Module 5: Power System Components
Circuit Breakers
- A switch with the capability of interrupting high current, even under fault conditions.
- Can interrupt normal load current and fault current to protect the system.
- Can be programmed to disconnect when current flow is too high for a specific period.
- This feature prevents disconnection due to transient currents (e.g., inrush currents or oscillations).
- Example settings: disconnect at 1000A in 0.1s, 500A in 0.5s, or 200A in 1s.
- Interrupts current with high values, even short-circuit currents.
Reclosers
A type of circuit breaker with automatic closing capability.
A regular circuit breaker opens and remains open until manually closed by an operator after fault clearance.
Reclosers are programmed for a certain number of reclosures (e.g., four times).
When a fault is detected:
- The recloser opens for a specific period.
- It recloses automatically.
- If the current returns to normal, it remains closed.
- If the fault persists (high current), it reopens.
- This open and reclose process repeats for the programmed number of cycles.
- If the fault is not cleared after all cycles, it remains open.
Useful for restoring system operation with temporary faults.
- Example: a tree branch touching a transmission line causes a temporary fault that might clear on its own or burn away.
Can be used with sectionalizers to clear permanent faults.
Sectionalizers
Used to isolate sections of a network with faults.
Cannot interrupt fault current; it cannot open while high current is flowing.
Used in conjunction with reclosers to isolate fault areas.
Operation:
- The sectionalizer detects fault current but does not open immediately.
- It waits for the recloser to open first.
- When the sectionalizer detects the current go to zero, it opens, isolating the fault area without interrupting high current.
Programmable to wait for a certain number of recloser operations before opening.
*Example*Grid connected to a transformer, then to a recloser (programmed to close three times).
*Recloser output connected to a distribution network divided into two sections (Section 1 and Section 2).
*Each section is connected through a sectionalizer.
*Normal Operation:
*Normal current flows from transformer through the recloser to each sectionalizer.
*Fault in Section 1:
*High current flows from the grid to the recloser to Section 1.
*Sectionalizer 1 and recloser detect high current (first count).
*Recloser opens and interrupts the current.
*Current in sectionalizer goes to zero.
*Sectionalizer is programmed not to open until two counts.
*Recloser closes again to check if the fault was cleared.
*High current is detected again (second count). Recloser opens again.
*Current goes to zero at the recloser and sectionalizer 1.
*After two open/close cycles, sectionalizer 1 opens (as it has counted two instances with zero current), isolating Section 1.
*Recloser still has another cycle to try, so it closes again.
*Since Section 1 is isolated, current flows normally from the grid to Section 2.
Isolators (Disconnecting Switches)
- Mechanical switches without current interrupting capability.
- Cannot be programmed to open after a certain number of faults, unlike sectionalizers.
- Can only be opened with very low or zero current flow.
- Used to isolate a circuit or equipment under maintenance from the live parts of the network.
- Example: Two generators (Generator 1 and Generator 2) are connected to a busbar.
*Isolator switches are placed before and after the busbar.
*A circuit breaker connects to a step-up transformer leading to a transmission line.
*Another circuit breaker and isolator are on the other side, connected to Busbar 2.
*Maintenance scenario:
*To take out Transformer 1 and its circuit breakers for maintenance:
*All isolators and circuit breakers are initially closed.
*Open the two circuit breakers first.
*Once the current is zero, open the isolators.
*This disconnects the circuit breakers from the voltage side.
*The isolator isolates the circuit breaker from Busbar 1, and another isolator isolates the breaker from Busbar 2 (high voltage side).
*With the transformer and circuit breakers isolated, maintenance can proceed. - Connection Sequence:
*Close the isolator first (while the circuit breaker is open).
*After ensuring no current will flow, close the circuit breaker.
*Disconnection Sequence:
*Open the circuit breaker first.
*Then, open the isolator. - Never open or close the isolator while current is flowing. Always operate it at zero current.
Air Brake Switch
Similar to a circuit breaker but can only interrupt normal load current, not fault current.
Can isolate circuits, but not designed to interrupt fault currents.
Comparison:
- Isolator: Cannot interrupt any current; it always opens and closes at zero current.
- Air Breaker Switch: Can interrupt only normal current.
- Circuit Breaker: Can interrupt normal and fault currents.
*Arc interruption:
*Air is used to interrupt the arc
*As the switch opens, an arc forms in the air between the contacts
Lightning Bolts
- Simple metal rods installed to protect equipment from lightning strikes.
- Lightning tends to hit the highest point with the lowest impedance.
- The metal rod is connected to the ground to discharge the lightning strike energy.
- Prevents damage to transmission lines, transformers, and insulators.
Lightning Arrestors
- Protects against high voltage surges from lightning strikes or sudden load disconnections.
- Even with lightning rods, strikes can still hit transmission lines.
- Formula: , where a sudden disconnection of a heavy load can cause a high voltage spike.
- Operation is similar to Zener diodes.
- Under normal conditions, it has very high impedance, acting as an open circuit.
- If the voltage reaches a certain threshold, the impedance drops significantly, creating a path to discharge the surge to the ground.
- Also called Metal Oxide Varistor (MOV).
- A "varistor" is a combination of "variable" and "resistor."
- Acts as a variable resistance inversely proportional to voltage.
Potential Transformer
- An instrument transformer used for measurement, not power delivery.
- Measures voltage levels for protection and control devices.
- Types:
- Electromagnetic Type: A normal transformer with primary and secondary windings. Voltage is stepped down by the ratio .
- Capacitive Voltage Transformer: Used with very high voltage transmission lines.
- Uses a voltage divider consisting of two capacitors ( and ).
- If is much higher than , its impedance is much smaller.
- Voltage over is much smaller compared to , dividing the voltage for measurement.
- An isolated transformer is connected to the secondary side for measurement.
- Formula:
Current Transformer
- A special transformer to measure current.
- An instrument transformer.
- Primary winding is the conductor carrying the current to be measured (often one turn).
- Secondary winding consists of an iron core and a high number of turns ().
- Relationship: .
- With , the secondary current .
- Example: If A in the main conductor and turns, then A.
- Allows for easy measurement of high currents by scaling them down.
Overhead Transmission Line
- Transmits bulk generated power from generation plants to load centers over long distances.
- Uses high voltage to reduce transmission current, losses, and voltage drop.
- High voltage levels range from 200 to 1200 kV.
- Overhead lines are preferred due to the high cost of underground cables.
- Conductors are mounted on tall towers, usually 25 to 45 meters tall.
- Suspended by insulators to prevent connection to the ground.
*Insulators
*Insulators must withstand static and dynamic forces.
*Static force: Weight of the conductor.
*Dynamic forces: Wind, heavy rain, freezing, snow accumulation.
*Conductors
*Conductors should be of good conducting material (copper or aluminum).
*Conductors should be flexible and strong.
*Stranded wire:
*Stranded wire is used for flexibility.
*Construction: Small diameter conductor strands.
*Reinforcement: Steel inner strands are used for increased strength.
*Skin Effect:
*AC current tends to flow in the outer diameter of the conductor at high frequencies.
Corona Discharge
Occurs with high voltage conductors due to ionization of the air around the conductor.
Formula: , where E is the electric field intensity, V is the voltage, and d is the diameter of the conductor.
High E ionizes the gas around the conductor, leading to electrical discharge.
Visible as a purple light around high voltage transmission lines at night.
*Problems
*Leak current produces losses
*Electromagnetic interference.
*Damage to the conductor surface.
*Reduction*Use bundled conductors
*Bundled Conductor*Increasing Wire Diameter to Reduce Electric Field
*Each conductor is still stranded with a steel reinforce middle.
*Use of Spacers in bundled Ductors for Voltage Equalization
Static Shield Wire (Overhead Ground Wire)
- Same function as a lightning rod for transmission lines.
- Installed at the highest point of the transmission tower.
- Connects to ground to discharge lightning strike energy through the tower.
Distribution Line
Smaller towers and lower voltage levels compared to transmission lines.
Surface Transformer: Steps down voltage from the distribution level to consumer voltage (100-240 V).
Commercial and Industrial loads often connect directly to the distribution network.
*Voltage/Frequency Standards:*United States and Canada: 120 V, 60 Hz.
*Europe, North Africa, China: 220 V, 50 Hz.
*Japan: Both 50 Hz and 60 Hz.
Grid Control Center
- Monitors and controls power system components in real time.
- Generation, transmission, and distribution networks are monitored.
- Data collected from substations, transformers, transmission lines, protection devices, and circuit breakers.
- Control signals are sent to disconnect or reclose circuit breakers, change transformer tap settings, etc.
- Algorithms and applications are used to predict future demand.
- Energy Trading
- Predict load patterns and establish energy trades between utility companies.
- Control Center Mimic Board
- Displays system conditions, such as power flow and transmission line status.