in sectionalizer goes to zero.
    *Sectionalizer is programmed not to open until two counts.
    *Recloser closes again to check if the fault was cleared.
    *High current is detected again (second count). Recloser opens again.
    *Current goes to zero at the recloser and sectionalizer 1.
    *After two open/close cycles, sectionalizer 1 opens (as it has counted two instances with zero current), isolating Section 1.
    *Recloser still has another cycle to try, so it closes again.
    *Since Section 1 is isolated, current flows normally from the grid to Section 2.

Isolators (Disconnecting Switches)

  • Mechanical switches without current interrupting capability.
  • Cannot be programmed to open after a certain number of faults, unlike sectionalizers.
  • Can only be opened with very low or zero current flow.
  • Used to isolate a circuit or equipment under maintenance from the live parts of the network.
  • Example: Two generators (Generator 1 and Generator 2) are connected to a busbar.
    *Isolator switches are placed before and after the busbar.
    *A circuit breaker connects to a step-up transformer leading to a transmission line.
    *Another circuit breaker and isolator are on the other side, connected to Busbar 2.
    *Maintenance scenario:
    *To take out Transformer 1 and its circuit breakers for maintenance:
    *All isolators and circuit breakers are initially closed.
    *Open the two circuit breakers first.
    *Once the current is zero, open the isolators.
    *This disconnects the circuit breakers from the voltage side.
    *The isolator isolates the circuit breaker from Busbar 1, and another isolator isolates the breaker from Busbar 2 (high voltage side).
    *With the transformer and circuit breakers isolated, maintenance can proceed.
  • Connection Sequence:
    *Close the isolator first (while the circuit breaker is open).
    *After ensuring no current will flow, close the circuit breaker.
    *Disconnection Sequence:
    *Open the circuit breaker first.
    *Then, open the isolator.
  • Never open or close the isolator while current is flowing. Always operate it at zero current.

Air Brake Switch

  • Similar to a circuit breaker but can only interrupt normal load current, not fault current.

  • Can isolate circuits, but not designed to interrupt fault currents.

  • Comparison:

    • Isolator: Cannot interrupt any current; it always opens and closes at zero current.
    • Air Breaker Switch: Can interrupt only normal current.
    • Circuit Breaker: Can interrupt normal and fault currents.
      *Arc interruption:
      *Air is used to interrupt the arc
      *As the switch opens, an arc forms in the air between the contacts

Lightning Bolts

  • Simple metal rods installed to protect equipment from lightning strikes.
  • Lightning tends to hit the highest point with the lowest impedance.
  • The metal rod is connected to the ground to discharge the lightning strike energy.
  • Prevents damage to transmission lines, transformers, and insulators.

Lightning Arrestors

  • Protects against high voltage surges from lightning strikes or sudden load disconnections.
  • Even with lightning rods, strikes can still hit transmission lines.
  • Formula: V=LdidtV = L \frac{di}{dt}, where a sudden disconnection of a heavy load can cause a high voltage spike.
  • Operation is similar to Zener diodes.
    • Under normal conditions, it has very high impedance, acting as an open circuit.
    • If the voltage reaches a certain threshold, the impedance drops significantly, creating a path to discharge the surge to the ground.
  • Also called Metal Oxide Varistor (MOV).
    • A "varistor" is a combination of "variable" and "resistor."
    • Acts as a variable resistance inversely proportional to voltage.

Potential Transformer

  • An instrument transformer used for measurement, not power delivery.
  • Measures voltage levels for protection and control devices.
  • Types:
    • Electromagnetic Type: A normal transformer with primary and secondary windings. Voltage is stepped down by the ratio N<em>1/N</em>2N<em>1/N</em>2.
    • Capacitive Voltage Transformer: Used with very high voltage transmission lines.
      • Uses a voltage divider consisting of two capacitors (C<em>1C<em>1 and C</em>2C</em>2).
      • If C<em>2C<em>2 is much higher than C</em>1C</em>1, its impedance is much smaller.
      • Voltage over C<em>2C<em>2 is much smaller compared to C</em>1C</em>1, dividing the voltage for measurement.
      • An isolated transformer is connected to the secondary side for measurement.
  • Formula: Z=1ωcZ = \frac{1}{\omega c}

Current Transformer

  • A special transformer to measure current.
  • An instrument transformer.
  • Primary winding is the conductor carrying the current to be measured (often one turn).
  • Secondary winding consists of an iron core and a high number of turns (N2N_2).
  • Relationship: I<em>1N</em>1=I<em>2N</em>2I<em>1 N</em>1 = I<em>2 N</em>2.
  • With N<em>1=1N<em>1 = 1, the secondary current I</em>2=I<em>1N</em>2I</em>2 = \frac{I<em>1}{N</em>2}.
    • Example: If I<em>1=1000I<em>1 = 1000 A in the main conductor and N</em>2=500N</em>2 = 500 turns, then I2=1000500=2I_2 = \frac{1000}{500} = 2 A.
  • Allows for easy measurement of high currents by scaling them down.

Overhead Transmission Line

  • Transmits bulk generated power from generation plants to load centers over long distances.
  • Uses high voltage to reduce transmission current, losses, and voltage drop.
  • High voltage levels range from 200 to 1200 kV.
  • Overhead lines are preferred due to the high cost of underground cables.
  • Conductors are mounted on tall towers, usually 25 to 45 meters tall.
  • Suspended by insulators to prevent connection to the ground.
    *Insulators
    *Insulators must withstand static and dynamic forces.
    *Static force: Weight of the conductor.
    *Dynamic forces: Wind, heavy rain, freezing, snow accumulation.
    *Conductors
    *Conductors should be of good conducting material (copper or aluminum).
    *Conductors should be flexible and strong.
    *Stranded wire:
    *Stranded wire is used for flexibility.
    *Construction: Small diameter conductor strands.
    *Reinforcement: Steel inner strands are used for increased strength.
    *Skin Effect:
    *AC current tends to flow in the outer diameter of the conductor at high frequencies.

Corona Discharge

  • Occurs with high voltage conductors due to ionization of the air around the conductor.

  • Formula: E=VdE = \frac{V}{d}, where E is the electric field intensity, V is the voltage, and d is the diameter of the conductor.

  • High E ionizes the gas around the conductor, leading to electrical discharge.

  • Visible as a purple light around high voltage transmission lines at night.
    *Problems
    *Leak current produces losses
    *Electromagnetic interference.
    *Damage to the conductor surface.
    *Reduction

    *Use bundled conductors
    *Bundled Conductor

    *Increasing Wire Diameter to Reduce Electric Field
    *Each conductor is still stranded with a steel reinforce middle.
    *Use of Spacers in bundled Ductors for Voltage Equalization

Static Shield Wire (Overhead Ground Wire)

  • Same function as a lightning rod for transmission lines.
  • Installed at the highest point of the transmission tower.
  • Connects to ground to discharge lightning strike energy through the tower.

Distribution Line

  • Smaller towers and lower voltage levels compared to transmission lines.

  • Surface Transformer: Steps down voltage from the distribution level to consumer voltage (100-240 V).

  • Commercial and Industrial loads often connect directly to the distribution network.
    *Voltage/Frequency Standards:

    *United States and Canada: 120 V, 60 Hz.
    *Europe, North Africa, China: 220 V, 50 Hz.
    *Japan: Both 50 Hz and 60 Hz.

Grid Control Center

  • Monitors and controls power system components in real time.
    • Generation, transmission, and distribution networks are monitored.
  • Data collected from substations, transformers, transmission lines, protection devices, and circuit breakers.
  • Control signals are sent to disconnect or reclose circuit breakers, change transformer tap settings, etc.
  • Algorithms and applications are used to predict future demand.
  • Energy Trading
    • Predict load patterns and establish energy trades between utility companies.
  • Control Center Mimic Board
    • Displays system conditions, such as power flow and transmission line status.